5
en
M [kg]
Amin [m²]
1.0
3
1.5
4.5
2.0
6
2.5
7.5
3.0
9
3.5
12
4.0
15.5
4.5
20
5.0
24
5.5
29
6.0
35
6.5
41
7.0
47
7.5
54
Wall mounted
h0
]
1.8 [m]
Ceiling concealed
Cassette
Ceiling suspended
h0
]
2.2 [m]
h0
]
2.2 [m]
h0
]
2.2 [m]
1-4-2. Minimum installation area for Indoor units
Install in a room with a floor area of Amin or more, corresponding to refrigerant quantity M (factory-charged refri locally added refrigerant).
Install the indoor unit so that the height from the floor to the bottom of the indoor unit is h0;
for wall mounted: 1.8 m or more;
for ceiling suspended, cassette and ceiling concealed: 2.2 m or more.
When installing floor standing, refer to indoor unit Installation manual.
There are restrictions in installation height for each model, so read the installation manual for the particular unit.
For wall mounted, ceiling suspended, cassette and concealed
WG79A798H02_01En.indd 5
2020/02/10 17:32:03
Содержание MXZ-4F83VF
Страница 172: ...A4_white_tombo indd 1 2018 08 09 14 11 29 ...
Страница 173: ...A4_white_tombo indd 1 2018 08 09 14 11 29 ...
Страница 174: ...A4_white_tombo indd 1 2018 08 09 14 11 29 ...