57
57
ACTUATOR CONTROL
10
SUZ-KA25VA(H) SUZ-KA35VA(H) SUZ-KA50VA
SUZ-KA60VA
SUZ-KA71VA
Discharge temperature thermistor
Indoor pipe temperature thermistor
Defrost thermistor
Fin temperature thermistor
Ambient temperature thermistor
Purpose
Protection
Cooling: Coil frost prevention
Heating: High pressure protection
Cooling: High pressure protection
Heating: Defrosting
Protection
Cooling: Low ambient temperature operation
Heating: Defrosting (Heater)
Compressor
LEV
Outdoor
fan motor
Indoor
fan motor
Defrost
heater
RV-coil
Sensor
Actuator
10-3. Relation between main sensor and actuator
SUZ-KA25VA(H).TH SUZ-KA35VA(H).TH
10-2. R.V. coil control
Heating . . . . . . . . . . . . . . . . . ON
Cooling . . . . . . . . . . . . . . . . . OFF
Dry . . . . . . . . . . . . . . . . . . . . OFF
ON
OFF
ON
OFF
Outdoor fan
Compressor
5 seconds
15 seconds
ON
OFF
Compressor
Outdoor fan
motor
R.V.coil
ON
OFF
ON
OFF
<COOL>
5 seconds
<HEAT>
5 seconds
ON or OFF
ON or OFF
10-1. Outdoor fan motor control
The fan motor turns ON/OFF, interlocking with the compressor.
[ON] The fan motor turns ON 5 seconds before the compressor starts up.
[OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
SUZ-KA25VA(H)R1.TH SUZ-KA35VA(H)R1.TH
e
s
o
p
r
u
P
r
o
s
n
e
S
Actuator
Compressor
LEV
Outdoor fan
motor
R.V.coil
Indoor fan
motor
Defrost
heater
Discharge temperature
thermistor
Protection
Indoor coil temperature
thermistor
Cooling: Coil frost prevention
Heating: High pressure protec-
tion
Defrost thermistor
Heating: Defrosting
Fin temperature thermistor
Protection
Ambient temperature
thermistor
Cooling: Low ambient tempera-
ture operation
Heating: Defrosting (Heater)
Outdoor heat exchanger tem-
perature thermistor
Cooling: Low ambient tempera-
ture operation
Cooling: High pressure protec-
tion
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
NOTE
: The 4-way valve reverses for 5 seconds
right before start-up of the compressor.