6. Refrigerant piping work

6.1. Refrigerant pipe

[Fig. 6-1-1] (P.3)

Refer to the Instruction Manual that came with the outdoor unit for the restrictions on
the height difference between units and for the amount of additional refrigerant
charge.

Avoid the following places for installation where air conditioner trouble is liable to
occur.
• Where there is too much oil such as for machine or cooking.
• Salty environment as seaside areas.
• Hot-spring areas.
• Where sulfide gas exists.
• Other special atmospheric areas.
• This unit has flared connections on both indoor and outdoor sides.

[Fig. 6-1-1]

• Refrigerant pipes are used to connect the indoor and outdoor units as shown in

the figure below.

• Insulate both refrigerant and drainage piping completely to prevent condensation.

Piping preparation

• Refrigerant pipes of 3, 5, 7, 10 and 15 m [9-13/16, 16-3/8, 22-15/16, 32-1/4 and

49-3/16 ft] are available as optional items.

(1)Table below shows the specifications of pipes commercially available.

(2)Ensure that the 2 refrigerant pipes are well insulated to prevent condensation.

(3)Refrigerant pipe bending radius must be 10 cm [3-15/16 in] or more.

Caution:

Using careful insulation of specified thickness. Excessive thickness prevents
storage behind the indoor unit and smaller thickness causes dew drippage.

6.2. Flaring work

• Main cause of gas leakage is defect in flaring work.

Carry out correct flaring work in the following procedure.

6.2.1. Pipe cutting

[Fig. 6-2-1] (P.3)

• Using a pipe cutter cut the copper tube correctly.

6.2.2. Burrs removal

[Fig. 6-2-2] (P.3)

• Completely remove all burrs from the cut cross section of pipe/tube.
• Put the end of the copper tube/pipe to downward direction as you remove burrs in

order to avoid burrs drop in the tubing.

6.2.3. Putting nut on

[Fig. 6-2-3] (P.3)

• Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube

having completed burr removal.
(not possible to put them on after flaring work)

6.2.4. Flaring work

[Fig. 6-2-4] (P.3)

• Carry out flaring work using flaring tool as shown below.

Firmly hold copper tube in a die in the dimension shown in the table at above.

6.2.5. Check

[Fig. 6-2-5] (P.3)

• Compare the flared work with a figure in right side hand.
• If flare is noted to be defective, cut off the flared section and do flaring work again.

6.3. Pipe connection

[Fig. 6-3-1] (P.4)

• Apply a thin coat of refrigeration oil on the seat surface of pipe.
• For connection first align the center, then tighten the first 3 to 4 turns of flare nut.
• Use  tightening  torque  table below  as  a guideline  for  indoor unit  side  union joint

section, and tighten using two wrenches. Excessive tightening damages the flare
section.

Warning:

Be careful of flying flare nut! (Internally pressurized)
Remove the flare nut as follows:
1. Loosen the nut until you hear a hissing noise.
2. Do  not  remove  the nut  until the  gas  has  been  completely  released  (i.e.,

hissing noise stops).

3. Check that the gas has been completely released, and then remove the nut.

Outdoor unit connection

Connect pipes to stop valve pipe joint of the outdoor unit in the same manner applied
for indoor unit.
• For tightening use a torque wrench or spanner, and use the same tightening torque

applied for indoor unit.

Refrigerant pipe insulation

• After connecting refrigerant piping, insulate the joints (flared joints) with thermal

insulation tubing as shown below.

[Fig. 6-3-2] (P.4)

1. Remove and  discard  the  rubber bung  which is  inserted  in  the  end  of  the  unit

piping.

2. Flare the end of the site refrigerant piping.
3. Pull out the thermal insulation on the site refrigerant piping and replace the

insulation in its original position.

a

Indoor unit

b

Outdoor unit

Model

Pipe

Outside

diameter

Min wall

thickness

Insulation

thickness

Insulation

material

mm

inch

mm

inch

mm

inch

PEAD-

A24AA5

For liquid

9.52

3/8

0.8

1/32

8

5/16

Heat resisting

foam plastic

0.045 specific

gravity

For gas

15.88

5/8

1.0

1/32

8

5/16

PEAD-

A30AA5

For liquid

9.52

3/8

0.8

1/32

8

5/16

For gas

15.88

5/8

1.0

1/32

8

5/16

PEAD-

A36AA5

For liquid

9.52

3/8

0.8

1/32

8

5/16

For gas

15.88

5/8

1.0

1/32

8

5/16

PEAD-

A42AA5

For liquid

9.52

3/8

0.8

1/32

8

5/16

For gas

15.88

5/8

1.0

1/32

8

5/16

a

Copper tubes

b

Good

c

No good

d

Tilted

e

Uneven

f

Burred

a

Burr

b

Copper tube/pipe

c

Spare reamer

d

Pipe cutter

a

Flare nut

b

Copper tube

a

Flaring tool

b

Die

c

Copper tube

d

Flare nut

e

Yoke

Pipe diameter

(mm [in])

