![Mitsubishi Electric PUHZ-W112VHA Скачать руководство пользователя страница 26](http://html.mh-extra.com/html/mitsubishi-electric/puhz-w112vha/puhz-w112vha_service-manual_239627026.webp)
26
OCH562D
8-4. HOW TO CHECK THE PARTS
PUHZ-W112VHA PUHZ-W112VHAR2
PUHZ-W112VHA-BS PUHZ-W112VHAR2-BS
PUHZ-W112VHAR1 PUHZ-W112VHAR3
PUHZ-W112VHAR1-BS PUHZ-W112VHAR3-BS
1
2
3
4
5
M
Gray
Orange
Red
Yellow
Black
Parts name
Checkpoints
Disconnect the connector then measure the resistance with a tester.
(At the ambient temperature of 10 to 30°C)
Thermistor (TH3) <Liquid>
Thermistor (TH4) <Discharge>
Thermistor (TH6) <Plate Hex liquid>
Thermistor (TH7) <Ambient>
Thermistor (TH8) <Heat sink>
Thermistor (TH32) <Inlet water>
Thermistor (TH33) <Suction>
Thermistor (TH34) <Comp. surface>
Normal
160 to 410 k
Ω
4.3 to 9.6 k
Ω
4.4 to 9.8 k
Ω
39 to 105 k
Ω
TH4
TH34
TH3
TH6
TH7
TH33
TH32
TH8
Abnormal
Open or short
Measure the resistance between the terminals with a tester.
(At the ambient temperature of 20°C)
Solenoid valve coil
<4-way valve>
(21S4)
Compressor
(MC)
Normal
Abnormal
Open or short
Refer to the next page.
Fan motor (MF1)
1435 ± 150
Ω
Normal
Abnormal
Open or short
0.188
Ω
Measure the resistance between the terminals with a tester.
(Winding temperature 20°C)
W
V
U
Linear expansion valve
(LEV-A) (LEV-B)
Disconnect the connector then measure the resistance with a tester.
(Winding temperature 20°C)
Normal
Gray - Black
Gray - Red
Gray - Yellow Gray - Orange
Abnormal
46 ± 3
Ω
Open or short
Содержание PUHZ-W112VHA
Страница 58: ......