13 - 8
MELSEC-Q
13 COMMON FUNCTIONS
13.5 External I/O signal logic switching function
This function switches the signal logic according to the external equipment connected
to the QD75MH or the external input signal (upper/lower limit switch, near-point dog) of
the servo amplifier.
For the system in which b-contact, upper limit switch, and lower limit switch are not
used, the parameter logic setting can be controlled without wiring if it is changed to a
"positive logic".
When the upper limit switch, and lower limit switch are used, ensure to use them with
b-contact.
The details shown below explain about the "External I/O signal logic switching
function".
[1] Parameter setting details
[2] Precautions on parameter setting
[1] Parameter setting details
To use the "External I/O signal logic switching function", set the parameters
shown in the following table.
Buffer memory address
Setting item
Setting details
Factory-
set initial
value
Axis
1
Axis
2
Axis
3
Axis
4
• Selection of logic of signals input from external
device to QD75MH
b0 1
Lower limit
b1 1
Upper limit
0: Negative logic,
1: Positive logic
b2
Not used
Set "0".
b3
Stop
signal
b4
External
command/
switching signal
0: Negative logic,
1: Positive logic
b5
Not used
Set "0".
b6 1
Near-point dog
signal
0: Negative logic,
1: Positive logic
b7
Not used
Set "0".
b8
Manual pulse
generator input
0: Negative logic,
1: Positive logic
Pr.22
Input signal logic
selection
b9 to b15
Not used
Set "0".
0 31
181
331
481
1: The input signal logic selection (positive/negative logic) is valid to the forced stop of the servo amplifier when
" Pr.80 External input signal selection" is set to "1".
2: Refer to Section 5.2 "List of parameters" for the information on detail settings.
[2] Precautions on parameter setting
(1) The external I/O signal logic switching parameters are validated when the
PLC READY signal [Y0] is turned OFF to ON. (The logic is negative right after
power-on.)
(2) If each signal logic is set erroneously, the operation may not be carried out
correctly.
Before setting, check the specifications of the equipment to be used.
Содержание QD75MH1
Страница 17: ...A 16 MEMO ...
Страница 19: ...MEMO ...
Страница 66: ...3 11 MELSEC Q 3 SPECIFICATIONS AND FUNCTIONS MEMO ...
Страница 97: ...4 18 MELSEC Q 4 INSTALLATION WIRING AND MAINTENANCE OF THE PRODUCT MEMO ...
Страница 102: ...5 5 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Страница 110: ...5 13 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Страница 116: ...5 19 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Страница 120: ...5 23 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Страница 124: ...5 27 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Страница 158: ...5 61 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Страница 196: ...5 99 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Страница 202: ...5 105 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Страница 208: ...5 111 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Страница 269: ...5 172 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Страница 290: ...6 21 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 291: ...6 22 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 292: ...6 23 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 293: ...6 24 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 294: ...6 25 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 295: ...6 26 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 296: ...6 27 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 297: ...6 28 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 298: ...6 29 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 299: ...6 30 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 300: ...6 31 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 301: ...6 32 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 302: ...6 33 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 303: ...6 34 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 304: ...6 35 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 305: ...6 36 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 306: ...6 37 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 307: ...6 38 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 308: ...6 39 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 309: ...6 40 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 310: ...6 41 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 311: ...6 42 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 312: ...6 43 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 313: ...6 44 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 314: ...6 45 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 315: ...6 46 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 316: ...6 47 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 317: ...6 48 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 318: ...6 49 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 319: ...6 50 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 320: ...6 51 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 348: ...7 7 MELSEC Q 7 MEMORY CONFIGURATION AND DATA PROCESS MEMO ...
Страница 352: ...7 11 MELSEC Q 7 MEMORY CONFIGURATION AND DATA PROCESS MEMO ...
Страница 363: ...MEMO ...
Страница 495: ...9 116 MELSEC Q 9 MAJOR POSITIONING CONTROL MEMO ...
Страница 557: ...11 36 MELSEC Q 11 MANUAL CONTROL MEMO ...
Страница 689: ...14 18 MELSEC Q 14 DEDICATED INSTRUCTIONS MEMO ...
Страница 751: ...Appendix 2 MELSEC Q APPENDICES MEMO ...
Страница 821: ...Appendix 72 MELSEC Q APPENDICES MEMO ...