WIRING SPECIFICATIONS
8-1. INDOOR UNIT POWER SUPPLIED FROM OUTDOOR UNIT
The following illustrations show available connection patterns.
The outdoor unit power supply patterns vary on each model.
1:1 System
Simultaneous twin system
A
Outdoor unit power supply
B
Wiring circuit breaker or isolating switch
C
Outdoor unit
D
Indoor unit/outdoor unit connecting cords
E
Remote controller
F
Indoor unit
G
Indoor unit earth
S1
S2
L1
L2
GR
1
2
S1
S2
S3
S3
S1
S2
L1
L2
GR
1
2
S1
S2
S3
1
2
S1
S2
S3
S3
A
C
B
D
E
A
C
B
D
E
F
F
F
G
G
G
Affix a label A that is included with the manuals near each wiring diagram for the indoor and outdoor units.
Outdoor model name
HA24
HA30
HA36
HA42
Outdoor unit power supply
Single, 208/230 V, 60 Hz
Breaker size
25
35
35
40
Minimum circuit ampacity
17
24
26
36
Maximum rating of overcurrent protective device
27
40
42
60
Wiring
Wire No. x
size
Outdoor unit power supply
2 × Min AWG 12
2 × Min AWG 10
2 × Min AWG 10
2 × Min AWG 8
Outdoor unit power supply earth
1 × Min AWG 12
1 × Min AWG 10
1 × Min AWG 10
1 × Min AWG 8
Indoor unit-Outdoor unit
*1 3 × AWG 14 (polar)
3 × AWG 14 (polar)
3 × AWG 14 (polar)
3 × AWG 14 (polar)
Indoor unit earth
1 × Min AWG 14
1 × Min AWG 14
1 × Min AWG 14
1 × Min AWG 14
Remote controller-Indoor unit
*2
2 × AWG 22
(Non-polar)
2 × AWG 22
(Non-polar)
2 × AWG 22
(Non-polar)
2 × AWG 22
(Non-polar)
Circuit
rating
Outdoor unit L1-L2
*3
208/230 VAC
208/230 VAC
208/230 VAC
208/230 VAC
Indoor unit-Outdoor unit S1-S2
*3
208/230 VAC
208/230 VAC
208/230 VAC
208/230 VAC
Indoor unit-Outdoor unit S2-S3
*3
24 VDC
24 VDC
24 VDC
24 VDC
Remote controller-Indoor unit
*3
12 VDC
12 VDC
12 VDC
12 VDC
Please follow applicable federal, state, or local codes to prevent potential leakage/electric shock. Or install a ground fault interrupt for
the prevention of leakage and electric shock.
*1. Maximum 147 ft [45 m].
If AWG13 used, maximum 164 ft [50 m].
If AWG13 used and S3 separated, maximum 262 ft [80 m].
*2. The 30 ft [10 m] wire is attached in the remote controller accessory. Maximum 1500 ft [500 m].
*3. The figures are NOT always against the ground.
S3 terminal has 24 VDC against S2 terminal. However between S3 and S1, these terminals are NOT electrically insulated by the transformer
or other device.
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Use copper supply wires.
3. Use wires rated 600 V or more for the power supply cables and the indoor/outdoor unit connecting cables.
4. Install an earth line longer than power cables.
S1
S2
S3
S1
S2
S3
A-Control
Outdoor Unit
3 poles isolator
208/230 V
Single phase
Isolator
A-Control
Indoor Unit
Warning:
In the case of A-control wiring, there is high voltage potential on the S3 terminal caused by electrical circuit design that has no
electrical insulation between power line and communication signal line. Therefore, please turn off the main power supply when
servicing. And do not touch the S1, S2, S3 terminals when the power is energized. If isolator should be used between indoor unit and
outdoor unit, please use 3-pole type.
• Turn on the main power when the ambient temperature is, −4°F [−20°C] or higher.
• In below, −4°F [−20°C] condition, it needs at least 4 h standby to operate in order to warm the electrical parts.
Содержание PUZ-HA24NHA1
Страница 13: ...13 OCH750A 6 OUTLINES AND DIMENSIONS Unit mm in PUZ HA24NHA1 ...
Страница 14: ...14 OCH750A Unit mm in PUZ HA30NKA PUZ HA36NKA 1 1 1 ...
Страница 15: ...15 OCH750A Unit mm in PUZ HA42NKA1 1 1 1 ...
Страница 16: ...16 OCH750A 7 WIRING DIAGRAM PUZ HA24NHA1 ...
Страница 17: ...17 OCH750A PUZ HA30NKA PUZ HA36NKA ...
Страница 18: ...18 OCH750A PUZ HA42NKA1 ...
Страница 127: ...127 OCH750A ...