Dimension

A (mm [in])

B

(mm [in])

When the tool for R410A is used

Clutch type

6.35 [1/4]

0 to 0.5 [0 to 1/32]

9.1 [3/8]

9.52 [3/8]

0 to 0.5 [0 to 1/32]

13.2 [17/32]

12.7 [1/2]

0 to 0.5 [0 to 1/32]

16.6 [21/32]

15.88 [5/8]

0 to 0.5 [0 to 1/32]

19.7 [25/32]

a

Smooth all around

b

Inside is shining without any scratches

c

Even length all around

d

Too much

e

Tilted

f

Scratch on flared plane

g

Cracked

h

Uneven

i

Bad examples

Copper pipe O.D.

(mm [in])

Flare nut O.D.

(mm [in])

Tightening torque

(N·m)

ø6.35 [1/4]

17 [11/16]

14 - 18

ø9.52 [3/8]

22 [7/8]

34 - 42

ø12.7 [1/2]

26 [1-1/32]

49 - 61

ø15.88 [5/8]

29 [1-5/32]

68 - 82

A

Pipe cover (small) (accessory)

B

Caution:
Pull out the thermal insulation on the refrigerant piping at the site, insert the flare nut to flare
the end, and replace the insulation in its original position.
Take care to ensure that condensation does not form on exposed copper piping.

C

Liquid end of refrigerant piping

D

Gas end of refrigerant piping

E

Site refrigerant piping

F

Main body

G

Pipe cover (large) (accessory)

H

Thermal insulation (field supply)

I

Pull

J

Flare nut

K

Return to original position

L

Ensure that there is no gap here

M

Plate on main body

N

Band (accessory)

O

Ensure that there is no gap here. Place join upwards.

+0

-0.4 [-1/32]

KD79P399H01.book  Page 10  Tuesday, July 1, 2014  4:51 PM

Содержание PEAD-42AA5

Страница 1: ...read this installation manual thoroughly before installing the air conditioner unit FOR INSTALLER Français MANUEL D INSTALLATION Veuillez lire le manuel d installation en entier avant d installer ce climatiseur pour éviter tout accident et vous assurer d une utilisation correcte POUR L INSTALLATEUR ...

Страница 2: ...200 3 15 16 7 7 8 Fig 3 2 4 Viewed from the direction of the arrow B 777 30 5 8 S 50 2 50 2 P 700 27 9 16 Min 300 11 13 16 G H K F A I Fig 3 2 5 Unit mm in A Electric box B Ceiling C Ceiling beam D Access door 2 450 mm x 450 mm 17 3 4 in x 17 3 4 in E Access door 1 450 mm x 450 mm 17 3 4 in x 17 3 4 in F Maintenance access space G Supply air H Intake air I Bottom of indoor unit J Access door 3 K A...

Страница 3: ... b c d c A c b a d e f g h i Fig 6 2 1 Fig 6 2 2 Fig 6 2 3 Fig 6 2 4 Fig 6 2 5 a d c b e f 90 a Copper tubes d Tilted b Good e Uneven c No good f Burred a Smooth all around d Too much g Cracked b Inside is shining without any scratches e Tilted h Uneven c Even length all around f Scratch on flared plane i Bad examples a Flaring tool d Flare nut b Die e Yoke c Copper tube a Flare nut b Copper tube ...

Страница 4: ...D D E K M B H I Max 20m 65ft 1 5 2m 5 7ft G F F F B J O N F Max 300mm 11 13 16in I B C D D G F E H A 32 1 1 4 35 1 7 16 25 1 Fig 6 5 2 Fig 6 5 1 A Indoor unit B Tie band accessory C Visible part D Insertion margin E Drain hose accessory F Drain pipe O D ø32 mm 1 1 4 in PVC TUBE field supply G Insulating material field supply H Tie band accessory I To be gap free The joint section of the insulation...

Страница 5: ...utlet G Leave distance enough to prevent short cycle A In case of rear inlet B In case of bottom inlet A Filter B Bottom plate C Nail for the bottom inlet D Nail for the rear inlet S1 S2 L1 L2 G 1 2 S1 S2 S3 CN105 RED S3 A B C D E F H J G Fig 8 1 1 A Outdoor unit power supply B Earth leakage breaker C Wiring circuit breaker or isolating switch D Outdoor unit E Indoor unit outdoor unit connecting c...

Страница 6: ...controller P Indoor controller board Q Radio frequency interface is installed on Indoor controller board R CN105 RED 5P S Wiring for radio frequency interface A Indoor terminal block B Earth wire green yellow C Indoor outdoor unit connecting wire 3 core 1 5 mm2 AWG 16 or more D Outdoor terminal block 1 Connecting cable Cable 3 core 1 5 mm2 AWG 16 in conformity with Design 245 IEC 57 2 Indoor termi...

Страница 7: ...nter button B TEST button C Set Time button D Timer On Off button Set Day button E Mode selection button F Set temperature button G Timer Menu button Monitor Set button A Hour button B Minute button C TEMP button D TEMP button E ON OFF button F CHECK button B A G H K L M I J C D E F Fig 11 1 1 A Indoor unit B Union C Liquid pipe D Gas pipe E Stop valve F Outdoor unit G Refrigerant gas cylinder ope...

Страница 8: ... an injury or leakage of water due to a fire an electric shock the unit falling etc Ventilate the room if refrigerant leaks during operation If the refrigerant comes in contact with a flame poisonous gases will be released Caution Perform grounding Do not connect the ground wire to a gas pipe water pipe arrester or telephone ground wire Defective grounding could cause an electric shock Do not inst...

Страница 9: ...ate access door 4 below the electric box and the unit as shown in Fig 3 2 5 Fig 3 2 1 P 2 Fig 3 2 2 Viewed from the direction of the arrow A P 2 Fig 3 2 3 P 2 Fig 3 2 4 Viewed from the direction of the arrow B P 2 Fig 3 2 5 Viewed from the direction of the arrow B P 2 3 3 Indoor unit accessories The unit is provided with the following accessories 4 Fixing hanging bolts 4 1 Fixing hanging bolts Fig...

Страница 10: ... Internally pressurized Remove the flare nut as follows 1 Loosen the nut until you hear a hissing noise 2 Do not remove the nut until the gas has been completely released i e hissing noise stops 3 Check that the gas has been completely released and then remove the nut Outdoor unit connection Connect pipes to stop valve pipe joint of the outdoor unit in the same manner applied for indoor unit For t...

Страница 11: ...ontroller operation Make sure using a transparent hose that drain is discharged 4 After confirmation cancel the test run mode and turn off the main power If the connector is connected to the ON side of SWE disconnect it and connect it to the OFF side and attach the water supply port cover into its original position Tighten the screws of the water supply port cover to the torque of 2 0 0 2 N m Fig ...

Страница 12: ...ectric wires securely to the CN105 RED of indoor controller board Connect the electric wires securely to the corresponding terminals 5 Secure the cables with clamps inside the electric component box 6 Attach the electric component cover as it was Tighten the screws of the terminal box cover to the torque of 2 0 0 2 N m Fix power supply cable and indoor outdoor cable to control box by using buffer ...

Страница 13: ...mber 01 to 04 To set all indoor units of two three or four indoor units which are connected when these units are simultaneously in operation select AL Refer to Function table 2 2 For IR wireless remote controller Fig 8 4 2 P 7 1 Changing the external static pressure setting Be sure to change the external static pressure setting depending on the duct and the grill used 1Go to the function select mo...

Страница 14: ...least 12 hours before starting operation Starting operation immediately after turning on the main power switch can result in severe damage to internal parts Keep the power switch turned on during the operational season 9 2 Test run Refer to the installation manual that comes with each remote controller for details Mode Settings Mode no Setting no Initial setting Check Power failure automatic recov...

Страница 15: ...iving error 10 11 12 Fb Indoor unit control system error memory error etc No sound No corresponding IR wireless remote controller Wired remote controller RF thermostat Symptom Remark Beeper sounds OPERATION INDICATOR lamp flashes Number of times Check code 1 E9 Indoor outdoor unit communication error Transmitting error Outdoor unit For details check the LED display of the outdoor controller board ...

Страница 16: ...INDOOR UNIT INLET TEMP INDOOR UNIT H EXC TEMP INDOOR UNIT FILTER USE H Indoor room temperature Heat exchanger temperature Filter operation time Display Indoor unit information The filter operation time displayed is the number of hours the filter has been used since the filter reset was performed 4 Press the FILTER button 5 The data is displayed in Airflow temperature display example Blinking Waiti...

Страница 17: ... the gas cylinder If the refrigerant is charged from the gas phase composition change may occur in the refrigerant inside the cylinder and the outdoor unit In this case ability of the refrigerating cycle decreases or normal operation can be impossible However charging the liquid refrigerant all at once may cause the compressor to be locked Thus charge the refrigerant slowly To maintain the high pr...

Страница 18: ...osition etc ce qui résulterait en une blessure ou une fuite d eau Aérez le local en cas de fuite de liquide frigorigène en cours de fonctionne ment Tout contact du liquide frigorigène avec une flamme libère des gaz toxiques Attention Mettre l appareil à la terre Ne pas relier le câble de terre au tuyau de gaz d eau un parafoudre ou un câble de terre téléphonique Toute mise à la terre défectueuse p...

Страница 19: ...ement d installation pour l appareil intérieur sans poutres ou autres objets pouvant obstruer son espace d accès pour l entretien 1 Lorsqu un espace de 300 mm 11 13 16 in ou plus est disponible sous l appareil entre l appareil et le plafond Fig 3 2 1 Créez les portes d accès 1 et 2 450 450 mm 17 3 4 17 3 4 in chacune comme indiqué sur la Fig 3 2 2 La porte d accès 2 n est pas nécessaire si l espac...

Страница 20: ...êchera le stockage derrière l appareil intérieur et un isolant trop mince ne pourra éviter le suintage de condensation 6 2 Evasement La cause principale de fuite de gaz est un évasement défectueux Veuillez effectuer l évasement selon la méthode suivante 6 2 1 Couper le tuyau Fig 6 2 1 P 3 Utiliser un coupe tuyaux pour couper le tube en cuivre correctement 6 2 2 Enlever les bavures Fig 6 2 2 P 3 En...

Страница 21: ... Fig 6 5 1 P 4 Tuyaux groupés Diam ext Tuyau en cuivre mm in Diam ext raccord conique mm in Couple de serrage N m ø6 35 1 4 17 11 16 14 18 ø9 52 3 8 22 7 8 34 42 ø12 7 1 2 26 1 1 32 49 61 ø15 88 5 8 29 1 5 32 68 82 A Couvre tube petit accessoire B Précaution Sur place retirer l isolation thermique des tuyaux de réfrigérant insérer l écrou évasé pour évaser l extrémité et remettre l isolation therm...

Страница 22: ... filtre à air Retirer d abord la vis de blocage du filtre 2 Retirer la plaque inférieure 3 Attacher la plaque de fond à l arrière de l appareil Fig 7 0 3 P 5 La position des trous de fixation sur la plaque diffère de ceux de l orifice d entrée arrière Serrer les vis de la plaque de fond au couple de serrage de 1 4 0 2 N m 4 Fixer le filtre sous le corps Vérifier le côté du filtre à ajuster Fig 7 0...

Страница 23: ...ons dans le mode d emploi de l appareil inté rieur 8 3 2 Pour télécommande sans fil infrarouge 1 Lieu d installation A l abri des rayons directs du soleil A l ecart de toute source de chaleur A l abri des courants d air froids ou chauds Lieu ou la telecommande sans fil infrarouge peut etre facilement utilisee Hors de la portee des enfants Le signal peut parcourir environ 7 mètres 23 ft ligne droit...

Страница 24: ...l vers le récepteur de l unité intérieure et appuyer sur la touche Minute B 3Sélection d un mode Entrer 08 pour modifier le réglage de la pression statique externe à l aide des touches C et D Dirigez la télécommande sans fil vers le récepteur de l appareil intérieur et appuyez sur le bouton des heures A Numéro de réglage actuel 1 1 bip une seconde 2 2 bips une seconde chacun 3 3 bips une seconde c...

Страница 25: ...sistance de l isolation chute en raison de l accumulation de réfrigérant dans le compresseur La résistance dépassera 1 MΩ après que le compresseur a chauffé pendant deux ou trois heures Le temps mis par le compresseur pour chauffer varie selon les conditions atmosphériques et l accumulation de réfrigérant Pour faire fonctionner le compresseur dans lequel s est accumulé du réfrigé rant il est néces...

Страница 26: ...onction de redémarrage automatique remet l appareil en service au moment où la tension secteur est rétablie après une coupure de courant Régler la FONCTION DE REMISE EN MARCHE AUTOMATIQUE avec la télécom mande Mode No 01 Symptôme Cause Télécommande sans fil LED 1 2 CCI de l appareil extérieur VEUILLEZ ATTENDRE Pendant les 2 minutes environ qui suivent la mise sous tension Après l éclairage de la L...

Страница 27: ...écharge du comp Température ambiante extérieur Affichage Informations sur l appareil intérieur Température ambiante intérieur Affichage Température de l échangeur thermique Durée de fonctionnement du filtre La durée de fonctionnement du filtre affichée correspond au nombre d heures d utilisation du filtre depuis sa réinitialisation 4 Appuyer sur la touche FILTER 5 Les données s affichent en Exempl...

Страница 28: ... for use in the residential commercial and light industrial environment Please be sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN ...

Отзывы: