Contents

1.  Safety precautions  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  

.  Installation location   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  3

3.  Installing the outdoor unit  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  4

4.  Installing the refrigerant piping  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  5

5.  Drainage piping work  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  7

6.  Electrical work  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  7

7.  Test run  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  9

8.  Special Functions  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  10

9.  System control (Fig. 9-1)  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  11

1. Safety precautions

  Before installing the unit, make sure you read all the “Safety precau-

tions”.

  Please report to or take consent by the supply authority before connec-

tion to the system.

After installation work has been completed, explain the “Safety Precautions,” 

use,and maintenance of the unit to the customer according to the information in the 

Operation Manual and perform the test run to ensure normal operation. Both the 

Installation Manual and Operation Manual must be given to the user for keeping. 

These manuals must be passed on to subsequent users.

 : Indicates a part which must be grounded.

 Warning:

Carefully read the labels affixed to the main unit.

 Warning:

•  The unit must not be installed by the user. Ask a dealer or an authorized 

technician to install the unit. If the unit is installed incorrectly, water 

leakage,electric shock, or fire may result.

•  For installation work, follow the instructions in the Installation Manual and 

use tools and pipe components specifically made for use with R410A re

-

frigerant. The R410A refrigerant in the HFC system is pressurized 1.6 times 

the pressure of usual refrigerants. If pipe components not designed for 

R410A refrigerant are used and the unit is not installed correctly, the pipes 

may burst and cause damage or injuries. In addition, water leakage, electric 

shock, or fire may result.

•  The unit must be installed according to the instructions in order to mini-

mize the risk of damage from earthquakes, typhoons, or strong winds. An 

incorrectly installed unit may fall down and cause damage or injuries.

•  The unit must be securely installed on a structure that can sustain its 

weight. If the unit is mounted on an unstable structure, it may fall down and 

cause damage or injuries.

•  If the air conditioner is installed in a small room, measures must be taken 

to prevent the refrigerant concentration in the room from exceeding the 

safety limit in the event of refrigerant leakage. Consult a dealer regarding 

the appropriate measures to prevent the allowable concentration from be-

ing exceeded. Should the refrigerant leak and cause the concentration limit 

to be exceeded, hazards due to lack of oxygen in the room may result.

•  Ventilate the room if refrigerant leaks during operation. If refrigerant comes 

into contact with a flame, poisonous gases will be released.

•  All electric work must be performed by a qualified technician according to 

local regulations and the instructions given in this manual. The units must 

be powered by dedicated power lines and the correct voltage and circuit 

breakers must be used. Power lines with insufficient capacity or incorrect 

electrical work may result in electric shock or fire.

•  Use C1220 copper phosphorus, for copper and copper alloy seamless 

pipes, to connect the refrigerant pipes. If the pipes are not connected cor-

rectly, the unit will not be properly grounded and electric shock may result.

•  Use only specified cables for wiring. The connections must be made se-

curely without tension on the terminals. If the cables are connected or in-

stalled incorrectly, overheating or fire may result.

•  The terminal block cover panel of the outdoor unit must be firmly attached. 

If the cover panel is mounted incorrectly and dust and moisture enter the 

unit, electric shock or fire may result.

•  When installing or moving the air conditioner, use only the specified refrig

-

erant (R410A) to charge the refrigerant lines. Do not mix it with any other 

refrigerant and do not allow air to remain in the lines. Air enclosed in the 

lines can cause pressure peaks resulting in a rupture and other hazards.

•  Use only accessories authorized by Mitsubishi Electric and ask a dealer or 

an authorized technician to install them. If accessories are incorrectly in-

stalled, water leakage, electric shock, or fire may result.

•  Do not alter the unit. Consult a dealer for repairs. If alterations or repairs are 

not performed correctly, water leakage, electric shock, or fire may result.

•  The user should never attempt to repair the unit or transfer it to another 

location. If the unit is installed incorrectly, water leakage, electric shock, 

or fire may result. If the air conditioner must be repaired or moved, ask a 

dealer or an authorized technician.

•  After installation has been completed, check for refrigerant leaks. If refrig-

erant leaks into the room and comes into contact with the flame of a heater 

or portable cooking range, poisonous gases will be released.

1.1. Before installation 

 Caution:

•  Do not use the unit in an unusual environment. If the air conditioner is 

installed in areas exposed to steam, volatile oil (including machine oil), or 

sulfuric gas, areas exposed to high salt content such as the seaside, or 

areas where the unit will be covered by snow, the performance can be sig-

nificantly reduced and the internal parts can be damaged.

•  Do not install the unit where combustible gases may leak, be produced, 

flow, or accumulate. If combustible gas accumulates around the unit, fire or 

explosion may result.

•  The outdoor unit produces condensation during the heating operation. 

Make sure to provide drainage around the outdoor unit if such condensa-

tion is likely to cause damage.

 Warning:

Describes precautions that must be observed to prevent danger of injury or 

death to the user.

 Caution:

Describes precautions that must be observed to prevent damage to the unit.

•  When installing the unit in a hospital or communications office, be prepared 

for noise and electronic interference. Inverters, home appliances, high-

frequency medical equipment, and radio communications equipment can 

cause the air conditioner to malfunction or breakdown. The air conditioner 

may also affect medical equipment, disturbing medical care, and communi-

cations equipment, harming the screen display quality.

1.2. Before installation (relocation) 

 Caution:

•  Be extremely careful when transporting the units. 2 or more persons are 

needed to handle the unit, as it weighs 20 kg, 44 Ibs or more. Do not grasp 

the packaging bands. Wear protective gloves to remove the unit from the 

packaging and to move it, as you can injure your hands on the fins or the 

edge of other parts.

• Be sure to safely dispose of the packaging materials. Packaging materials, 

such as nails and other metal or wooden parts may cause stabs or other 

injuries.

•  The  base  and  attachments  of  the  outdoor  unit  must  be  periodically 

checked for looseness, cracks or other damage. If such defects are left 

uncorrected,the unit may fall down and cause damage or injuries.

•  Do not clean the air conditioner unit with water. Electric shock may result.

•  Tighten all flare nuts to specification using a torque wrench. If tightened too 

much, the flare nut can break after an extended period and refrigerant can 

leak out.

Содержание PUY-A NHA4

Страница 1: ...allation manual thoroughly before installing the air conditioner unit MANUEL D INSTALLATION Avant d installer le climatiseur lire attentivement ce manuel ainsi que le manuel d installation de l appareil intérieur pour une utilisation sûre et correcte MANUAL DE INSTALACIÓN Para un uso correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar...

Страница 2: ...door unit must be firmly attached If the cover panel is mounted incorrectly and dust and moisture enter the unit electric shock or fire may result When installing or moving the air conditioner use only the specified refrig erant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines Air enclosed in the lines can cause pressure pea...

Страница 3: ...nt lines oil deterioration or compressor breakdown may result Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil applied to the flared sections If mineral oil is mixed in the refrigeration oil oil deterioration may result Do not use refrigerant other than R410A refrigerant If another refrigerant is used the chlorine will cause the oil to deteriorate Use the following to...

Страница 4: ...r A18 and 10 mm 13 32 inch for A24 A42 space or more between the units 1 Obstacles at rear only Fig 2 12 2 Obstacles at rear and above only Fig 2 13 No more than three units must be installed side by side In addition leave space as shown Do not install the optional air outlet guides for upward airflow 3 Obstacles at front only Fig 2 14 When using an optional air outlet guide the clearance for A42 ...

Страница 5: ...52 3 8 1 The flare nut is attached to its pipe 2 The flare nut is in the outdoor unit accessory Do not use the flare nut attached If it is used a gas leakage or even a pipe ex traction may occur When bending the pipes be careful not to break them Bend radii of 100 mm 3 15 16 inch to 150 mm 5 27 32 inch are sufficient Make sure the pipes do not contact the compressor Abnormal noise or vibration may...

Страница 6: ...G Service port H Wrench hole Refrigerant pipes are protectively wrapped for A24 A42 The pipes can be protectively wrapped up to a diameter of ø90 mm 3 35 64 inch before or after connecting the pipes Cut out the knockout in the pipe cover following the groove and wrap the pipes Pipe inlet gap for A24 A42 Use putty or sealant to seal the pipe inlet around the pipes so that no gaps remain If the gaps...

Страница 7: ...y use the drain socket or the drain pan option Fig 4 8 A12 A18 A24 A42 Drain socket PAC SG61DS E Drain pan PAC SG63DP E PAC SG64DP E 6 Electrical work 6 1 Outdoor unit Fig 6 1 Fig 6 2 1 Remove the service panel 2 Wire the cables referring to the Fig 6 1 and the Fig 6 2 Fig 6 1 Fig 6 2 A12 A18 B C A A24 A36 A B C 50m 165 ft B C 8m 26 ft S3 S3 S2 S1 S2 S1 L1 L2 GR Indoor unit Outdoor unit Remote con...

