3.
Obstacles in front (blowing) only
When there is an obstacle in front of the
unit as shown in the figure, open space
above, behind, and on the sides of the unit
is required.
2.
Front (blowing) side open
As long as space indicated in the
figure is provided, it is allowed to
install the unit where obstacles
are behind and on the sides of
the unit. (No obstacle above
the unit)
FREE SPACE REQUIRED AROUND OUTDOOR UNIT
500 or more
200 or more
350 or more
100 or more
1.
Obstacles above
When there is no obstacle in front and on
the sides of the unit, it is allowed to install
the unit where an obstacle is above the
unit only if the space shown in the figure
is provided.
100 or more
500 or more
100 or more
Service space
350 or more
350 or more
6.
Service space
Provide space for service and maintenance as shown in the figure.
500 or more
100 or more
• When installing the unit in an area that is enclosed with walls such as a
verandah, be sure to have enough space as shown below.
In this case, the air conditioning capacity and power consumption might
deteriorate.
• When there is a lack of airflow or there is a possibility of becoming short
cycle, install an outlet guide and make sure there is enough space behind
of the unit.
• When installing two or more units, do not install the units in front or behind
each other.
100 or more
200 or more
350 or more
500 or more
500 or more
(Unit: mm)
5.
Obstacles in front, behind and on side(s)
4.
Obstacles in front and behind
The unit can be used by attach-
ing an optional outdoor blowing
guide (PAC-SH96SG-E) (but
both sides and top are open).
500 or more
100 or more
Blowing guide (PAC-SH96SG-E)
Height of the obstacle is 1200 or less
•
R32 is heavier than air—as well as other refrigerants—so tends to accumulate at the base (in the vicinity of the floor). If R32 accumulates around base, it may reach
a flammable concentration in case room is small. To avoid ignition, maintaining a safe work environment is required by ensuring appropriate ventilation. If a refriger-
ant leak is confirmed in a room or an area where there is insufficient ventilation, refrain from using of flames until the work environment can be improved by ensuring
appropriate ventilation.
• Refrigerant pipes connection shall be accessible for maintenance purposes.
• Install outdoor units in a place where at least one of the four sides is open, and in a sufficiently large space without depressions.
OK
OK
OK
NG
WG79A798H02_01En.indd 3