j Check of power supply
Is there voltage 230 VAC
between the indoor terminal
block S1 and S2?
No
Yes
Replace the indoor
electronic control P.C.
board.
Rectify indoor/outdoor
connecting wire.
Yes
If light up, OK.
If fl ash, refer to 12-3.
Does the left lamp of OPERATION
INDICATOR lamp on the indoor unit
light up?
Dose LED on the inverter P.C.
board light up or fl ash?
(Refer to 12-6-3. or 12-6-7.)
No
Replace the inverter
P.C. board.
Is there voltage 280 - 370 VDC
between DB61 (+) and DB61 (–) on
the inverter P.C. board?
(Refer to 12-6-3. or 12-6-7.)
No
Check the electric parts in main circuit.
Yes
Yes
No
Disconnect the connector (CN61)
between compressor and intelligent
power module.
Turn ON power supply and press
EMERGENCY OPERATION switch.
Inverter P.C. board
(Solder side)
DB61
280 - 370 VDC
[SUZ-KA25/35VA(H)R1.TH SUZ-KA50VAR2.TH]
k Check of LEV
Press OPERATE/STOP (ON/OFF) button of the remote
controller (the set temperature is displayed) with the
remote controller headed towards the indoor unit. 1
Expansion valve operates in full-opening direction.
OK
NOTE
: After check of LEV, do the undermentioned operations.
1. Turn OFF the power supply and turn ON it again.
2. Press RESET button on the remote controller.
1. Regardless of normal or abnormal condition, a short beep
is emitted once the signal is received.
Measure each voltage between connector
pins of CN724 on the inverter P.C. board.
1. Pin (-) — Pin (+)
2. Pin (-) — Pin (+)
3. Pin (-) — Pin (+)
4. Pin (-) — Pin (+)
Is there about 3 ~ 5 VAC between each?
NOTE
: Measure the voltage by an analog
tester.
Properly fi x the LEV coil to the expansion valve.
Replace the LEV coil.
Replace the expansion valve.
Is LEV coil properly fi xed to
the expansion valve?
Does the resistance of LEV
coil have the characteristics?
(Refer to 12-4.)
Do you hear the expansion valve "click,
click·······"?
Do you feel the expansion valve vibrate
on touching it ?
Turn ON the power supply.
<Preparation of the remote controller>
While pressing both OPERATION SELECT button
and TOO COOL button on the remote controller at the
same time, press RESET button.
First, release RESET button.
And release the other two buttons after all LCD except
the set temperature in operation display section of the
remote controller is displayed after 3 seconds.
Yes
No
No
Yes
No
Yes
Yes
ON/OFF
RES
ET
TOO
WARM
TOO
COOL
MOD
E
AUTO
COOL
DRY
HEAT
FAN
VANE
SELECT
TIME
ON/OFF
TOO
WARM
TOO
COOL
h
(For wireless remote controller use model)