3.3 I/O Signals to the Programmable Controller CPU
3.3.2 Functions of I/O signals
3
SPECIFICATIONS
(2) Output signals
* 1 Set ON/OFF time such as the coincidence signal reset command (Y01) to 2ms or longer using the
following methods.
Using the timer (T) device
Set the constant scan to 2 ms or longer.
Table 3.6 Output signals
Device
No.
Signal name
Programmable controller
CPU
QD63P6
Operation
timing
Description
Y01
CH1
Coincidence signal
reset command
•Turn ON to reset the counter value coincidence (X02).
•Note that the ON/OFF time must be 2ms or longer. *1
•Turn OFF the coincidence signal reset command (Y01) when the
counter value coincidence (X02) is reset.
•For general operation, refer to Counter value large (X01) or
Y06
CH2
Y0B
CH3
Y10
CH4
Y15
CH5
Y1A
CH6
Y02
CH1
Preset command
•Turn ON to execute the preset function.
•Note that the ON/OFF time must be 2ms or longer. *1
•Turn OFF the preset command (Y02) when the preset value
setting (Un\G4 and 5) is stored to the present value A (Un\G10
and 11)/present value B (Un\G200 and 201).
•For general operation, refer to "Section 5.4".
Y07
CH2
Y0C
CH3
Y11
CH4
Y16
CH5
Y1B
CH6
Y03
CH1
Subtraction count
command
•Turn ON to perform the subtraction count at 1-phase pulse input
mode.
•If either phase B pulse is input or the subtraction count command
(Y03) turns ON, the subtraction count is performed.
•Check that the phase B pulse is input and the subtraction count
command (Y03) is OFF for addition.
•This command operates as follows when the pulse input mode is
1 multiple of 1 phase.
Y08
CH2
Y0D
CH3
Y12
CH4
Y17
CH5
Y1C
CH6
Performed by the QD63P6.
CH1 Preset
value
setting
(Un/G4 and 5)
CH1 Preset command
(Y02)
CH1 Present value A
(Un/G10 and 11)
OFF
ON
t*
100
100
0
*: t 2ms
CH1
Subtraction count command
(Y03)
CH1
Present value A
(Un/G10 and 11)
ON
OFF
ON
ON
99
98
97
100
99
A
B