5 - 48
MELSEC-Q
5 DATA USED FOR POSITIONING CONTROL
2) When the difference between the last command position of the
QD75MH at the time the servo stop signal turned ON and the
present value at the time the servo stop signal turned OFF is greater
than the value set in the buffer memory for the restart allowable
range setting, the positioning operation is judged as on-standby and
cannot be restarted.
ON
OFF
Operation
Error
Servo OFF
Stopping/Waitting
Last command position
Servo ON
Restart invalid
Restart valid
Axis status
Servo emergency
stop signal
(b) Processing when the servo ON signal changes from OFF to ON.
1) The positioning operation is stopped and restart can be performed
when the difference between the last command position of the
QD75MH when the servo ON signal went from OFF to ON is lower
than the value set in the buffer memory for restart allowable range
setting.
2) When the difference between the last command position of the
QD75MH at the time the servo ON signal when from ON to OFF and
the present value at the time the servo ON signal went from OFF to
ON is greater than the value set in the buffer memory for the restart
allowable range setting, the positioning operation is judged as on-
standby and cannot be restarted.
Axis status
Servo emergency
stop signal
Stopping
Positioning
Servo OFF
Stopping/Waiting
Stop command
Servo OFF
Waitting
Restart invalid
Restart valid
Servo ON
ON
OFF
Servo ON
Restart invalid
(2) Setting method
When performing restart at the time servo OFF changes to ON, set the restart
allowable range in the following buffer memory.
Setting value buffer memory
address
Axis 1 Axis 2 Axis 3 Axis 4
Item Setting
range
Default value
64
65
214
215
364
365
514
515
Pr.84
Restart allowable range
setting when servo OFF
changes to ON
0, 1 to 327680 (PLS)
0: restart not allowed
0
[Setting example]
A program in which the restart allowable range for axis 1 is set to 10000 PLS
is shown below.
DMOVP K10000 D0
DTOP H0 K64 D0 K1
Restart allowable range (10000 PLS)
is stored in D0, D1.
Data for D0, D1 is stored in buffer
memory 64, 65 of the QD75MH.
Содержание QD75MH1
Страница 17: ...A 16 MEMO ...
Страница 19: ...MEMO ...
Страница 66: ...3 11 MELSEC Q 3 SPECIFICATIONS AND FUNCTIONS MEMO ...
Страница 97: ...4 18 MELSEC Q 4 INSTALLATION WIRING AND MAINTENANCE OF THE PRODUCT MEMO ...
Страница 102: ...5 5 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Страница 110: ...5 13 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Страница 116: ...5 19 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Страница 120: ...5 23 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Страница 124: ...5 27 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Страница 158: ...5 61 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Страница 196: ...5 99 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Страница 202: ...5 105 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Страница 208: ...5 111 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Страница 269: ...5 172 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Страница 290: ...6 21 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 291: ...6 22 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 292: ...6 23 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 293: ...6 24 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 294: ...6 25 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 295: ...6 26 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 296: ...6 27 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 297: ...6 28 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 298: ...6 29 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 299: ...6 30 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 300: ...6 31 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 301: ...6 32 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 302: ...6 33 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 303: ...6 34 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 304: ...6 35 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 305: ...6 36 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 306: ...6 37 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 307: ...6 38 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 308: ...6 39 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 309: ...6 40 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 310: ...6 41 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 311: ...6 42 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 312: ...6 43 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 313: ...6 44 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 314: ...6 45 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 315: ...6 46 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 316: ...6 47 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 317: ...6 48 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 318: ...6 49 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 319: ...6 50 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 320: ...6 51 MELSEC Q 6 PLC PROGRAM USED FOR POSITIONING CONTROL ...
Страница 348: ...7 7 MELSEC Q 7 MEMORY CONFIGURATION AND DATA PROCESS MEMO ...
Страница 352: ...7 11 MELSEC Q 7 MEMORY CONFIGURATION AND DATA PROCESS MEMO ...
Страница 363: ...MEMO ...
Страница 495: ...9 116 MELSEC Q 9 MAJOR POSITIONING CONTROL MEMO ...
Страница 557: ...11 36 MELSEC Q 11 MANUAL CONTROL MEMO ...
Страница 689: ...14 18 MELSEC Q 14 DEDICATED INSTRUCTIONS MEMO ...
Страница 751: ...Appendix 2 MELSEC Q APPENDICES MEMO ...
Страница 821: ...Appendix 72 MELSEC Q APPENDICES MEMO ...