(1102)
(1) High discharging temperature
Abnormal if discharge temperature ther-
mistor (TH4) exceeds 125
:
or 110
:
continuously for 5 minutes.
Abnormal if pressure detected by high
pressure sensor and converted to satu-
ration temperature exceeds 40
:
during
defrosting and discharge temperature
thermistor (TH4) exceeds 110
:
.
(2) Refrigerant shortage abnormality
1
When the conditions of below detecting
mode
1
or
2
are satisfied (1st detec-
tion) during the compressor operation,
the compressor stops and restarts
operation in 3 minutes.
<Detecting
mode
1
>
When the below conditions are satisfied
completely.
1. Compressor is operating in HEAT
mode.
2. Discharge superheat is 70
;
or more.
3. Difference of outer temperature
thermistor (TH7) and outdoor piping
temp. thermistor (TH3) applies to the
formula of (TH7-TH3)<5
;
.
4. High-pressure sensor is below about
2.04MPa.
<Detecting
mode
2
>
When the below conditions are satisfied
completely.
1. Compressor is operating.
2. When cooling, discharge superheat
is 80
;
or more.
When heating, discharge superheat
is 90
;
or more.
High pressure sensor is below about
2.32MPa.
2
When the conditions of detecting mode
1
and
2
are satisfied again (2nd detec-
tion) within 30 minutes since the com-
pressor has stopped, it stops abnor-
mally. In this time, <U2> is displayed.
3
When the conditions of detecting
mode
1
and
2
are satisfied again after
30 minutes since the compressor has
stopped (1st time), it becomes the 1st
detection and same performance as
above
1
.
4
It is being delay for abnormal stop dur-
ing 30 minutes since the compressor
has stopped. In this time, check delay
code <U2> will be displayed.
1
Overheated compressor opera-
tion caused by shortage of
refrigerant
2
Defective operation of stop
valve
3
Defective thermistor
4
Defective outdoor controller
board
5
Defective action of linear
expansion valve
1
Gas leakage, Gas shortage
2
When heating operation, scant
refrigerant operation
(When heating, airflow or ther-
mo OFF are mixed-operation,
it cause a refrigerant shortage
operation.)
3
Ball valve performance failure
(Not fully opened.)
4
Error detection of discharge
super heat
1) High-pressure sensor defec-
tive
2) Discharge temperature ther-
mistor defective
3) Thermistor input circuit
defective and high-pressure
sensor defective in multi
controller board
5
Error detection of TH7/TH3
1) Thermistor defective
2) Thermistor input circuit
defective in multi controller
board
1
Check intake superheat.
Check leakage of refrigerant.
Charge additional refrigerant.
2
Check if stop valve is fully open.
34
Turn the power off and check if U3 is dis-
played when the power is turned on again.
When U3 is displayed, refer to “Judgement
and action” for U3.
5
Check linear expansion valve.
Refer to 9-6.
1
Check the refrigerant amount.
2
Check the operation condition and refrigerant
amount.
3
Check the ball valve is fully opened.
4
1) Check the ball valve is fully opened.
2) Check the resistance of discharge tem-
perature thermistor.
3) According to “Monitoring function for out-
door unit”, set the SW2 and check the
high-pressure sensor level.
According to “Monitoring function for outdoor
unit”, set the SW2 and check the discharge
temp. thermistor level.
When the high-pressure sensor and dis-
charge temp. thermistor are normal, if the
above mentioned detecting pressure level
and temp. are big different from the actual
pressure and temp., replace the multi control-
ler board.
5
1) Check the resistance of thermistor.
2) According to “Monitoring function for out-
door unit”, set the SW2 and check the out-
door pipe temp. thermistor level.
3) According to “Monitoring function for out-
door unit”, set the SW2 and check the
outer temp. thermistor level.
Error Code
Abnormal point and detection method
Judgment and action
Case
U3
(5104)
Open/short circuit of discharge
temperature thermistor (TH4)
Abnormal if open (3
:
or less) or short
(217
:
or more) is detected during com-
pressor operation.
(Detection is inoperative for 10 minutes
of compressor starting process and for 10
minutes after and during defrosting.)
1
Disconnection or contact failure
of connector (TH4) on the out-
door controller circuit board
2
Defective thermistor
3
Defective outdoor controller
circuit
board
1
Check connection of connector (TH4) on the
outdoor controller circuit board.
Check breaking of the lead wire for thermistor
(TH4). Refer to 9-6.
2
Check resistance value of thermistor (TH4)or
temperature by microprocessor.
(Thermistor/TH4: Refer to 9-6.)
(SW2 on A-Control Service Tool:
Refer to 9-8.)
3
Replace outdoor controller board.
Содержание PAC-AK31BC
Страница 90: ...90 15 2 FUNCTIONAL PARTS BRANCH BOX PAC AK50BC 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 18 17 16 19 20 ...
Страница 92: ...92 15 3 FUNCTIONAL PARTS BRANCH BOX PAC AK30BC 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 18 17 16 ...
Страница 98: ...98 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 18 17 16 19 20 16 3 FUNCTIONAL PARTS BRANCH BOX PAC AK50BC PAC AK51BC ...
Страница 100: ...100 16 4 FUNCTIONAL PARTS BRANCH BOX PAC AK30BC PAC AK31BC 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 18 17 16 ...
Страница 160: ...Related Links Model Number MXZ8A140VA 3 MXZ 8A_Parts_Catalog_ OC316E MXZ 8A_Service_Manual_ OC316E ...