90
h Check of R.V. coil
First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 12-4.
In case CN721 is not connected or R.V. coil is open, voltage is generated between the terminal pins of the connector
although any signal is not being transmitted to R.V. coil.
Check if CN721 is connected.
Is there 230 VAC between CN721 and
on the inverter P.C. board 3 minutes
after the power supply is turned ON?
No
Yes
Replace the inverter
P.C. board.
Replace the 4-way valve.
Unit operates COOL mode even if it is set to HEAT mode.
Is there 230 VAC between CN721 and
on the inverter P.C. board 3 minutes
after the power supply is turned ON?
Yes
No
Replace the inverter
P.C. board.
Replace the 4-way valve.
Unit operates HEAT mode even if it is set to COOL mode.
Disconnect connector (CN61)
between the compressor and the
intelligent power module.
Turn ON the power supply and press
EMERGENCY OPERATION switch
twice (HEAT mode).
Disconnect connector (CN61)
between the compressor and the
intelligent power module.
Turn ON the power supply and
press EMERGENCY OPERATION
switch once (COOL mode).
[SUZ-KA25/35VA(H)R1.TH SUZ-KA50VAR2.TH]
Is the resistance between each ter-
minal of outdoor fan motor normal?
(Refer to 12-4.)
Check the connection between the
connector CN931 and CN932.
Disconnect CN932 from outdoor electronic control P.C. board or
the inverter P.C. board, and turn on the power supply.
Rotate the outdoor fan motor manually and measure the voltage
of CN931.
Between 1(+) and 5(-)
Between 2(+) and 5(-)
Between 3(+) and 5(-)
Does the voltage between each terminal become 5 and 0
VDC repeatedly?
Does the outdoor fan motor rotate smoothly?
Replace the outdoor fan motor.
Replace the outdoor electronic control P.C. board or the inverter
P.C. board.
Yes
Yes
No
(Fixed to either 5 or 0 VDC)
No
No
Yes
i Check of outdoor fan motor