9.1. Checking the contents (Fig. 9-1)

•  This kit contains this manual and the following parts.

Accessory name

Q’ty

Remarks

1

Grille

1

950 × 950 (mm)

2

Installation gauge

1

(Divided into 4 parts)

3

Screw (4 × 16)

1

For PLP-6EAE, PLP-6EALE, PLP-6EALME

4

i-see Sensor corner panel

1

For PLP-6EAE, PLP-6EALE, PLP-6EALME

5

Wireless remote controller

1

For PLP-6EALM, PLP-6EALME

6

Remote controller holder

1

Included when equipped with the wire-

less remote controller.

7

LR6 AA batteries

2

Included when equipped with the wire-

less remote controller.

8

3.5 × 16 tapping screws

2

Included when equipped with the wire-

less remote controller.

9.2. Preparing to attach the grille (Fig. 9-2)

•  With the gauge 

2

 supplied with this kit, adjust and check the positioning of the main 

unit relative to the ceiling surface. If the main unit is not properly positioned relative 

to the ceiling surface, it may allow air leaks or cause condensation to collect.

•  Make sure that the opening in the ceiling is within the following tolerances: 

 860 × 860 - 910 × 910

•  Make sure that A is performed within 17 - 22 mm. Damage could result by failing to 

adhere to this range.

A

 Main unit

B

 Ceiling surface

C

 Installation gauge 

2

 (inserted into the main unit)

D

 Ceiling opening dimensions

9.2.1.  Removing the intake grille (Fig. 9-3)

•  Slide the levers in the direction indicated by the arrows 

1

 to open the intake grille.

•  Unlatch the hook that secures the grille. 

* Do not unlatch the hook for the intake grille.

•  With the intake grille in the “open” position, remove the hinge of the intake grille 

from the grille as indicated by the arrows 

2

.

9.2.2.  Removing the corner panel (Fig. 9-4)

•  Loose the 4 screws on the corner. Slide the corner panel in the direction of the arrow  

1

 in the figure and remove the corner panel.

[Fig. 9-3] [Fig. 9-4]

A

 Intake grille

B

 Grille 

1

C

 Intake grille levers

D

 Grille hook

E

 Hole for the grille’s hook

F

 Corner panel

G

 Screw

H

 Detail

9.3. Selection of air outlets

For this grille the discharge direction is available in 11 patterns. Also, by setting the 

remote controller to the appropriate settings, you can adjust the air-flow and speed. 

Select the required settings from the Table 1 according to the location in which you 

want to install the unit. (More than two directions must be selected.)

1)  Decide on the discharge direction pattern.

2)  Be sure to set the remote controller to the appropriate settings according to the 

number of air outlets and the height of the ceiling on which the main unit will be 

installed.

  (Refer to page 13.)

Note:

•  When changing the number of directions, you need an air outlet shutter plate, 

which is optional part.

•  Do not select 2 directions in a hot and humid environment. (Dew formation 

or dew drop may result.) 

9.4. Installing the grille

9.4.1.  Preparations (Fig. 9-5)

Make sure to flip 2 hooks on the grille up.

9.  Installing the grille

A

D

A=17

+5   0

B

C

Fig. 9-3

Fig. 9-2

Fig. 9-4

Fig. 9-1

Fig. 9-5

4-directional

3-directional

Blowout direction 

patterns

1 pattern: initial setting

4 patterns:

one air outlet fully closed

2-directional

Blowout direction 

patterns

6 patterns:

2 air outlet fully closed

Table 1

C

A

B

E

D

2

2

F

B

1

F

G

H

G

<Hook is in the lowered position>

<Hook is in the raised position>

1

2

3

4

When equipped with the wireless remote controller

5

6

7

8

RG79F156K01_EN.indd   18

12/13/2016   1:14:24 PM

Содержание PLA-ZM-EA Series

Страница 1: ...rna MANUAL DE INSTALACIÓN Para un uso seguro y correcto lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado ΕΓΧΕΙΡΙΔΙΟ ΟΔΗΓΙΩΝ ΕΓΚΑΤΑΣΤΑΣΗΣ Για σωστή και ασφαλή χρήση διαβάστε προσεκτικά αυτό το εγχειρίδιο καθώς και το εγχειρίδιο εγκατάστασης της εξωτερικής μονάδας πριν από την εγκατάσταση της μονάδας κλιματιστικού MANUAL DE INSTALAÇÃO Para uma utilização ...

Страница 2: ...ack of oxygen in the room may result Keep gas burning appliances electric heaters and other fire sources igni tion sources away from the location where installation repair and other air conditioner work will be performed If refrigerant comes into contact with a flame poisonous gases will be released Ventilate the room if refrigerant leaks during operation If refrigerant comes into contact with a f...

Страница 3: ...n using a torque wrench If tightened too much the flare nut can break after an extended period If the unit is run for long hours when the air above the ceiling is at high tem perature high humidity dew point above 26 ºC dew condensation may be produced in the indoor unit or the ceiling materials When operating the units in this condition add insulation material 10 20 mm to the entire surface of th...

Страница 4: ...0 3 8 suspension bolts Suspension bolts are to be procured at the field Install securely ensuring that there is no clearance between the ceiling panel grille and between the main unit grille A Outer side of main unit E Grille B Bolt pitch F Ceiling C Ceiling opening G Multi functional casement option D Outer side of Grille H Entire periphery Note that the space between ceiling panel of the unit an...

Страница 5: ...9 cm long if the beams are separated by as much as 180 cm The size of the suspension bolts should be ø10 3 8 The bolts do not come with the unit 2 Ferro concrete structures Secure the suspension bolts using the method shown or use steel or wooden hang ers etc to install the suspension bolts 3 6 Unit suspension procedures Fig 3 6 Suspend the main unit as shown in the diagram Figures given in parent...

Страница 6: ...seating surface before tightening flare nut Use 2 wrenches to tighten piping connections Use refrigerant piping insulation provided to insulate indoor unit connections Insulate carefully After connecting the refrigerant piping to the indoor unit be sure to test the pipe connections for gas leakage with nitrogen gas Check that there is no refrigerant leakage from the refrigerant piping to the indoo...

Страница 7: ...s applied to the drain socket that damages the hose or causes the hose to become detached water leakage may result 1 Correct piping G Make the piping size large for grouped pip ing 2 Wrong piping 3 Grouped piping H Downward slope 1 100 or more A Insulation 9 mm or more I O D ø38 PVC TUBE for grouped piping 9 mm or more insulation B Downward slope 1 100 or more C Support metal J Up to 85 cm D O D ø...

Страница 8: ...or electrical box cover E Screw F Slide direction of the electrical box cover G Entry for power cable and indoor outdoor unit connecting cable H Secure with the cable strap I Earth cable J Indoor outdoor unit connecting terminal K Electrical wiring service panel remote controller L Entry for wired remote controller M Wired remote controller terminal N Secure with the cable strap Caution Wiring for...

Страница 9: ... used Max 50 m If 2 5 mm2 used and S3 separated Max 80 m For 200 250 outdoor unit application Max 18 m If 2 5 mm2 used Max 30 m If 4 mm2 used and S3 separated Max 50 m If 6 mm2 used and S3 separated Max 80 m 2 Max 500 m When using 2 remote controllers the maximum wiring length for the remote controller cables is 200 m 3 The figures are NOT always against the ground S3 terminal has 24 VDC against S...

Страница 10: ...onnection of all active phase conductors of the supply 2 Max 120 m 3 Max 500 m When using 2 remote controllers the maximum wiring length for the remote controller cables is 200 m 4 The figures are NOT always against the ground Notes 1 Wiring size must comply with the applicable local and national code 2 Power supply cords and indoor unit outdoor unit connecting cords shall not be lighter than poly...

Страница 11: ...nit ºC ºF A Time display 12 hour format 24 hour format B AUTO mode Single set point Dual set point C Pair No 0 3 D Backlight On Off E 4 1 Switching to the initial setting mode 1 Press the button 1 to stop the air conditioner 2 Press the button 2 The Function setting screen will be displayed and the function No A will blink Fig 6 9 Press the button 4 to change the function No 3 Check that function ...

Страница 12: ...de 1 Mode 2 Mode 3 Mode 4 Grp F1 F2 F3 F4 Function setting Cursor Cursor Request Ref address Mode 7 Mode 8 Mode 9 Mode10 Unit 1 Fig 6 13 Fig 6 14 F1 F2 F3 F4 Function setting Ref address Sending data Grp Fig 6 15 Fig 6 16 Fig 6 18 Fig 6 17 Fig 6 19 6 3 2 By wireless remote controller 1 Going to the function select mode Press the button between of 5 seconds Start this operation from the status of r...

Страница 13: ...lent low ceiling 08 1 Standard 2 Ο High ceiling 3 No of air outlets 4 directions 09 1 Ο 3 directions 2 2 directions 3 Installed options high efficiency filter Not supported 10 1 Ο Supported 2 Up down vane setting Downward setting vanes angle setup 3 11 1 Middle setting vanes angle setup 1 2 Draft less setting vanes angle setup 2 3 Ο 3D i see Sensor positioning Position 1 12 3 1 Position 2 2 Positi...

Страница 14: ...r power is turned on PLEASE WAIT is displayed for 2 minutes during system startup Normal After power is turned on PLEASE WAIT is dis played for 3 minutes then error code is displayed After startup is displayed green once and red once blink alternately F1 Incorrect connection of outdoor terminal block R S T and S1 S2 S3 After startup is displayed green once and red twice blink alternately F3 F5 F9 ...

Страница 15: ...door controller board LED 1 microcomputer power supply Indicates whether control power is supplied Make sure that this LED is always lit LED 2 remote controller power supply Indicates whether power is supplied to the wired remote controller The LED is lit only for the indoor unit that is connected to the outdoor unit that has an address of 0 LED 3 indoor outdoor unit communication Indicates whethe...

Страница 16: ... For details check the LED display of the outdoor controller board 2 UP Compressor overcurrent interruption 3 U3 U4 Open short of outdoor unit thermistors 4 UF Compressor overcurrent interruption When compressor locked 5 U2 Abnormal high discharging temperature 49C worked insufficient refrigerant 6 U1 Ud Abnormal high pressure 63H worked Overheating protection operation 7 U5 Abnormal temperature o...

Страница 17: ...tem start up Correct operation PLEASE WAIT Error code Subsequent to about 2 minutes after power on Only LED 1 is lighted LED 1 2 blink Connector for the outdoor unit s protection device is not con nected Reverse or open phase wiring for the outdoor unit s power terminal block L1 L2 L3 Display messages do not appear even when operation switch is turned ON operation lamp does not light up Only LED 1...

Страница 18: ...take grille from the grille as indicated by the arrows 2 9 2 2 Removing the corner panel Fig 9 4 Loose the 4 screws on the corner Slide the corner panel in the direction of the arrow 1 in the figure and remove the corner panel Fig 9 3 Fig 9 4 A Intake grille B Grille 1 C Intake grille levers D Grille hook E Hole for the grille s hook F Corner panel G Screw H Detail 9 3 Selection of air outlets For...

Страница 19: ...clamp into the electrical box 9 4 5 Installing signal receiver Fig 9 9 Route the lead wire white 9 poles for signal receiver corner panel from the side of the electrical box on the main unit Make sure to connect to CN90 white on the controller board Make sure that the lead wire of the signal receiver corner panel is passed through the claw of bellmouth The remaining lead wire must be held together...

Страница 20: ...t be supported by some models F1 F2 F3 F4 Check menu Cursor Service menu Error history Refrigerant volume check Refrigerant leak check Smooth maintenance Request code Smooth maintenance Begin Smooth maintenance Exit Ref address Stable mode Cursor Ref address Stable mode Stabilization Collecting Cool Heat Normal Address Cool Heat Normal Smooth maintenance Return Smooth maintenance Return Smooth mai...

Страница 21: ...is manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment RG79F156K01 Printed in UNITED KINGDOM HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN ...

Отзывы: