4
- 13
4.4 Wiring
4.4.2 Example of wiring the module and an encoder
4
PROCEDURES AND SETTINGS BEFORE
OPERATION
(4) Example of wiring with an encoder of voltage output type (12/24 VDC)
Figure 4.13 Example of wiring with an encoder (12/24 VDC)
According to external power supply voltage, connect load resistance between each pulse
input terminal of the QD63P6 and shielded twisted pair cable. The following table shows
conditions on load resistance.
Table 4.6 Conditions on load resistance
External voltage [V]
Load resistance [ ]
Capacity [W]
Tolerance [%]
12
820
1/4
5
24
2200
1/2
5
Shield
Shield
Phase A
Phase B
QD63P6
Phase A pulse input +
Phase B pulse input +
Phase A pulse input -
Phase B pulse input -
GND
OUT
OUT
GND
E
E
12/24 V
0 V
B19
A18
B18
A19
External power supply
12/24 VDC
0 V
Load resistance
Load resistance
Encoder
Shielded
twisted pair cable
Shielded
twisted pair cable
240 1/8 W
240 1/8 W
12 V 820 1/4 W
24 V 2200 1/2W