37
OCH750A
Abnormal point and detection method
Judgment and action
Cause
Ed
(0403)
Serial communication error
1. Abnormal if serial communication
between outdoor controller circuit board
and outdoor power circuit board is defec-
tive.
1
Breaking of wire or contact
failure of connector CN2
between the outdoor controller
circuit board and the outdoor
power circuit board
2
Breaking of wire or contact
failure of connector CN4
between the outdoor controller
circuit board and the outdoor
power circuit board
3
Defective communication circuit
of outdoor power circuit board
4
Defective communication cir-
cuit of outdoor controller circuit
board for outdoor power circuit
board
12
Check connection of each connector CN2
and CN4 between the outdoor controller
circuit board and the outdoor power circuit
board.
3
Replace outdoor power circuit board.
4
Replace outdoor controller circuit board.
1
Breaking of wire or contact
failure of connector between
outdoor controller circuit board
and M-NET board
2
Contact failure of M-NET board
power supply line
3
Noise has entered into M-NET
transmission wire.
2. Abnormal if communication between out-
door controller circuit board and M-NET
board is not available.
1
Check disconnection, looseness, or breaking of
connection wire between outdoor controller cir-
cuit board (CNMNT) and M-NET board (CN5).
2
Check disconnection, looseness, or breaking of
connection wire between outdoor controller cir-
cuit board(CNVMNT) and M-NET board (CND).
3
Check M-NET transmission wiring method.
Check Code
EF
(6607
or
6608)
Non defined check code
This code is displayed when non-defined
check code is received.
1
Noise has entered transmission
wire of remote controller.
2
Noise has entered indoor/ out-
door unit connecting wire.
3
Outdoor unit is not inverter
model.
12
Turn the power off, and on again to check.
Replace indoor controller board or outdoor
controller circuit board if abnormality is dis-
played again.
3
Replace outdoor unit with power inverter type.
P8
Pipe temperature
<Cooling mode>
Detected as abnormal when the pipe tem-
perature is not in the cooling range 3 min-
utes after compressor start and 6 minutes
after the liquid or condenser/evaporator
pipe is out of cooling range.
Note 1: It takes at least 9 minutes to detect.
Note 2: Abnormality P8 is not detected in
drying mode.
Cooling range: Indoor pipe temperature
(TH2 or TH5)−room temperature
(TH1)
[
−5.4˚F [−3˚C
]
TH: Lower temperature between liquid pipe
temperature and condenser/
evaporator temperature
<Heating mode>
When 10 seconds have passed after the
compressor starts operation and the hot
adjustment mode has finished, the unit is
detected as abnormal when condenser/
evaporator pipe temperature is not in heat-
ing range within 20 minutes.
Note 3: It takes at least 27 minutes to
detect abnormality.
Note 4: It excludes the period of defrosting
(Detection restarts when defrosting
mode is over)
Heating range: −5.4˚F [−3˚C
]
[
(Condenser/
Evaporator temperature(TH5)−
room temperature(TH1))
1
–
4
Check pipe <liquid or condenser/
evaporator> temperature with room tem-
perature display on remote controller and
outdoor controller circuit board.
Pipe <liquid or condenser/evaporator>
temperature display is indicated by setting
SW2 of outdoor controller circuit board as
follows.
Conduct temperature check with outdoor
controller circuit board after connecting
‘A-Control Service Tool(PAC-SK52ST)’.
23
Check converse connection of extension
pipe or converse wiring of indoor/outdoor
unit connecting wire.
5
Check the stop valve is opened completely.
(
)
1
2
3
4
5
6
ON
OFF
1
2
3
4
5
6
ON
OFF
1
2
3
4
5
6
ON
OFF
1
2
3
4
5
6
ON
OFF
A-Control Service Tool SW2 setting
Temperature display of indoor liquid pipe
Indoor 1
Temperature display of indoor liquid pipe
Indoor 2
Temperature display of indoor condenser/
evaporator pipe Indoor 1
Temperature display of indoor condenser/
evaporator pipe Indoor 2
1
Slight temperature difference
between indoor room tempera-
ture and pipe <liquid or con-
denser/evaporator> tempera-
ture thermistor
• Shortage of refrigerant
• Disconnected holder of pipe
<liquid or condenser/
evaporator> thermistor
• Defective refrigerant circuit
2
Converse connection of exten-
sion pipe (on plural units con-
nection)
3
Converse wiring of indoor/
outdoor unit connecting wire
(on plural units connection)
4
Defective detection of indoor
room temperature and pipe
<condenser/evaporator>
temperature thermistor
5
Stop valve is not opened com-
pletely.
Содержание PUZ-HA24NHA1
Страница 13: ...13 OCH750A 6 OUTLINES AND DIMENSIONS Unit mm in PUZ HA24NHA1 ...
Страница 14: ...14 OCH750A Unit mm in PUZ HA30NKA PUZ HA36NKA 1 1 1 ...
Страница 15: ...15 OCH750A Unit mm in PUZ HA42NKA1 1 1 1 ...
Страница 16: ...16 OCH750A 7 WIRING DIAGRAM PUZ HA24NHA1 ...
Страница 17: ...17 OCH750A PUZ HA30NKA PUZ HA36NKA ...
Страница 18: ...18 OCH750A PUZ HA42NKA1 ...
Страница 127: ...127 OCH750A ...