9-3. SELF-DIAGNOSIS ACTION TABLE
<Abnormalities detected when the power is put on>
(Note 1) Refer to indoor unit section for code P and code E.
Error Code
Abnormal point and detection method
Case
Judgment and action
None
—
1
No voltage is supplied to termi-
nal block (TB1) of outdoor unit.
a) Power supply breaker is
turned off.
b) Contact failure or disconnec-
tion of power supply terminal
c) Open phase (L or N phase)
2
Electric power is not charged to
power supply terminal of out-
door power circuit board.
a) Contact failure of power
supply terminal
b) Open phase on the outdoor
power circuit board
Disconnection of connector
SC-R or SC-S
3
Electric power is not supplied
to outdoor controller circuit
board.
a) Disconnection of connector
(CNDC)
4
Disconnection of reactor (DCL)
5
Disconnection of outdoor noise
filter circuit board or parts fail-
ure in outdoor noise filter circuit
board
6
Defective outdoor power circuit
board
7
Defective outdoor controller
circuit
board
1
Check following items.
a) Power supply breaker
b) Connection of power supply terminal
block.
(TB1)
c) Connection of power supply terminal
block.
(TB1)
2
Check following items.
a) Connection of power supply terminal
block.
(TB1)
b) Connection of terminal on outdoor
power circuit board.
Disconnection of connector SC-R or
SC-S
Refer to 9-7.
3
Check
connection of the connector (CNDC)
on the outdoor controller circuit board.
Check
connection of the connector, CNDC
on the outdoor power circuit board.
Refer to 9-7.
4
Check
connection of reactor. (DCL)
Check connection of “L1” and “L2”
on the active filter module. (ACTM)
5
a) Check connection of outdoor noise filter
circuit board.
b) Replace outdoor noise filter circuit board.
Refer to 9-7.
6
Replace outdoor power circuit board.
7
Replace controller board (When items
above are checked but the units cannot be
repaired.)
F3
(5202)
63L connector open
Abnormal if 63L connector circuit is open
for 3 minutes continuously after power sup-
ply
63L: Low-pressure switch
1
Disconnection or contact failure
of 63L connector on outdoor
controller circuit board
2
Disconnection or contact failure
of 63L
3
63L is operating due to refriger-
ant leakage or defective parts.
4
Defective outdoor controller
circuit
board
1
Check connection of 63L connector on
outdoor controller circuit board.
Refer to 9-7.
2
Check the 63L side of connecting wire.
3
Check refrigerant pressure.
Charge additional refrigerant.
Check continuity by tester.
Replace the parts if the parts are defective.
4
Replace outdoor controller circuit board.
F9
(4119)
2 connector open
Abnormal if both 63H and 63L connector
circuits are open for 3 minutes continuously
after power supply
63H: High-pressure switch
63L: Low-pressure switch
1
Disconnection or contact failure
of connector (63H, 63L) on
outdoor controller circuit board.
2
Disconnection or contact failure
of 63H, 63L
3
63H and 63L are operating due
to defective parts.
4
Defective outdoor controller
board
1
Check connection of connector (63H,63L) on
outdoor controller circuit board.
Refer to 9-7.
2
Check the 63H and 63L side of connecting
wire.
3
Check continuity by tester.
Replace the parts if the parts are defective.
4
Replace outdoor controller circuit board.
F5
(5201)
63H connector open
Abnormal if 63H connector circuit is open
for 3 minutes continuously after power sup-
ply
63H: High-pressure switch
1
Disconnection or contact failure
of 63H connector on outdoor
controller circuit board
2
Disconnection or contact failure
of 63H
3
63H is operating due to defec-
tive parts.
4
Defective outdoor controller
circuit
board
1
Check connection of 63H connector on
outdoor controller circuit board.
Refer to 9-7.
2
Check the 63H side of connecting wire.
3
Check continuity by tester.
Replace the parts if the parts are defective.
4
Replace outdoor controller circuit board.
Содержание PAC-AK31BC
Страница 90: ...90 15 2 FUNCTIONAL PARTS BRANCH BOX PAC AK50BC 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 18 17 16 19 20 ...
Страница 92: ...92 15 3 FUNCTIONAL PARTS BRANCH BOX PAC AK30BC 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 18 17 16 ...
Страница 98: ...98 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 18 17 16 19 20 16 3 FUNCTIONAL PARTS BRANCH BOX PAC AK50BC PAC AK51BC ...
Страница 100: ...100 16 4 FUNCTIONAL PARTS BRANCH BOX PAC AK30BC PAC AK31BC 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 18 17 16 ...
Страница 160: ...Related Links Model Number MXZ8A140VA 3 MXZ 8A_Parts_Catalog_ OC316E MXZ 8A_Service_Manual_ OC316E ...