67
1. Press EMERGENCY OPERATION switch to COOL or HEAT mode (COOL : Press once, HEAT : Press twice).
2. Test run operation starts and continues to operate for 30 minutes.
3. Compressor operates at rated frequency.
4. Indoor fan operates at High speed.
5. After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts (Operation frequency of compressor
varies).
6. To cancel test run operation (EMERGENCY OPERATION), press EMERGENCY OPERATION switch or any button on
remote controller.
8-3. HOW TO OPERATE FIXED-FREQUENCY OPERATION <Test run operation>
Both indoor and outdoor units are under the
same temperature/humidity condition.
Operation : TEST RUN OPERATION (Refer to 8-3.)
Dry-bulb temperature ( )
Relative humidity (%)
20
50
25
60
30
70
8-4. OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT CURVE
(single operation)
NOTE:
The unit of pressure has been changed to MPa on the international system of units (SI unit system).
The conversion factor is :
1 (MPa[Gauge]) = 10.2(kgf/cm
2
[Gauge])
(1) COOL operation
MXZ-2C30VA
MXZ-2C40VA
15-class unit
20-class unit
22-class unit
25-class unit
15-class unit
20-class unit
Ambient temperature ( )
Ambient humidity (%)
Ambient temperature ( )
Ambient humidity (%)
Outdoor low pressure
(MPa[Gauge])
Outdoor unit current (A)
15
20
25
30
35
50
60
70
0.7
0.8
0.9
1.0
1.2
1.3
1.4
(%)
15
20
25
30
35
50
60
70
(%)
42Hz
1
2
3
4
42Hz
14
13
12
11
10
9
7
8
1.1
Ambient temperature ( )
Ambient humidity (%)
Ambient temperature ( )
Ambient humidity (%)
Outdoor low pressure
(MPa[Gauge])
Outdoor unit current (A)
15
20
25
30
35
50
60
70
0.7
0.8
0.9
1.0
1.2
1.3
1.4
(%)
15
20
25
30
35
50
60
70
(%)
42Hz
1
2
3
4
42Hz
14
13
12
11
10
9
7
8
1.1
Outdoor low pressure
(MPa[Gauge])
Outdoor unit current (A)
Ambient temperature ( )
Ambient humidity (%)
Ambient temperature ( )
Ambient humidity (%)
50
60
70
(%)
50
60
70
(%)
48Hz
48Hz
13
12
11
10
9
8
7
15
20
25
30
35
0.7
0.8
0.9
1.0
1.1
1.2
1.3
15
20
25
30
35
1
2
3
4
5
6
Outdoor low pressure
(MPa[Gauge])
Outdoor unit current (A)
Ambient temperature ( )
Ambient humidity (%)
Ambient temperature ( )
Ambient humidity (%)
50
60
70
(%)
50
60
70
(%)
48Hz
48Hz
13
12
11
10
9
8
7
15
20
25
30
35
0.7
0.8
0.9
1.0
1.1
1.2
1.3
15
20
25
30
35
0
1
2
3
4
5
Outdoor low pressure
(MPa[Gauge])
Outdoor unit current (A)
Ambient temperature ( )
Ambient humidity (%)
Ambient temperature ( )
Ambient humidity (%)
50
60
70
(%)
50
60
70
(%)
48Hz
48Hz
15
14
13
12
11
10
9
15
20
25
30
35
0.9
1.0
1.1
1.2
1.3
1.4
1.5
15
20
25
30
35
0
1
2
3
4
5
Outdoor low pressure
(MPa[Gauge])
Outdoor unit current (A)
Ambient temperature ( )
Ambient humidity (%)
Ambient temperature ( )
Ambient humidity (%)
50
60
70
(%)
50
60
70
(%)
48Hz
48Hz
15
14
13
12
11
10
9
15
20
25
30
35
0.9
1.0
1.1
1.2
1.3
1.4
1.5
15
20
25
30
35
0
1
2
3
4
5
OBH584G
Содержание MXZ-2C30VA
Страница 24: ...24 WIRING DIAGRAM 6 MXZ 2C30VA MXZ 2C40VA MXZ 2C52VA OBH584G ...
Страница 25: ...25 MXZ 3C54VA OBH584G ...
Страница 26: ...26 MXZ 3C68VA OBH584G ...
Страница 27: ...27 MXZ 4C71VA OBH584G ...
Страница 28: ...28 MXZ 4C80VA OBH584G ...
Страница 29: ...29 MXZ 4C80VA2 OBH584G ...
Страница 30: ...30 MXZ 5C100VA OBH584G ...
Страница 31: ...31 MXZ 5C100VA2 OBH584G ...
Страница 32: ...32 MXZ 6C120VA E1 OBH584G ...
Страница 33: ...33 MXZ 6C120VA E2 OBH584G ...
Страница 34: ...34 MXZ 6C122VA E1 OBH584G ...
Страница 35: ...35 MXZ 6C122VA ER1 OBH584G ...
Страница 36: ...36 MXZ 6C122VA E2 OBH584G ...
Страница 37: ...37 MXZ 6C122VA ER2 OBH584G ...