94
MXZ-3C/4C/5C
LED1(Red) LED2(Yellow)
Lighted
Twice
Outdoor power system
Lighted
3 times
Discharge temperature
thermistor
• Refer to 11-6. "Check of outdoor thermistors".
Outdoor heat exchanger
temperature thermistor
Defrost thermistor
Lighted
7 times
Nonvolatile memory data
• Replace the electronic control P.C. board.
Lighted
8 times
Current sensor
• Replace the power board.
Lighted
11 times
Communication error
between P.C. boards
• Check the connecting wire between electronic control
P.C. board and the power board.
Lighted
12 times
Zero cross detecting
circuit
• Check the connecting wire between electronic control
P.C. board, noise filter P.C. board and the power board.
Abnormal point / Condition
Remedy
A short circuit is detected in the thermistor during operation, or an open
circuit is detected in the thermistor 5 minutes (in cooling) and 10
minutes (in heating) after compressor start-up.
A short circuit is detected in the thermistor during operation, or an open
circuit is detected in the thermistor 5 minutes after compressor start-up.
• Replace the electronic control P.C. board.
Indication
Overcurrent protection cut-out operates 3 consecutive times
within 1 minute after the compressor gets started, or converter protection
or bus-bar voltage protection cut-out operates 3 consecutive times
within 3 minutes after start-up.
A short circuit is detected in the thermistor during operation, or an open
circuit is detected in the thermistor 10 minutes after compressor start-up.
Condition
The nonvolatile memory data cannot be read properly.
Fin temperature
thermistor
P.C board temperature
thermistor
Lighted
4 times
Ambient temperature
thermistor
Current sensor protection cut-out operates 2 consecutive times.
Communication error occurs twice between the electronic control
P.C. board and power board for more than 10 seconds.
The protection cut-out of the zero cross detecting circuit operates 10
consecutive times.
A short or open circuit is detected in the thermistor during operation.
A short or open circuit is detected in the thermistor during operation.
5 times
Lighted
IPM protection
Lock protection
3 times
Not lighted
Discharge temperature
protection
Fin temperature
protection
P.C. board temperature
protection
High-pressure
protection
8 times
Not lighted
Converter protection
• Replace the power board.
Bus-bar voltage
protection (1)
• Check the voltage of power supply.
• Replace the power board or the electronic
control P.C. board.
• Refer to 11-6. “Check of bus-bar voltage”.
Bus-bar voltage
protection (2)
13 times
Not lighted
Outdoor fan motor
• Refer to 11-6. "Check of outdoor fan motor".
Lighted
8 times
Current sensor
protection
• Replace the power board.
Lighted
11 times
Communication protection
between P.C. boards
• Check the connecting wire between electronic
control P.C. board and the power board.
Lighted
12 times
Zero cross detecting circuit
protection
• Check the connecting wire between electronic control
P.C. board, noise filter P.C. board and the power board.
• Check the amount of gas and the refrigerant circuit.
• Check the stop valve.
• Check the amount of gas and the refrigerant circuit.
• Refer to 11-6. "Check of LEV".
•Check the refrigerant circuit and the refrigerant amount.
•Refer to 11-6. "Check of outdoor fan motor".
• Reconnect compressor connector.
• Refer to 11-6. "How to check inverter/compressor".
• Check the stop valve.
• Check the power module (PAM module).
Twice
Not lighted
4 times
Not lighted
5 times
Not lighted
9 times
Not lighted
Overcurrent is detected 30 seconds after compressor start-up.
Overcurrent is detected within 30 seconds after compressor start-up.
The bus-bar voltage exceeds 400 V or falls to 200 V or below during
compressor operating.
The bus-bar voltage exceeds 400 V
(MXZ-3C54/3C68/4C71VA)
/
430 V
(MXZ-4C80/5C100VA, 4C80/5C100VA2)
or falls to 50 V or below
while the compressor is operating.
Discharge temperature exceeds 116°C during operation. Compressor can
restart if discharge temperature thermistor reads 100°C or less 3 minutes
later.
The fin temperature exceeds 89°C during operation.
The P.C. board temperature exceeds 73°C (
MXZ-3C54/3C68/4C71VA)
/
87°C
(MXZ-4C80/5C100VA, 4C80/5C100VA2)
during operation.
High-pressure is detected with the high-pressure switch (HPS) during
operation.
(MXZ-3C68/4C71/4C80/5C100VA, 4C80/5C100VA2)
Failure occurs 3 consecutive times within 30 seconds after the fan
gets started.
A short or open circuit is detected in the current sensor while the
compressor is operating.
Communication error occurs between the electronic control P.C. board
and power board for more than 10 seconds.
Zero cross signal cannot be detected while the compressor is operating.
The outdoor heat exchanger temperature exceeds 70°C during cooling
or indoor gas pipe temperature exceeds 70°C during heating.
A failure is detected in the operation of the converter during operation.
Outdoor unit
does not
operate.
Lighted
Once
LEV and drain pump
• Check the connection of the compressor connecting
wire.
• Refer to 11-6.
"How to check inverter/compressor".
• Check the stop valve.
• Refer to 11-6.
"Check of outdoor thermistors".
• Refer to 11-6.
"Check of outdoor thermistors".
• Refer to 11-6.
"Check of LEV".
• Check the drain pump of the indoor unit.
The indoor unit detects an abnormality in the LEV and drain pump.
No.
1
2
3
4
5
6
7
9
8
10
11
12
13
14
15
16
17
18
19
Symptom
'Outdoor unit
stops and
restarts 3
minutes
later' is
repeated.
OBH584G
Содержание MXZ-2C30VA
Страница 24: ...24 WIRING DIAGRAM 6 MXZ 2C30VA MXZ 2C40VA MXZ 2C52VA OBH584G ...
Страница 25: ...25 MXZ 3C54VA OBH584G ...
Страница 26: ...26 MXZ 3C68VA OBH584G ...
Страница 27: ...27 MXZ 4C71VA OBH584G ...
Страница 28: ...28 MXZ 4C80VA OBH584G ...
Страница 29: ...29 MXZ 4C80VA2 OBH584G ...
Страница 30: ...30 MXZ 5C100VA OBH584G ...
Страница 31: ...31 MXZ 5C100VA2 OBH584G ...
Страница 32: ...32 MXZ 6C120VA E1 OBH584G ...
Страница 33: ...33 MXZ 6C120VA E2 OBH584G ...
Страница 34: ...34 MXZ 6C122VA E1 OBH584G ...
Страница 35: ...35 MXZ 6C122VA ER1 OBH584G ...
Страница 36: ...36 MXZ 6C122VA E2 OBH584G ...
Страница 37: ...37 MXZ 6C122VA ER2 OBH584G ...