background image

2

Contents

1.  Safety precautions .....................................................................................2

2.  Installation location ....................................................................................3

3.  Installing the indoor unit ............................................................................3

4.  Installing the refrigerant piping ..................................................................6

5.  Drainage piping work .................................................................................7

6.  Electrical work ...........................................................................................8

7.  Test run ....................................................................................................14

8.  System control  ........................................................................................17

9.  Installing the grille ....................................................................................18

10. Easy maintenance function .....................................................................20

1.  Safety precautions

Note:

The phrase “Wired remote controller” in this installation manual refers only to the PAR-32MAA.

If you need any information for the other remote controller, please refer to either the installation manual or initial setting manual which are included in these 

boxes.

►  Before installing the unit, make sure you read all the “Safety Precautions”. 

►  The “Safety Precautions” provide very important points regarding safety. Make sure you follow them. 

►  Please report to your supply authority or obtain their consent before connecting this equipment to the power supply system. 

Symbols used in the text

 Warning:

Describes precautions that should be observed to prevent danger of injury or 

death to the user.

 Caution:

Describes precautions that should be observed to prevent damage to the unit.

Symbols used in the illustrations 

 : Indicates a part which must be grounded.
 : Be sure not to do.

After installation work has been completed, explain the “Safety Precautions,” use, and 

maintenance of the unit to the customer according to the information in the Operation 

Manual and perform the test run to ensure normal operation. Both the Installation 

Manual and Operation Manual must be given to the user for keeping. These manuals 

must be passed on to subsequent users.

MEANINGS OF SYMBOLS DISPLAYED ON THE UNIT

WARNING

(Risk of fire)

This mark is for R32 refrigerant only. Refrigerant type is written on nameplate of outdoor unit.

In case that refrigerant type is R32, this unit uses a flammable refrigerant.

If refrigerant leaks and comes in contact with fire or heating part, it will create harmful gas and there is risk of fire.

Read the OPERATION MANUAL carefully before operation.

Service personnel are required to carefully read the OPERATION MANUAL and INSTALLATION MANUAL before operation.

Further information is available in the OPERATION MANUAL, INSTALLATION MANUAL, and the like.

 Warning:

•  Carefully read the labels affixed to the main unit. 

•  Ask a dealer or an authorized technician to install, relocate and repair the 

unit.

•  The user should never attempt to repair the unit or transfer it to another loca-

tion.

•  Do not alter the unit.

•  For installation and relocation work, follow the instructions in the Installation 

Manual and use tools and pipe components specifically made for use with 

refrigerant specified in the outdoor unit installation manual.

•  The unit must be installed according to the instructions in order to minimize 

the risk of damage from earthquakes, typhoons, or strong winds. An incor-

rectly installed unit may fall down and cause damage or injuries.

•  The unit must be securely installed on a structure that can sustain its weight. 

•  The appliance shall be stored in a well-ventilated area where the room size 

corresponds to the room area as specified for operation.

•  If the air conditioner is installed in a small room or closed room, measures must 

be taken to prevent the refrigerant concentration in the room from exceed-

ing the safety limit in the event of refrigerant leakage. Should the refrigerant 

leak and cause the concentration limit to be exceeded, hazards due to lack 

of oxygen in the room may result.

•  Keep gas-burning appliances, electric heaters, and other fire sources (igni-

tion sources) away from the location where installation, repair, and other air 

conditioner work will be performed.

  If refrigerant comes into contact with a flame, poisonous gases will be released.

•  Ventilate the room if refrigerant leaks during operation. If refrigerant comes 

into contact with a flame, poisonous gases will be released.

•  All electric work must be performed by a qualified technician according to 

local regulations and the instructions given in this manual. 

•  Use only specified cables for wiring. The wiring connections must be made 

securely with no tension applied on the terminal connections. Also, never 

splice the cables for wiring (unless otherwise indicated in this document).

  Failure to observe these instructions may result in overheating or a fire.

•  When installing or relocating, or servicing the air conditioner, use only the 

specified refrigerant written on outdoor unit  to charge the refrigerant lines. 

Do not mix it with any other refrigerant and do not allow air to remain in the 

lines.

   If air is mixed with the refrigerant, then it can be the cause of abnormal high 

pressure in the refrigerant line, and may result in an explosion and other 

hazards.

   The use of any refrigerant other than that specified for the system will cause 

mechanical failure or system malfunction or unit breakdown. In the worst 

case, this could lead to a serious impediment to securing product safety.

•  The appliance shall be installed in accordance with national wiring regulations.

•  This appliance is not intended for use by persons (including children) with 

reduced physical, sensory or mental capabilities, or lack of experience and 

knowledge, unless they have been given supervision or instruction concern-

ing use of the appliance by a  person responsible for their safety.

•  Children should be supervised to ensure that they do not play with the appli-

ance.

•  The terminal block cover panel of the unit must be firmly attached.

•  If the supply cord is damaged, it must be replaced by the manufacturer, its 

service agent or similarly qualified persons in order to avoid a hazard.

•  Use only accessories authorized by Mitsubishi Electric and ask a dealer or 

an authorized technician to install them.

•  After installation has been completed, check for refrigerant leaks. If refriger-

ant leaks into the room and comes into contact with the flame of a heater or 

portable cooking range, poisonous gases will be released.

•  Do not use means to accelerate the defrosting process or to clean, other than 

those recommended by the manufacturer.

•  The appliance shall be stored in a room without continuously operating igni-

tion sources (for example: open flames, an operating gas appliance or an 

operating electric heater).

•  Do not pierce or burn.

•  Be aware that refrigerants may not contain an odour.

•  Pipe-work shall be protected from physical damage.

•  The installation of pipe-work shall be kept to a minimum.

•  Compliance with national gas regulations shall be observed.

•  Keep any required ventilation openings clear of obstruction.

•  Do not use low temperature solder alloy in case of brazing the refrigerant 

pipes.

•  When performing brazing work, be sure to ventilate the room sufficiently.

  Make sure that there are no hazardous or flammable materials nearby.

  When performing the work in a closed room, small room, or similar location, 

make sure that there are no refrigerant leaks before performing the work.

  If refrigerant leaks and accumulates, it may ignite or poisonous gases may 

be released.

RG79F156K01_EN.indd   2

12/13/2016   1:14:16 PM

Содержание PLA-ZM-EA Series

Страница 1: ...rna MANUAL DE INSTALACIÓN Para un uso seguro y correcto lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado ΕΓΧΕΙΡΙΔΙΟ ΟΔΗΓΙΩΝ ΕΓΚΑΤΑΣΤΑΣΗΣ Για σωστή και ασφαλή χρήση διαβάστε προσεκτικά αυτό το εγχειρίδιο καθώς και το εγχειρίδιο εγκατάστασης της εξωτερικής μονάδας πριν από την εγκατάσταση της μονάδας κλιματιστικού MANUAL DE INSTALAÇÃO Para uma utilização ...

Страница 2: ...ack of oxygen in the room may result Keep gas burning appliances electric heaters and other fire sources igni tion sources away from the location where installation repair and other air conditioner work will be performed If refrigerant comes into contact with a flame poisonous gases will be released Ventilate the room if refrigerant leaks during operation If refrigerant comes into contact with a f...

Страница 3: ...n using a torque wrench If tightened too much the flare nut can break after an extended period If the unit is run for long hours when the air above the ceiling is at high tem perature high humidity dew point above 26 ºC dew condensation may be produced in the indoor unit or the ceiling materials When operating the units in this condition add insulation material 10 20 mm to the entire surface of th...

Страница 4: ...0 3 8 suspension bolts Suspension bolts are to be procured at the field Install securely ensuring that there is no clearance between the ceiling panel grille and between the main unit grille A Outer side of main unit E Grille B Bolt pitch F Ceiling C Ceiling opening G Multi functional casement option D Outer side of Grille H Entire periphery Note that the space between ceiling panel of the unit an...

Страница 5: ...9 cm long if the beams are separated by as much as 180 cm The size of the suspension bolts should be ø10 3 8 The bolts do not come with the unit 2 Ferro concrete structures Secure the suspension bolts using the method shown or use steel or wooden hang ers etc to install the suspension bolts 3 6 Unit suspension procedures Fig 3 6 Suspend the main unit as shown in the diagram Figures given in parent...

Страница 6: ...seating surface before tightening flare nut Use 2 wrenches to tighten piping connections Use refrigerant piping insulation provided to insulate indoor unit connections Insulate carefully After connecting the refrigerant piping to the indoor unit be sure to test the pipe connections for gas leakage with nitrogen gas Check that there is no refrigerant leakage from the refrigerant piping to the indoo...

Страница 7: ...s applied to the drain socket that damages the hose or causes the hose to become detached water leakage may result 1 Correct piping G Make the piping size large for grouped pip ing 2 Wrong piping 3 Grouped piping H Downward slope 1 100 or more A Insulation 9 mm or more I O D ø38 PVC TUBE for grouped piping 9 mm or more insulation B Downward slope 1 100 or more C Support metal J Up to 85 cm D O D ø...

Страница 8: ...or electrical box cover E Screw F Slide direction of the electrical box cover G Entry for power cable and indoor outdoor unit connecting cable H Secure with the cable strap I Earth cable J Indoor outdoor unit connecting terminal K Electrical wiring service panel remote controller L Entry for wired remote controller M Wired remote controller terminal N Secure with the cable strap Caution Wiring for...

Страница 9: ... used Max 50 m If 2 5 mm2 used and S3 separated Max 80 m For 200 250 outdoor unit application Max 18 m If 2 5 mm2 used Max 30 m If 4 mm2 used and S3 separated Max 50 m If 6 mm2 used and S3 separated Max 80 m 2 Max 500 m When using 2 remote controllers the maximum wiring length for the remote controller cables is 200 m 3 The figures are NOT always against the ground S3 terminal has 24 VDC against S...

Страница 10: ...onnection of all active phase conductors of the supply 2 Max 120 m 3 Max 500 m When using 2 remote controllers the maximum wiring length for the remote controller cables is 200 m 4 The figures are NOT always against the ground Notes 1 Wiring size must comply with the applicable local and national code 2 Power supply cords and indoor unit outdoor unit connecting cords shall not be lighter than poly...

Страница 11: ...nit ºC ºF A Time display 12 hour format 24 hour format B AUTO mode Single set point Dual set point C Pair No 0 3 D Backlight On Off E 4 1 Switching to the initial setting mode 1 Press the button 1 to stop the air conditioner 2 Press the button 2 The Function setting screen will be displayed and the function No A will blink Fig 6 9 Press the button 4 to change the function No 3 Check that function ...

Страница 12: ...de 1 Mode 2 Mode 3 Mode 4 Grp F1 F2 F3 F4 Function setting Cursor Cursor Request Ref address Mode 7 Mode 8 Mode 9 Mode10 Unit 1 Fig 6 13 Fig 6 14 F1 F2 F3 F4 Function setting Ref address Sending data Grp Fig 6 15 Fig 6 16 Fig 6 18 Fig 6 17 Fig 6 19 6 3 2 By wireless remote controller 1 Going to the function select mode Press the button between of 5 seconds Start this operation from the status of r...

Страница 13: ...lent low ceiling 08 1 Standard 2 Ο High ceiling 3 No of air outlets 4 directions 09 1 Ο 3 directions 2 2 directions 3 Installed options high efficiency filter Not supported 10 1 Ο Supported 2 Up down vane setting Downward setting vanes angle setup 3 11 1 Middle setting vanes angle setup 1 2 Draft less setting vanes angle setup 2 3 Ο 3D i see Sensor positioning Position 1 12 3 1 Position 2 2 Positi...

Страница 14: ...r power is turned on PLEASE WAIT is displayed for 2 minutes during system startup Normal After power is turned on PLEASE WAIT is dis played for 3 minutes then error code is displayed After startup is displayed green once and red once blink alternately F1 Incorrect connection of outdoor terminal block R S T and S1 S2 S3 After startup is displayed green once and red twice blink alternately F3 F5 F9 ...

Страница 15: ...door controller board LED 1 microcomputer power supply Indicates whether control power is supplied Make sure that this LED is always lit LED 2 remote controller power supply Indicates whether power is supplied to the wired remote controller The LED is lit only for the indoor unit that is connected to the outdoor unit that has an address of 0 LED 3 indoor outdoor unit communication Indicates whethe...

Страница 16: ... For details check the LED display of the outdoor controller board 2 UP Compressor overcurrent interruption 3 U3 U4 Open short of outdoor unit thermistors 4 UF Compressor overcurrent interruption When compressor locked 5 U2 Abnormal high discharging temperature 49C worked insufficient refrigerant 6 U1 Ud Abnormal high pressure 63H worked Overheating protection operation 7 U5 Abnormal temperature o...

Страница 17: ...tem start up Correct operation PLEASE WAIT Error code Subsequent to about 2 minutes after power on Only LED 1 is lighted LED 1 2 blink Connector for the outdoor unit s protection device is not con nected Reverse or open phase wiring for the outdoor unit s power terminal block L1 L2 L3 Display messages do not appear even when operation switch is turned ON operation lamp does not light up Only LED 1...

Страница 18: ...take grille from the grille as indicated by the arrows 2 9 2 2 Removing the corner panel Fig 9 4 Loose the 4 screws on the corner Slide the corner panel in the direction of the arrow 1 in the figure and remove the corner panel Fig 9 3 Fig 9 4 A Intake grille B Grille 1 C Intake grille levers D Grille hook E Hole for the grille s hook F Corner panel G Screw H Detail 9 3 Selection of air outlets For...

Страница 19: ...clamp into the electrical box 9 4 5 Installing signal receiver Fig 9 9 Route the lead wire white 9 poles for signal receiver corner panel from the side of the electrical box on the main unit Make sure to connect to CN90 white on the controller board Make sure that the lead wire of the signal receiver corner panel is passed through the claw of bellmouth The remaining lead wire must be held together...

Страница 20: ...t be supported by some models F1 F2 F3 F4 Check menu Cursor Service menu Error history Refrigerant volume check Refrigerant leak check Smooth maintenance Request code Smooth maintenance Begin Smooth maintenance Exit Ref address Stable mode Cursor Ref address Stable mode Stabilization Collecting Cool Heat Normal Address Cool Heat Normal Smooth maintenance Return Smooth maintenance Return Smooth mai...

Страница 21: ...is manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment RG79F156K01 Printed in UNITED KINGDOM HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN ...

Отзывы: