70
Specifications
List of functions that can/cannot be used in combination
Schedule
Unit or Zone ON/OFF timer
Unit Auto-OFF
timer
Auto return
Set temp. range limit
Lock operations
Night setback
Energy saving
(Assist function)
Schedule
1
4
Unit or Zone
ON/OFF timer
1
2
Unit Auto-OFF timer
3
Auto return
2
6
1
Set temp. range limit
2
5
Lock operations
Night setback
4
2
3
6
5
7
Energy saving
(Assist function)
1
7
: The functions can be used in combination.
: Restricted : The functions cannot be used in combination.
1 : The “Schedule” setting is not effective because “ON/OFF timer” has the higher priority.
2 : The “Auto return” function cannot be used because the “Set temp. range limit” setting has the
higher priority.
1 : The “Auto return” function will not be executed when the units are operated in the “Set
temperature offset” mode.
2 : The “Night setback” function will not be executed when the unit has been turned on by “Unit ON/
OFF timer.”
When Zone ON/OFF timer is set, both of the functions will remain effective.
3 : The “Unit Auto-OFF timer” function will not be executed while the “Night setback” function is
executed.
4 : The “Night setback” function will not be executed when the unit has been turned on by “Schedule”
settings.
5 : The “Set temp. range limit” settings will not be effective while the “Night setback” function is
executed.
6 : The “Auto return” function will not be executed while the “Night setback” function is executed.
7 : The “Energy saving” function will not be executed while the “Night setback” function is executed.