![Mitsubishi Electric PAC-ZC40H Скачать руководство пользователя страница 38](http://html.mh-extra.com/html/mitsubishi-electric/pac-zc40h/pac-zc40h_instruction-book_240744038.webp)
38
Function settings
Night setback
The Night setback function starts heating operation when a given group is stopped and
the room temperature drops below the specified lower limit temperature. Also, this function
starts cooling operation when a given group is stopped and the room temperature rises
above the specified upper limit temperature.
* If the room temperature is measured by the return air temperature sensor on the air conditioning unit,
the measured value may not be an accurate representation of the temperature in the room, especially
when the air conditioning unit is stopped and the room air is stagnant. When this is the case, use
optional sensor or remote controller sensor to measure the room temperature.
Button operation
1
Select
[Night setback]
from the Menu.
The Night setback function will not work in the
following cases:
when the unit is in operation,
when the Night setback function is disabled,
during an error, during test run, when the clock is
not set.
The Night setback function will be cancelled when
the Unit ON/OFF operation, operation mode
setting, or set temperature setting is made from
the remote controller while the Night setback
function is executed.
2
The default setting is “Disabled.”
To activate the Night setback function, touch the
[Disabled]
button to change it to
[Enabled]
.
To continue making detailed settings, touch to
access the settings screen.