Страница 8: ... CORD COVER CONDUIT COVER CABLE STRAP TERMINAL BED SERVICE PANEL CONDUIT PLATE accessory GR L2 L1 S1 S2 S3 A12 A18 A24 A42 ...

Страница 9: ... operational season The followings must be checked as well The outdoor unit is not faulty LED1 and LED2 on the control board of the outdoor unit flash when the outdoor unit is faulty Both the gas and liquid stop valves are completely open A protective sheet covers the surface of the DIP switch panel on the control board of the outdoor unit Remove the protective sheet to operate the DIP switches ea...

Страница 10: ...the liquid stop valve completely and then repeat step 2 after three minutes have passed If the refrigerant collecting operation has been completed normally LED1 and LED2 are lit the unit will remain stopped until the power supply is turned off 4 Turn off the power supply circuit breaker Brown Orange A Circuit diagram example Demand function B On site arrangement 8 2 Demand function on site modific...

Страница 11: ... Indoor unit C Master remote controller D Subordinate remote controller E Standard 1 1 Refrigerant address 00 F Simultaneous twin Refrigerant address 01 G Simultaneous twin Refrigerant address 02 E SW 1 3 6 F SW 1 3 6 G SW 1 3 6 9 System control Fig 9 1 Fig 9 1 SW1 Function table SW1 Function Operation according to switch setting ON OFF SW1 function settings 1 Compulsory defrosting Start Normal 2 ...

Страница 12: ... 16 5 29 32 15 3 4 23 5 8 39 3 8 78 23 32 39 3 8 59 1 16 19 11 16 31 1 2 5 29 32 39 3 8 59 1 16 11 13 16 19 11 16 15 3 4 23 5 8 78 23 32 118 3 32 Fig 2 6 Fig 2 7 Fig 2 8 Fig 2 9 Fig 2 10 Fig 2 11 Fig 2 12 Fig 2 13 Fig 2 14 Fig 2 15 Fig 2 16 Fig 2 17 Fig 2 18 3 15 16 7 7 8 3 15 16 7 7 8 7 7 8 11 13 16 5 29 32 9 27 32 5 29 32 9 27 32 39 3 8 59 1 16 11 13 16 19 11 16 Max 19 11 16 19 11 16 39 3 8 3 15...

Страница 13: ...ercle du bloc de sortie de l appareil extérieur doit être solidement fixé S il n est pas correctement installé et si des poussières et de l humidité s infiltrent dans l appareil un choc électrique ou un incendie peut se produire Lors de l installation ou du déplacement du climatiseur n utiliser que le réfrigérant spécifié R410A pour remplir les tuyaux de réfrigérant Ne pas le mélanger avec un autr...

Страница 14: ...de l huile ou endommager le compresseur Appliquer une petite quantité d huile ester éther ou alkylbenzène comme huile réfrigérante sur les sections évasées Le mélange d huile minérale et d huile réfrigérante peut affecter la qualité de l huile Ne pas utiliser un réfrigérant autre que le réfrigérant R410A Si c est le cas le chlore peut affecter la qualité de l huile Utiliser les outils suivants spé...

Страница 15: ...essus Fig 2 13 Ne pas installer côte à côte plus de trois appareils Espacer également les appareils comme illustré Ne pas utiliser les guidages de sortie d air en option pour un débit d air vers le haut 3 Obstacles uniquement à l avant Fig 2 14 Lors de l utilisation d un guidage de sortie d air en option le jeu des modèles A42 est de 1000 mm 39 3 8 inch minimum 4 Obstacles uniquement à l avant et ...

Страница 16: ... cela pourrait provoquer une fuite de gaz voire l extraction du tuyau Veiller à ne pas rompre les tuyaux lors de leur courbure Des rayons de courbure compris entre 100 mm 3 15 16 inch à 150 mm 5 27 32 inch suffisent Vérifier que les tuyaux ne touchent pas le compresseur Des vibrations ou des bruits anormaux pourraient se produire 1 Raccorder les tuyaux en commençant par l appareil intérieur Serrer...

Страница 17: ...ute infiltration d eau dans le matériel d isolation thermique K Poignée Stop valve Liquid side Stop valve Gas side Service port Open Close section Local pipe Sealed same way for gas side Pipe cover Do not use a wrench here Refrigerant leakage may result Use 2 wrenches here Fig 4 4 Fig 4 5 Fig 4 6 4 6 Ajout de produit réfrigérant Une charge supplémentaire n est pas nécessaire si la longueur du tuya...

Страница 18: ...age PAC SG61DS E Cuvette de drainage PAC SG63DP E PAC SG64DP E 6 Installations électriques 6 1 Appareil extérieur Fig 6 1 Fig 6 2 1 Retirer le panneau de service 2 Effectuer le câblage conformément aux figures 6 1 et 6 2 Fig 6 1 Fig 6 2 A12 A18 B C A A24 A36 A B C 50m 165 ft B C 8m 26 ft S3 S3 S2 S1 S2 S1 L1 L2 GR Indoor unit Outdoor unit Remote controller Main switch Breaker Earth For Power For P...

Страница 19: ...R CABLE STRAP TERMINAL BED SERVICE PANEL CONDUIT PLATE accessory GR L2 L1 S1 S2 S3 A12 A18 A24 A42 6 Installations électriques TERMINAL BED SANGLE A CABLE PANNEAU DE SERVICE COUVRE CABLE COUVRE TUBE PLAQUETTE DE TUBE accessoire ...

Страница 20: ...ande de l appareil extérieur clignotent lorsque celui ci est défectueux Les vannes d arrêt de liquide et de gaz sont complètement ouvertes Une feuille protectrice recouvre la surface du panneau des commutateurs DIP sur la carte de commande de l appareil extérieur Retirer la feuille protectrice pour utiliser aisément les commutateurs DIP Vérifier que tous les commutateurs DIP SW5 de changement de f...

Страница 21: ...ra ajoutée au connecteur CNDM en option sur le panneau du contrôleur de l appareil extérieur 1 Etablir le circuit comme illustré lors de l utilisation de l adaptateur d entrée ex terne PAC SC36NA Option 2 En installant les commutateurs SW7 1 et SW7 2 sur le panneau du contrôleur de l appareil extérieur la consommation électrique par rapport à la consomma tion normale sera réduite comme indiquée ci...

Страница 22: ...xtérieur B Appareil intérieur C Télécommande principale D Télécommande secondaire E Standard 1 1 Adresse de réfrigérant 00 F Jumelé simultané Adresse de réfrigérant 01 G Double simultané Adresse du réfrigérant 02 E SW 1 3 6 F SW 1 3 6 G SW 1 3 6 9 Contrôle du système Fig 9 1 Fig 9 1 SW1 Tableau des fonctions SW1 Fonction Fonctionnement selon le réglage du commutateur ON OFF Réglag es des fonctions...

Страница 23: ... 16 5 29 32 15 3 4 23 5 8 39 3 8 78 23 32 39 3 8 59 1 16 19 11 16 31 1 2 5 29 32 39 3 8 59 1 16 11 13 16 19 11 16 15 3 4 23 5 8 78 23 32 118 3 32 Fig 2 6 Fig 2 7 Fig 2 8 Fig 2 9 Fig 2 10 Fig 2 11 Fig 2 12 Fig 2 13 Fig 2 14 Fig 2 15 Fig 2 16 Fig 2 17 Fig 2 18 3 15 16 7 7 8 3 15 16 7 7 8 7 7 8 11 13 16 5 29 32 9 27 32 5 29 32 9 27 32 39 3 8 59 1 16 11 13 16 19 11 16 Max 19 11 16 19 11 16 39 3 8 3 15...

Страница 24: ...l polvo y la hume dad entran en la unidad se pueden producir una descarga eléctrica o un incendio Cuando instale o mueva el equipo de aire acondicionado utilice sólo el refrigerante indicado R410A para cargar los tubos de refrigerante No lo mezcle con otro tipo de refrigerante y vacíe completamente de aire los tu bos El aire que quede en los tubos puede provocar picos de presión que causarían su r...

Страница 25: ...sus embalajes Si el polvo los restos o la humedad entran en las tuberías de refrigeración se puede producir el deterioro del aceite o una avería en el aparato Utilice aceite de éster de éter o alquilobenceno en pequeñas cantidades para recubrir las secciones abocardadas Si se mezcla aceite mineral con aceite de refrigeración se puede deteriorar el aceite No utilice otro refrigerante que no sea R41...

Страница 26: ... la parte trasera Fig 2 12 2 Obstáculos sólo en la parte trasera y superior Fig 2 13 No se deben instalar más de tres unidades correlativas Además se debe dejar el espacio indicado No utilice las guías para salida de aire opcionales para corriente de aire hacia arriba 3 Obstáculos sólo en la parte delantera Fig 2 14 Si utiliza una guía para salida de aire opcional el espacio libre para los modelos...

Страница 27: ...ardada está en el accesorio de la unidad exterior No use la tuerca abocardada adjunta Si se usa podría ocurrir una fuga de gas o incluso la extracción de una tubería Cuando doble los tubos tenga cuidado de no romperlos Un radio de curvatura de 100 mm 3 15 16 inch a 150 mm 5 27 32 inch es suficiente Asegúrese de que las tuberías no tocan el compresor Podría producir ruidos o vibraciones extrañas 1 ...

Страница 28: ...a del tubo siguiendo la guía y envuelva los tubos Hueco de entrada de la tubería para A24 A42 Utilice masilla de minio o un sellador para sellar el extremo del tuvo alrededor del tubo para que no queden espacios vacíos Si no se tapan los vacíos se puede producir ruido o puede entrar agua o polvo y la unidad se podría averiar Fig 4 7 I Sección de llave doble No utilice una llave en ninguna otra sec...

Страница 29: ... SG64DP E 6 Trabajo eléctrico 6 1 Unidad exterior Fig 6 1 Fig 6 2 1 Extraiga el panel de servicio 2 Tienda los cables de acuerdo con la Fig 6 1 y Fig 6 2 Fig 6 1 Fig 6 2 A12 A18 B C A A24 A36 A B C 50m 165 ft B C 8m 26 ft S3 S3 S2 S1 S2 S1 L1 L2 GR Indoor unit Outdoor unit Remote controller Main switch Breaker Earth For Power For Power A24 A42 L1 GR L2 S1 S2 S3 Earth terminal Terminal block Clamp ...

Страница 30: ... TERMINAL BED SERVICE PANEL CONDUIT PLATE accessory GR L2 L1 S1 S2 S3 A12 A18 A24 A42 6 Trabajo eléctrico BANCO DE TERMINALES BRIDA DE SUJECIÓN DE CABLES PANEL DE SERVICIO CUBIERTA DE CABLES CUBIERTA DEL CONDUCTO PLACA DEL CONDUCTO accesorio ...

Страница 31: ...da a la corriente durante la temporada de funcionamiento También debe comprobar lo siguiente La unidad exterior no está averiada Los indicadores LED1 y LED2 del cuadro de control parpadean cuando la unidad exterior está averiada Tanto las válvulas de gas como las de líquido están completamente abiertas La superficie del panel de los conmutadores DIP del cuadro de control de la unidad exterior está...

Страница 32: ...o los indicadores LED1 y LED2 estén encendidos y la unidad exte rior esté parada abra completamente la válvula de parada de líquido y repita el paso 2 al cabo de tres minutos Si la operación de recuperación del refrigerante se ha completado con éxito los indicadores LED1 y LED2 están encendidos la unidad continuará parada hasta que se corte la corriente 4 Corte la corriente disyuntor Brown Orange ...

Страница 33: ...ior C Control remoto principal D Control remoto secundario E Estándar 1 1 Dirección de refrigerante 00 F Doble simultáneo Dirección de refrigerante 01 G Sistema doble simultáneo dirección de refrig erante 02 E SW 1 3 6 F SW 1 3 6 G SW 1 3 6 9 Sistema de control Fig 9 1 Fig 9 1 SW1 Tabla de funciones SW1 Función Funcionamiento según el ajuste del interruptor Activado Desactivado SW1 Ajustes de fun ...

Страница 34: ... 16 5 29 32 15 3 4 23 5 8 39 3 8 78 23 32 39 3 8 59 1 16 19 11 16 31 1 2 5 29 32 39 3 8 59 1 16 11 13 16 19 11 16 15 3 4 23 5 8 78 23 32 118 3 32 Fig 2 6 Fig 2 7 Fig 2 8 Fig 2 9 Fig 2 10 Fig 2 11 Fig 2 12 Fig 2 13 Fig 2 14 Fig 2 15 Fig 2 16 Fig 2 17 Fig 2 18 3 15 16 7 7 8 3 15 16 7 7 8 7 7 8 11 13 16 5 29 32 9 27 32 5 29 32 9 27 32 39 3 8 59 1 16 11 13 16 19 11 16 Max 19 11 16 19 11 16 39 3 8 3 15...

Страница 35: ......

Страница 36: ...00 8310 JAPAN Please be sure to put the contact address telephone number on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment BG79U896H06 Printed in Japan ...

Отзывы: