16
The unit of pressure has been changed to MPa based on international SI system.
The conversion factor is : 1(MPa)=10.2(kgf/cm²)
T
otal
Electrical circuit
Refrigerant circuit
Indoor side
Outdoor
side
Representative matching
SHF
BF
W
kW
Mode
Capacity
Input
PLA-ZM100EA.UK
PLA-ZM125EA.UK
PLA-ZP140EA.UK
Cooling
9,500
2.03
Heating
11,200
2.47
Cooling
12,500
3.24
Heating
14,000
3.54
Cooling
13,400
3.61
Heating
16,000
4.25
9.18/3.08
2.51
1.00
73
43
14
5
27
19
13
35
24
0.73
0.10
10.99/3.74
2.51
0.72
80
42
3
5
20
15
40
7
6
—
—
14.33/4.91
2.68
0.93
81
44
9
5
27
19
11
35
24
0.64
0.123
15.62/5.36
2.81
0.73
92
45
1
5
20
15
44
7
6
—
—
15.99/5.34
2.72
0.90
82
45
11
5
27
19
12
35
24
0.67
0.14
18.83/6.27
2.87
0.70
88
47
0
5
20
15
45
7
6
—
—
1 , 50
230
1/3 , 50
230/400
1 , 50
230
1/3 , 50
230/400
1 , 50
230
1/3 , 50
230/400
Phase , Hz
Voltage
Current
Outdoor unit
Phase , Hz
Voltage
Current
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
V
A
V
A
MPa
MPa
°C
°C
°C
m
°C
°C
°C
°C
°C
Indoor unit
D.B.
W.B.
D.B.
D.B.
W.B.
PUZ-ZM100VKA.UK
PUZ-ZM100YKA.UK
PUZ-ZM125VKA.UK
PUZ-ZM125YKA.UK
PUZ-ZM140VKA.UK
PUZ-ZM140YKA.UK
0.47
0.45
0.52
0.50
0.66
0.64
PLA-ZM100EA.UK
PLA-ZM125EA.UK
PLA-ZM140EA.UK
5-4. STANDARD OPERATION DATA
OCH654