Contents

1. Safety 

precautions 

..................................................................................... 2

2. Installation 

location 

.................................................................................... 3

3.  Installing the indoor unit ............................................................................ 3
4.  Installing the refrigerant piping .................................................................. 5

5. Drainage 

piping 

work 

................................................................................. 6

6. Electrical 

work 

........................................................................................... 6

7. Test 

run 

....................................................................................................10

8.  Easy maintenance function .....................................................................13

1. Safety precautions

 

Before installing the unit, make sure you read all the “Safety precau-
tions”.

 

Please report to your supply authority or obtain their consent before 
connecting this equipment to the power supply system. 

 Warning:

Describes precautions that must be observed to prevent danger of injury or 
death to the user.

 Caution:

Describes precautions that must be observed to prevent damage to the unit.

After installation work has been completed, explain the “Safety Precautions,” use, 
and maintenance of the unit to the customer according to the information in the 
Operation Manual and perform the test run to ensure normal operation. Both the 
Installation Manual and Operation Manual must be given to the user for keeping. 
These manuals must be passed on to subsequent users.

 : Indicates a part which must be grounded.

 Warning:

Carefully read the labels af

fi

 xed to the main unit.

 Warning:

•  Ask a dealer or an authorized technician to install the unit.
• For installation work, follow the instructions in the Installation Manual and 

use tools and pipe components speci

fi

 cally made for use with refrigerant 

speci

fi

 ed in the outdoor unit installation manual.

• The unit must be installed according to the instructions in order to mini-

mize the risk of damage from earthquakes, typhoons, or strong winds. An 
incorrectly installed unit may fall down and cause damage or injuries.

•  The unit must be securely installed on a structure that can sustain its weight. 
•  If the air conditioner is installed in a small room, measures must be taken 

to prevent the refrigerant concentration in the room from exceeding the 
safety limit in the event of refrigerant leakage. Should the refrigerant leak 
and cause the concentration limit to be exceeded, hazards due to lack of 
oxygen in the room may result.

•  Ventilate the room if refrigerant leaks during operation. If refrigerant comes 

into contact with a 

fl

 ame, poisonous gases will be released.

•  All electric work must be performed by a quali

fi

 ed technician according to 

local regulations and the instructions given in this manual. 

•  Use only speci

fi

 ed cables for wiring.

•  The terminal block cover panel of the unit must be 

fi

 rmly attached.

•  Use only accessories authorized by Mitsubishi Electric and ask a dealer or 

an authorized technician to install them.

• The user should never attempt to repair the unit or transfer it to another 

location.

•  After installation has been completed, check for refrigerant leaks. If refrig-

erant leaks into the room and comes into contact with the 

fl

 ame of a heater 

or portable cooking range, poisonous gases will be released.

1.1.  Before installation (Environment)

 Caution:

• Do not use the unit in an unusual environment. If the air conditioner is in-

stalled in areas exposed to steam, volatile oil (including machine oil), or sulfu-
ric gas, areas exposed to high salt content such as the seaside, the perform-
ance can be signi

fi

 cantly reduced and the internal parts can be damaged.

• Do not install the unit where combustible gases may leak, be produced, 

fl

 ow, or accumulate. If combustible gas accumulates around the unit, 

fi

 re or 

explosion may result.

•  Do not keep food, plants, caged pets, artwork, or precision instruments in 

the direct air

fl

 ow of the indoor unit or too close to the unit, as these items 

can be damaged by temperature changes or dripping water.

• When the room humidity exceeds 80% or when the drainpipe is clogged, 

water may drip from the indoor unit. Do not install the indoor unit where 
such dripping can cause damage.

• When installing the unit in a hospital or communications office, be pre-

pared for noise and electronic interference. Inverters, home appliances, 
high-frequency medical equipment, and radio communications equipment 
can cause the air conditioner to malfunction or breakdown. The air con-
ditioner may also affect medical equipment, disturbing medical care, and 
communications equipment, harming the screen display quality.

1.2.  Before installation or relocation

 Caution:

•  Be extremely careful when transporting the units. Two or more persons are 

needed to handle the unit, as it weighs 20 kg, 44 lbs or more. Do not grasp 
the packaging bands. Wear protective gloves as you can injure your hands 
on the 

fi

 ns or other parts.

•  Be sure to safely dispose of the packaging materials. Packaging materials, 

such as nails and other metal or wooden parts may cause stabs or other 
injuries.

•  Thermal insulation of the refrigerant pipe is necessary to prevent condensa-

tion. If the refrigerant pipe is not properly insulated, condensation will be 
formed.

•  Place thermal insulation on the pipes to prevent condensation. If the drain-

pipe is installed incorrectly, water leakage and damage to the ceiling, 

fl

 oor, 

furniture, or other possessions may result.

•  Do not clean the air conditioner unit with water. Electric shock may result.
• Tighten all 

fl

 are nuts to speci

fi

 cation using a torque wrench. If tightened 

too much, the 

fl

 are nut can break after an extended period.

1.3.  Before electric work

 Caution:

•  Be sure to install circuit breakers. If not installed, electric shock may result.
•  For the power lines, use standard cables of suf

fi

 cient capacity. Otherwise, 

a short circuit, overheating, or 

fi

 re may result.

•  When installing the power lines, do not apply tension to the cables.

• Be sure to ground the unit. If the unit is not properly grounded, electric 

shock may result.

• Use circuit breakers (ground fault interrupter, isolating switch (+B fuse), 

and molded case circuit breaker) with the speci

fi

 ed capacity. If the circuit 

breaker capacity is larger than the speci

fi

 ed capacity, breakdown or 

fi

 re 

may result.

1.4.  Before starting the test run

 Caution:

•  Turn on the main power switch more than 12 hours before starting opera-

tion. Starting operation just after turning on the power switch can severely 
damage the internal parts.

• Before starting operation, check that all panels, guards and other protec-

tive parts are correctly installed. Rotating, hot, or high voltage parts can 
cause injuries.

•  Do not operate the air conditioner without the air 

fi

 lter set in place. If the air 

fi

 lter is not installed, dust may accumulate and breakdown may result.

•  Do not touch any switch with wet hands. Electric shock may result.
•  Do not touch the refrigerant pipes with bare hands during operation.
•  After stopping operation, be sure to wait at least 

fi

 ve minutes before turn-

ing off the main power switch. Otherwise, water leakage or breakdown may 
result.

01̲RG79D508H01̲EN.indd   2

01̲RG79D508H01̲EN.indd   2

2009/02/10   9:36:05

2009/02/10   9:36:05

Содержание PCA-A KA

Страница 1: ...nditioner unit MANUEL D INSTALLATION Avant d installer le climatiseur lire attentivement ce manuel ainsi que le manuel d installation de l appareil exté rieur pour une utilisation sûre et correct MANUAL DE INSTALACIÓN Para un uso seguro y correcto lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado FOR INSTALLER PARA EL INSTALADOR POUR L INSTALLATEUR ...

Страница 2: ...le gases may leak be produced flow or accumulate If combustible gas accumulates around the unit fire or explosion may result Do not keep food plants caged pets artwork or precision instruments in the direct airflow of the indoor unit or too close to the unit as these items can be damaged by temperature changes or dripping water When the room humidity exceeds 80 or when the drainpipe is clogged wat...

Страница 3: ...e outlet G Gas tubing C Right side outlet H Liquid tubing D Independent piece Removable I Rubber plug E Right drain tubing J with Joint socket 5 In case of the rear pipe arrangement make sure to remove the shaded portions from the D independent piece Then put the D independent piece back in initial position The heat exchanger might be clogged because of dust 3 2 3 Selection of suspension bolts and...

Страница 4: ...with the unit and the nuts to be locally procured 2 Set hook the unit through the suspending bolts 3 Tighten the nuts Check the unit installing condition Check that the unit is horizontal between the right and left sides Check that the front and the rear of suspending brackets are horizontal To keep drainage the unit is inclined to the suspending brackets The unit slopes continuously downward from...

Страница 5: ...ipe 5 8 ø15 88 thickness 3 64 1 0 Do not use pipes thinner than those specified above 4 2 Connecting pipes Fig 4 1 When commercially available copper pipes are used wrap liquid and gas pipes with commercially available insulation materials heat resistant to 212 F 100 C or more thickness of 1 2 in 12 mm or more The indoor parts of the drain pipe should be wrapped with polyethylene foam in sulation ...

Страница 6: ...over 7 supplied with the unit Seam taping A Drain pan B Drain tubing C Socket cover 6 D Joint socket 5 E Drain tubing cover 7 F Insertion length 1 15 32 in 37mm 5 Check for correct drainage Fig 5 3 Fill the drain pan with water of about 1 4 gal 1 L from the air outlet 6 1 Electric wiring Fig 6 1 Wiring procedures 1 Remove the tapping screw C then remove the beam 2 Remove the 2 tapping screws B the...

Страница 7: ...emote controller 6 2 1 For wired remote controller 1 Installing procedures 1 Select an installing position for the remote controller Fig 6 2 The temperature sensors are located on both remote controller and indoor unit Procure the following parts locally 2 piece switch box Thin copper conduit tube Lock nuts and bushings Fig 6 2 ARemote controller profile BRequired clearances surrounding the remote...

Страница 8: ...with something sharp at the end MODELSELECT and Model No are lighted for 3 seconds then turned off Indoor Outdoor A Model No PCA PUZ 001 PUY 033 4 Assigning a remote controller to each unit Fig 6 7 Each unit can be operated only by the assigned remote controller Make sure each pair of an indoor unit PC board and a remote controller is assigned to the same pair No 5 Wireless remote controller pair ...

Страница 9: ...or unit and press the h button A 2 Setting the unit number Press the temp buttons C and D to set the unit number 00 Direct the wireless remote controller toward the receiver of the indoor unit and press the min button B 3 Selecting a mode Enter 04 to change the power voltage setting using the temp buttons C and D Direct the wireless remote controller toward the receiver of the indoor unit and pres...

Страница 10: ... unit fan 7 Release test run by pressing the ON OFF button Stop 8 Register a telephone number The telephone number of the repair shop sales office etc to contact if an error occurs can be registered in the remote controller The telephone number will be displayed when an error occurs For registration procedures refer to the opera tion manual for the indoor unit 7 2 2 Using wireless remote controlle...

Страница 11: ...e self check ACHECK button BRefrigerant address CTEMP button DIC Indoor unit OC Outdoor unit ECheck code FUnit address 7 3 2 Wireless remote controller Fig 7 4 1 Turn on the power 2 Press the CHECK button twice Start this operation from the status of remote controller display turned off A begins to light B 00 begins to blink 3 While pointing the remote controller toward the unit s receiver press t...

Страница 12: ... the LCD If the unit cannot be operated properly after test run refer to the following table to find the cause Symptom Cause Wired remote controller LED 1 2 PCB in outdoor unit PLEASE WAIT For about 2 minutes after power on After LED 1 2 are lighted LED 2 is turned off then only LED 1 is lighted Correct operation For about 2 minutes after power on operation of the remote controller is not possible...

Страница 13: ... Stable operation Using the maintenance mode the operation frequency can be fixed and the op eration can be stabilized If the air conditioner is stopped use the following pro cedure to start this operation COOL STABLE MODE HEAT STABLE MODE STABLE MODE CANCEL Stable cooling operation Stable heating operation Stable operation cancellation Display Press the MODE button to select the operation mode Pr...

Страница 14: ...ation de gaz de com bustion autour de l appareil peut provoquer un incendie ou une explosion Ne pas placer d aliments de plantes d animaux en cage d objets d art ou d instruments de précision dans la soufflerie d air direct de l appareil intérieur ou à proximité de l appareil au risque de les endommager par des variations de température ou des gouttes d eau Si l humidité ambiante dépasse 80 ou si ...

Страница 15: ... du côté gauche G Tuyau à gaz C Sortie du côté droit H Tuyau à liquide D Pièce indépendante peut être enlevé I Bouchon en caoutchouc E Tuyau d évacuation droit J avec douille 5 Dans le cas de la préparation de la conduite arrière s assurer de retirer les parties ombrées de la pièce indépendante D Puis remettre la pièce indépendante D dans sa position initiale L échangeur thermique peut être bouché...

Страница 16: ...installation 1 Mettre en place la rondelle 1 fournie avec l appareil et les écrous sera fourni localement 2 Accrocher l appareil aux boulons de suspension 3 Serrer les écrous Vérifier la condition d installation de l appareil Vérifier que l appareil est à l horizontale entre les côtés droit et gauche Vérifier que les supports de suspension avant et arrière sont à l horizontale Pour favoriser l éco...

Страница 17: ...s fins que ceux spécifiés ci dessus 4 2 Connexion des tuyaux Fig 4 1 En cas d utilisation de tuyaux en cuivre disponibles sur le marché envelopper les tuyaux de liquide et de gaz avec de la matière isolante vendue dans le com merce sur le marché résistant à une chaleur de 212 F 100 C ou supérieure et d une épaisseur de 1 2 in 12 mm ou plus Les parties intérieures du tuyau d écoulement doivent égal...

Страница 18: ...nt dans le côté droit de la boîte de jonction A Couvercle H Connecteur du câble de mise en terre B Vis de serrage 2 I Bloc de sortie de la télécommande C Vis de serrage Faisceau i Attacher avec la bride des fils D Bride pour câbles E Carte de commande F Orifice pour l entretien des câbles G Bloc de sortie pour la connexion des appareils intérieur et extérieur 5 Vérifier que le système d évacuation...

Страница 19: ...cordement de l appareil intérieur l appareil extérieur 4 Installer un câble de terre plus long que les autres câbles 6 2 Télécommande 6 2 1 Pour la télécommande filaire 1 Méthodes d installation 1 Sélectionner l endroit d installation de la télécommande Fig 6 2 Les détecteurs de température se trouvent sur la télécommande et l appareil intérieur Fournir les pièces suivantes localement Boîte de com...

Страница 20: ...ment pendant trois secondes puis s éteignent Intérieur Extérieur A No modèle PCA PUZ 001 PUY 033 4 Attribuer une télécommande à chaque appareil Fig 6 7 Chaque appareil sera contrôlé par sa propre télécommande Vous assurer d attribuer à chaque paire de télécommande et de plaque de circuit imprimé d un appareil intérieur le même numéro de paire 5 Programmation des numéros de paires de la télécommand...

Страница 21: ...areil Appuyer sur le bouton temp C et D pour attribuer le numéro 00 à l appareil Diriger la télécommande sans fil vers le récepteur de l appareil intérieur et appuyer sur la touche min B 3 Sélection d un mode Entrer 04 pour modifier le réglage de tension d alimentation à l aide des touches temp C et D Diriger la télécommande sans fil vers le récepteur de l appareil intérieur et appuyer sur la touc...

Страница 22: ...registrez un numéro de téléphone Le numéro de téléphone de l atelier de réparation de l agence commerciale etc à contacter en cas de panne peut être enregistré dans la télécommande Le numéro de téléphone s affichera en cas d erreur Pour prendre connais sance des procédures d enregistrement consultez le mode d emploi de l appar eil intérieur 7 2 2 Utilisation de la télécommande sans fil Fig 7 2 1 M...

Страница 23: ...de clignotements bips du schéma indique le code de vérification du tableau suivant xième 1er 2ème 3ème 1er 2ème Lancement de la vérification au tomatique Signal de lancement reçu Emission de bips Schéma de sortie B Schéma de clignotement du témoin OPERATION INDICATOR témoin de fonc tionnement Bip Bip Bip Bip Bip Bip Bip Arrêt 2 5 sec environ Marche 0 5 sec Marche 0 5 sec Marche 0 5 sec Marche 0 5 ...

Страница 24: ...e fonctionnement Sur la télécommande filaire Code de vérification affiché à l écran LCD Si vous ne parvenez pas à faire fonctionner l appareil correctement après avoir mené à bien le test d essai indiqué ci dessus consulter le tableau suivant pour en trouver la cause éventuelle Symptôme Cause Télécommande filaire Témoin 1 2 circuit de l appareil extérieur PLEASE WAIT Pendant environ 2 minutes aprè...

Страница 25: ...a consommation électrique du compresseur pour les appareils in térieur et extérieur Cette fonction peut être utilisée que le climatiseur fonctionne ou non En fonctionnement les données peuvent être vérifiées pendant le fonctionnement normal ou le fonctionnement stable en mode d entretien Cette fonction ne peut pas être utilisée pendant la marche d essai La disponibilité de cette fonction dépend de...

Страница 26: ... producir un incendio o una explosión No coloque alimentos plantas animales obras de arte o instrumentos de pre cisión en la salida de aire directa de la unidad exterior o demasiado cerca de ella ya que los cambios de temperatura o el agua que gotea podrían dañarlos Cuando la humedad de la habitación supera el 80 o cuando el tubo de drenaje esté obstruido puede gotear agua de la unidad interior No...

Страница 27: ... lateral izquierda G Tubería del gas C Salida de aire lateral derecha H Tubería del líquido D Pieza independiente extraíble I Tapón de caucho E Tubería de drenaje derecha J con adaptador de junta 5 Al colocar la tubería trasera asegúrese de retirar las porciones sombreadas de la D pieza independiente A continuación vuelva a colocar la D pieza independiente en la posición original El intercambiador...

Страница 28: ...ón 3 Apriete las tuercas Comprobación de las condiciones de instalación de la unidad Comprobar que la unidad haya quedado en posición horizontal de izquierda a derecha Compruebe que la parte delantera y trasera de los soportes de suspensión se encuentran completamente horizontales Para mantener un buen drenaje la unidad queda inclinada en los soportes de suspensión La unidad se inclina continuamen...

Страница 29: ... 3 64 1 0 No utilice tubos con un grosor menor del especificado a continuación 4 2 Tubos de conexió Fig 4 1 Si se utilizan tubos de cobre convencionales envuelva los tubos de gas y líquido con materiales aislantes resistente al calor hasta 212 F 100 C o más espesor de 1 2 in 12 mm o más Las piezas interiores del tubo de drenaje tienen que estar envueltas en materi ales aislantes de espuma de polie...

Страница 30: ...inistrado con la unidad Tapando la junta A Depósito de drenaje B Tubo de drenaje C Tapón del adaptador 6 D Adaptador de junta 5 E Tapón del tubo de drenaje 7 F Longitud de inserción 1 15 32 in 37mm 5 Comprobación de un drenaje correcto Fig 5 3 Llene el depósito de drenaje con 1 litro de agua aproximadamente vertida desde la salida de aire 6 1 Cableado eléctrico Fig 6 1 Procedimientos de cableado 1...

Страница 31: ...e tierra más largo que el resto de los cables 6 2 Control remoto 6 2 1 Para el controlador remoto cableado 1 Procedimientos de instalación 1 Seleccione una posición adecuada para el control remoto Fig 6 2 Hay sensores de temperatura tanto en el control remoto como en la unidad interior Tendrá que adquirir las siguientes piezas no suministradas con la unidad Caja de interruptores para dos piezas Tu...

Страница 32: ... iluminan durante tres segundos y a continuación desaparecen Interior Exterior A Número de modelo PCA PUZ 001 PUY 033 4 Asignación de un mando a distancia para cada unidad Fig 6 7 Cada unidad responderá sólo a las señales del mando a distancia asignado Cerciórese de que cada mando a distancia tenga el mismo código que la unidad interior que debe gobernar 5 Procedimiento para establecer el número d...

Страница 33: ...tón h A 2 Configuración del número de unidad Pulse el botón TEMP C y D para seleccionar el número de unidad 00 Apunte el mando a distancia hacia el receptor de la unidad interior y pulse el botón min button B 3 Cómo seleccionar un modo Introduzca 04 para cambiar el ajuste de voltaje de alimentación con los botones TEMP C y D Oriente el controlador remoto inalámbrico hacia el receptor de la unidad ...

Страница 34: ... el botón de activación desac tivación ON OFF ACTIVAR DESACTIVAR Parar 8 Registre un número de teléfono El controlador remoto permite registrar el número de teléfono de la tienda de electrodomésticos distribuidor etc con quien se deba contactar en caso de error El número aparecerá si se produce algún error Para conocer el proced imiento de registro consulte el manual de instrucciones de la unidad ...

Страница 35: ...OC Unidad exterior E Código de comprobación F Dirección de unidad 7 3 2 Para controlador remoto inalámbrico Fig 7 4 1 Encienda el aparato 2 Pulse el botón CHECK dos veces Inicie el procedimiento con la pantalla de estado del controlador remoto apagada A Se encenderán B 00 empieza a parpadear 3 Apunte con el mando a distancia hacia el receptor de la unidad y pulse el botón h El número de veces que ...

Страница 36: ...o se puede activar la unidad adecuadamente después de haberse llevado a cabo la ejecución de prueba consulte la tabla siguiente para suprimir la causa Síntoma Causa Controlador remoto cableado LED 1 2 tarjeta de circuito impreso en unidad exterior PLEASE WAIT Durante aproximadamente 2 minutos después del encendido Se iluminan los LED 1 y 2 y a continuación el LED 2 se apaga y sólo queda encendido ...

Страница 37: ...nsumo de corriente del compresor para las unidades interiores y exterior Esta función se puede utilizar independientemente de si el aire acondicionado esté funcionando o no Durante el funcionamiento del aire acondicionado los datos se pueden comprobar durante el funcionamiento normal o durante el funcionamiento estable del modo de mantenimiento Esta función no se puede utilizar durante la prueba d...

Страница 38: ......

Страница 39: ......