En-6

4-4. LOCKING THE OPERATION MODE OF THE AIR CONDITIONER (COOL, DRY, HEAT)

4-5. LOWERING THE OPERATION NOISE OF THE OUTDOOR UNIT

•  Description of the function:

  With this function, once the operation mode is locked to either COOL/DRY mode 

or HEAT mode, the air conditioner operates in that mode only.

*  Changing the setting is required to activate this function. Please explain about 

this function to your customers and ask them whether they want to use it.

[How to lock the operation mode]

1) Be sure to turn off the main power for the air conditioner before making the 

setting.

2) Set the “3” of SW1 on the outdoor controller board to ON to enable this function.

3) To lock the operation mode in COOL/DRY mode, set the “4” of SW1 on the 

outdoor controller board to OFF. To lock the operation in HEAT mode, set the 

same switch to ON.

4) Turn on the main power for the air conditioner.

•  Description of the function:

  With this function, the operating noise of the outdoor unit can be lowered by reducing the operation load, for example, during nighttime in COOL mode. 

However, please note that the cooling and heating capacity may lower if this function is activated.

*  Changing the setting is required to activate this function. Please explain about this function to your customers and ask them whether they want to use it.

Lower the operating noise

[How to lower the operating noise]

1) Be sure to turn off the main power for the air conditioner before making the setting.

2) Set the “5” of SW1 on the outdoor controller board to ON to enable this function.

3) Turn on the main power for the air conditioner.

4-6. TEST RUN

•  Test runs of the indoor units should be performed individually. See the installation manual coming with the indoor unit, and make sure all the units operate 

properly.

•  If the test run with all the units is performed at once, possible erroneous connections of the refrigerant pipes and the indoor/outdoor unit connecting wires 

cannot be detected. Thus, be sure to perform the test run one by one.

About the restart protective mechanism

Once the compressor stops, the restart preventive device operates so the compressor will not operate for 3 minutes to protect the air conditioner. 

Wiring/piping correction function

This unit has a wiring/piping correction function which corrects wiring and piping combination. When there is possibility of incorrect wiring and piping combi

-

nation, and confirming the combination is difficult, use this function to detect and correct the combination by following the procedures below.
Make sure that the following is done.

•  Power is supplied to the unit.

•  Stop valves are open.

Note:

During detection, the operation of the indoor unit is controlled by the outdoor unit. During detection, the indoor unit automatically stops operation. This is not 

a malfunction.

When relocating or disposing of the air conditioner, pump down the system following the procedure below so that no refrigerant is released into the atmosphere.

1) Turn off the breaker.

2) Connect the gauge manifold valve to the service port of the stop valve on the gas pipe side of the outdoor unit.

3) Fully close the stop valve on the liquid pipe side of the outdoor unit.

4) Turn on the breaker.

5) Start the emergency COOL operation on all the indoor units.

6) When the pressure gauge shows 0.05 to 0 MPa [Gauge] (approx. 0.5 to 0 kgf/cm

2

), fully close the stop valve on the gas pipe side of the outdoor unit and 

stop the operation. (Refer to the indoor unit installation manual about the method for stopping the operation.)

  * If too much refrigerant has been added to the air conditioner system, the pressure may not drop to 0.05 MPa [Gauge] (approx. 0.5 kgf/cm

2

), or the protection 

function may operate due to the pressure increase in the high-pressure refrigerant circuit. If this occurs, use a refrigerant collecting device to collect all of 

the refrigerant in the system, and then recharge the system with the correct amount of refrigerant after the indoor and outdoor units have been relocated.

7) Turn off the breaker. Remove the pressure gauge and the refrigerant piping.

4-7. EXPLANATION TO THE USER

•  Using the OPERATING INSTRUCTIONS, explain to the user how to use the air conditioner (how to use the remote controller, how to remove the air filters, 

how to remove or put the remote controller in the remote controller holder, how to clean, precautions for operation, etc.).

•  Recommend the user to read the OPERATING INSTRUCTIONS carefully.

Procedure

Press the piping/wiring correction switch (SW871) 1 minute or more after turning on the 

power supply.
•  Correction completes in 10 to 15 minutes. When the correction is completed, its result 

is shown by LED indication. Details are described in the following table.

•  To cancel this function during its operation, press the piping/wiring correction switch 

(SW871) again.

•  When the correction completed without error, do not press the piping/wiring correction 

switch (SW871) again.

When the result is “Not completed”, press the piping/wiring correction switch (SW871) again 

to cancel this function. Then, confirm the wiring and piping combination in a conventional 

manner by operating the indoor units one by one.
•  The operation is done while the power is supplied. Make sure not to contact parts other 

than the switch, including the P.C. board. This may cause electric shock or burn by hot 

parts and live parts around the switch. Contacting the live parts may cause P.C. board 

damage.

•  To prevent electronic control P.C. board damage, make sure to perform static elimination 

before operating this function.

•  This function does not operate when the outside temperature is 0°C or below.

LED indication during detection:

LED1

(Red)

LED2

(Yellow)

LED3 

(Green)

Lit

Lit

Once

Result of piping/wiring correction function

LED1

(Red)

LED2

(Yellow)

LED3

(Green)

Result

Lit

Not lit

Lit

Completed

(Problem corrected or 

normal)

Once

Once

Once

Not completed 

(Detection failed)

Other indications

Refer to “SAFETY PRE

-

CAUTIONS WHEN LED 

BLINKS” located behind 

the top panel.

When pumping down the refrigerant, stop the compressor before disconnecting the refrigerant pipes.

The compressor may burst and cause injury if any foreign substance, such as air, enters the pipes.

 WARNING

5.  PUMPING DOWN

HEAT

COOL/DRY

LED
SW1

SW871

SW2

SW1

ON

1   2   3   4   5   6

SW1

ON

1   2   3   4   5   6

Содержание MXZ-2E52VAD2

Страница 1: ...ner MXZ 2E52VAD2 MXZ 3E54VAD2 MXZ 4E71VAD2 English Installation Manual For INSTALLER This manual only describes the installation of outdoor unit When installing the indoor unit refer to the installation manual of indoor unit ...

Страница 2: ...the system will cause mechanical failure system malfunction or unit breakdown In the worst case this could lead to a serious impediment to securing product safety n Do not discharge the refrigerant into the atmosphere If refrigerant leaks during installation ventilate the room If refrigerant comes in contact with a fire harmful gas could be generated n Check that the refrigerant gas does not leak ...

Страница 3: ...E INSTALLATION LOCATION Where it is not exposed to strong wind Where airflow is good and dustless Where rain or direct sunshine can be avoided as much as possible Where neighbours are not annoyed by operation sound or hot air Where rigid wall or support is available to prevent the increase of opera tion sound or vibration Where there is no risk of combustible gas leakage When installing the unit b...

Страница 4: ...or unit Units should be installed by licensed contractor according to local code requirements Outdoor unit installation Air inlet 169 500 Air inlet 4 10 21 Oval holes 396 Air outlet 840 Unit mm 361 330 1 6 DRAIN PIPING FOR OUTDOOR UNIT Please perform the drain piping work only when draining from one place 1 Choose one hole to discharge drain and install the drain socket 1 to the hole 2 Close the r...

Страница 5: ...ling devise DRED For further information consult your dealer This unit supports 3 Demand Response Modes DRMs DRM1 DRM2 and DRM3 CAUTION To prevent malfunction caused by noise route the cord connecting this unit to DRED and the power supply cord as parallel as possible Do not connect the demand control transmission cable to the terminal block for power supply Do not pull extremely bend or apply str...

Страница 6: ...ue 19 6 to 29 4 N m 200 to 300 kgf cm Gauge manifold valve for R410A Compound pressure gauge for R410A 0 101MPa 760 mmHg Handle Low Handle High Vacuum pump for R410A Close Open Hexagonal wrench 4 to 5 turns Stop valve for LIQUID Pressure gauge for R410A Precautions when us ing the control valve When attaching the control valve to the service port valve core may deform or loosen if excess pres sure...

Страница 7: ...rvice port of the stop valve on the gas pipe side of the outdoor unit 3 Fully close the stop valve on the liquid pipe side of the outdoor unit 4 Turn on the breaker 5 Start the emergency COOL operation on all the indoor units 6 When the pressure gauge shows 0 05 to 0 MPa Gauge approx 0 5 to 0 kgf cm2 fully close the stop valve on the gas pipe side of the outdoor unit and stop the operation Refer t...

Страница 8: ...BH79N583H01 HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN ...

Отзывы: