87
11-time flash
15-time flash
• Replace the inverter P.C.
board.
• Replace the inverter P.C.
board.
A short or open circuit is detected in
the current sensor during compressor
operating.
The bus-bar voltage exceeds 430 V
or falls to 50 V or below during
compressor operating.
Current sensor
Bus-bar voltage
LEV and drain pump
8 times
Not
lighted
6 times
Not
lighted
The indoor unit detects abnormality
in the LEV and drain pump.
Lighted Lighted
14-time flash
• Refer to 11-6.
"Check
of LEV".
• Check the drain pump of
the indoor unit.
• Refer to 11-6.
"How to
check inverter/
compressor".
Power module
There is a high possibility that the
power module is out of order.
7 times
Not
lighted
12 times
Stop valve
(Closed valve)
Closed valve is detected by compressor
current.
(MXZ-2C30VA, MXZ-2C40VA)
• Check the stop valve.
Lighted
Abnormal point
(Failure mode / protection)
Condition
Remedy
Indoor/outdoor
unit failure mode
recall function
LED indication
(Outdoor P.C. board)
LED 1
LED 2
Upper or left lamp of
OPERATION INDICATOR
lamp (Indoor unit)
NOTE
: Blinking patterns of this mode differ from the ones of Troubleshooting check table (11-4).
OBH584G
Содержание MXZ-2C30VA
Страница 24: ...24 WIRING DIAGRAM 6 MXZ 2C30VA MXZ 2C40VA MXZ 2C52VA OBH584G ...
Страница 25: ...25 MXZ 3C54VA OBH584G ...
Страница 26: ...26 MXZ 3C68VA OBH584G ...
Страница 27: ...27 MXZ 4C71VA OBH584G ...
Страница 28: ...28 MXZ 4C80VA OBH584G ...
Страница 29: ...29 MXZ 4C80VA2 OBH584G ...
Страница 30: ...30 MXZ 5C100VA OBH584G ...
Страница 31: ...31 MXZ 5C100VA2 OBH584G ...
Страница 32: ...32 MXZ 6C120VA E1 OBH584G ...
Страница 33: ...33 MXZ 6C120VA E2 OBH584G ...
Страница 34: ...34 MXZ 6C122VA E1 OBH584G ...
Страница 35: ...35 MXZ 6C122VA ER1 OBH584G ...
Страница 36: ...36 MXZ 6C122VA E2 OBH584G ...
Страница 37: ...37 MXZ 6C122VA ER2 OBH584G ...