21
OCH750A
8-3. INDOOR – OUTDOOR CONNECTING CABLE
Note: The maximum cable length may vary depending on the condition of installation, humidity or materials, etc.
Indoor unit-Outdoor unit
Outdoor power supply
Max. 147 ft [45 m]
3
o
AWG15 (polar)
Max. 164 ft [50 m]
3
o
AWG13 (polar)
Max. 262 ft [80 m]
3
o
AWG13 (polar) and S3 separated
Wire No.
o
Size
Be sure to connect the indoor-outdoor connecting cables directly to the units (no intermediate connections).
Intermediate connections can lead to communication errors if water enters the cables and causes insufficient
insulation to ground or a poor electrical contact at the intermediate connection point.
Indoor unit-Outdoor unit
Indoor/Outdoor separate
power supply
Max. 393 ft [120 m]
2
o
Min AWG22
Wire No.
o
Size
Note: The optional indoor power supply terminal kit is necessary.
8-4. M-NET WIRING METHOD
Points to notice:
(1) Outside the unit, transmission wires should stay away from electric wires in order to prevent electromagnetic noise from making
an influence on the signal communication. Place them at intervals of more than 5 cm [2 in]. Do not put them in the same con-
duit tube.
(2) Terminal block (TB7) for transmission wires should never be connected to 208/230 V power supply. If it is connected,
electronic parts on M-NET P.C. board may be burnt out.
(3) Use 2-core x 1.25 mm
2
[AWG16] shield wire (CVVS, CPEVS) for the transmission wire. Transmission signals may not be
sent or received normally if different types of transmission wires are put together in the same multi-conductor cable. Never
do this because this may cause a malfunction.
It is acceptable if M-NET wire (non-polar, 2-cores) is arranged in addition to the wiring for A-control.
(4) Ground only one of any appliances through M-NET transmission wire (shield wire). Communication error may occur due to
the influence of electromagnetic noise.
“Ed” error will appear on the LED display of outdoor unit.
“0403” error will appear on the centralized remote controller.
If there are more than 2 grounding spots on the shield wire, noise may enter into the shield wire because the ground wire and shield
wire form one circuit and the electric potential difference occurs due to the impedance difference among grounding spots. In the case
of single spot grounding, noise does not enter into the shield wire because the ground wire and shield wire do not form 1 circuit.
To avoid communication errors caused by noise, make sure to observe the single spot grounding method described in the
installation manual.
Centralized
controller
Refrigerant
address 00
M-NET
address 01
A-control
remote
controller
A-control
remote
controller
A-control
remote
controller
Refrigerant
address 00
M-NET
address 02
Refrigerant
address 00
M-NET
address 03
Power
supply unit
Centralized
controller
M-NET transmission wire
O
Bad example (Multi spot earthing of shield wire)
Good example 1 (Single spot earthing of shield wire)
Power
supply unit
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET transmission wire
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET transmission wire
M-NET type
outdoor unit
M-NET type
outdoor unit
Good example 2 (Single spot earthing of shield wire)
Centralized
controller
Centralized
controller
Power
supply unit
Power
supply unit
Содержание PUZ-HA24NHA1
Страница 13: ...13 OCH750A 6 OUTLINES AND DIMENSIONS Unit mm in PUZ HA24NHA1 ...
Страница 14: ...14 OCH750A Unit mm in PUZ HA30NKA PUZ HA36NKA 1 1 1 ...
Страница 15: ...15 OCH750A Unit mm in PUZ HA42NKA1 1 1 1 ...
Страница 16: ...16 OCH750A 7 WIRING DIAGRAM PUZ HA24NHA1 ...
Страница 17: ...17 OCH750A PUZ HA30NKA PUZ HA36NKA ...
Страница 18: ...18 OCH750A PUZ HA42NKA1 ...
Страница 127: ...127 OCH750A ...