background image

En-2

3. 

Obstacles in front (blowing) only

When there is an obstacle in front of 

the unit as shown in the figure, open 

space above, behind, and on the sides 

of the unit is required.

2. 

Front (blowing) side open

As long as space indicated 

in  the  figure  is  provided,  it 

is allowed to install the unit 

where obstacles are behind 

and on the sides of the unit. 

(No obstacle above the unit)

1-3. SELECTING OPTIONAL DIFFERENT-DIAMETER JOINTS

If the diameter of connection pipe does not match the port size of outdoor unit, use optional different-diameter joints according to the following table.

Port size of outdoor unit

Optional different-diameter joints 

(port size of outdoor unit → diameter of connection pipe)

MXZ-2E52

MXZ-3E54

MXZ-4E71

Liquid / Gas

6.35 (1/4) → 9.52 (3/8) : PAC-493PI

9.52 (3/8) → 12.7 (1/2) : MAC-A454JP-E

9.52 (3/8) → 15.88 (5/8) : PAC-SG76RJ-E

12.7 (1/2) → 9.52 (3/8) : MAC-A455JP-E

12.7 (1/2) → 15.88 (5/8) : MAC-A456JP-E

Refer to the installation manual of indoor unit for the diameter of connection 

pipe of indoor unit.

A UNIT

6.35 (1/4) / 12.7 (1/2)

A - B UNIT

A - C UNIT

B - D UNIT

6.35 (1/4) / 9.52 (3/8)

*1  Connect to the power switch which has a gap of 3 mm or more when open 

to interrupt the source power phase. (When the power switch is shut off, it 

must interrupt all phases.)

*2  Use wires in conformity with design 60245 IEC 57. Use the indoor/outdoor 

connecting wire in conformity with the wire specifications specified in the 

installation manual of the indoor unit.

*3  Never use pipes with thickness less than specified. The pressure resistance 

will be insufficient.

*4  Use a copper pipe or a copper-alloy seamless pipe.

*5  Be careful not to crush or bend the pipe during pipe bending.

*6  Refrigerant pipe bending radius must be 100 mm or more.

*7  Insulation material : Heat resisting foam plastic 0.045 specific gravity

*8  Be sure to use the insulation of specified thickness. Excessive thickness 

may cause incorrect installation of the indoor unit and insufficient thickness 

may cause dew drippage.

*9  If the outdoor unit is installed higher than the indoor unit, max. height 

difference is reduced to 10 m.

*10 If pipe length exceeds 40 m, additional refrigerant (R410A) charge is re

-

quired. (No additional charge is required for pipe length less than 40 m.)

  Additional refrigerant = A × (pipe length (m) - 40)

FREE SPACE REQUIRED AROUND OUTDOOR UNIT

1-4. SELECTING THE INSTALLATION LOCATION

•  Where it is not exposed to strong wind.

•  Where airflow is good and dustless.

•  Where rain or direct sunshine can be avoided as much as possible.

•  Where neighbours are not annoyed by operation sound or hot air.

•  Where rigid wall or support is available to prevent the increase of opera-

tion sound or vibration.

•  Where there is no risk of combustible gas leakage.

•  When installing the unit, be sure to secure the unit legs.

•  Where it is at least 3 m away from the antenna of TV set or radio. Opera

-

tion of the air conditioner may interfere with radio or TV reception in areas 

where reception is weak. An amplifier may be required for the affected 

device.

•  Install the unit horizontally.

•  Please install it in an area not affected by snowfall or blowing snow. In 

areas with heavy snow, please install a canopy, a pedestal and/or some 

baffle boards.

Note:

It is advisable to make a piping loop near outdoor unit so as to reduce 

vibration transmitted from there.

Note: 

When operating the air conditioner in low outside temperature, be sure 

to follow the instructions described below.

•  Never install the outdoor unit in a place where its air inlet/outlet side 

may be exposed directly to wind.

•  To prevent exposure to wind, install the outdoor unit with its air inlet 

side facing the wall.

• 

To prevent exposure to wind, it is recommended to install a baffle 

board on the air outlet side of the outdoor unit.

Avoid the following places for installation where air conditioner trouble 

is liable to occur.

•  Where flammable gas could leak.

•  Where there is much machine oil.

•  Where oil is splashed or where the area is filled with oily smoke 

(such as cooking areas and factories, in which the properties of 

plastic could be changed and damaged).

•  Salty places such as the seaside.

•  Where sulfide gas is generated such as hot spring, sewage, waste 

water.

•  Where there is high-frequency or wireless equipment.

•  

Where there is emission of high levels of VOCs, including phthalate 

compounds, formaldehyde, etc., which may cause chemical cracking.

500 or more

200 or more

350 or more

100 or more

1. 

Obstacles above

When there is no obstacle in front and 

on the sides of the unit, it is allowed 

to install the unit where an obstacle is 

above the unit only if the space shown 

in the figure is provided.

500 or more

100 or more

(Unit: mm (inch))

4. 

Obstacles in front and behind

The unit can be used by at

-

taching an optional outdoor 

blowing guide (MAC-

856SG) (but both sides and 

top are open).

100 or more

500 or more

Blowing guide (MAC-856SG)

(Unit: mm)

Содержание MXZ-2E52VAD2

Страница 1: ...ner MXZ 2E52VAD2 MXZ 3E54VAD2 MXZ 4E71VAD2 English Installation Manual For INSTALLER This manual only describes the installation of outdoor unit When installing the indoor unit refer to the installation manual of indoor unit ...

Страница 2: ...the system will cause mechanical failure system malfunction or unit breakdown In the worst case this could lead to a serious impediment to securing product safety n Do not discharge the refrigerant into the atmosphere If refrigerant leaks during installation ventilate the room If refrigerant comes in contact with a fire harmful gas could be generated n Check that the refrigerant gas does not leak ...

Страница 3: ...E INSTALLATION LOCATION Where it is not exposed to strong wind Where airflow is good and dustless Where rain or direct sunshine can be avoided as much as possible Where neighbours are not annoyed by operation sound or hot air Where rigid wall or support is available to prevent the increase of opera tion sound or vibration Where there is no risk of combustible gas leakage When installing the unit b...

Страница 4: ...or unit Units should be installed by licensed contractor according to local code requirements Outdoor unit installation Air inlet 169 500 Air inlet 4 10 21 Oval holes 396 Air outlet 840 Unit mm 361 330 1 6 DRAIN PIPING FOR OUTDOOR UNIT Please perform the drain piping work only when draining from one place 1 Choose one hole to discharge drain and install the drain socket 1 to the hole 2 Close the r...

Страница 5: ...ling devise DRED For further information consult your dealer This unit supports 3 Demand Response Modes DRMs DRM1 DRM2 and DRM3 CAUTION To prevent malfunction caused by noise route the cord connecting this unit to DRED and the power supply cord as parallel as possible Do not connect the demand control transmission cable to the terminal block for power supply Do not pull extremely bend or apply str...

Страница 6: ...ue 19 6 to 29 4 N m 200 to 300 kgf cm Gauge manifold valve for R410A Compound pressure gauge for R410A 0 101MPa 760 mmHg Handle Low Handle High Vacuum pump for R410A Close Open Hexagonal wrench 4 to 5 turns Stop valve for LIQUID Pressure gauge for R410A Precautions when us ing the control valve When attaching the control valve to the service port valve core may deform or loosen if excess pres sure...

Страница 7: ...rvice port of the stop valve on the gas pipe side of the outdoor unit 3 Fully close the stop valve on the liquid pipe side of the outdoor unit 4 Turn on the breaker 5 Start the emergency COOL operation on all the indoor units 6 When the pressure gauge shows 0 05 to 0 MPa Gauge approx 0 5 to 0 kgf cm2 fully close the stop valve on the gas pipe side of the outdoor unit and stop the operation Refer t...

Страница 8: ...BH79N583H01 HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN ...

Отзывы: