Check of outdoor fan motor
• Fan motor does not operate or stops operating shortly after starting the operation.
Yes
Yes
Yes
No
(Fixed to either 5 V or 0 VDC)
No
No
Disconnect CN932 and measure the
resistance of the outdoor fan motor.
Turn ON the power supply.
Rotate the outdoor fan motor manually and measure the voltage of
CN931.
Between (+) and (-)
Between (+) and (-)
Between (+) and (-)
Is the resistance of outdoor fan motor
normal? (Refer to 11-5.)
Does the outdoor fan motor rotate smoothly?
Does the voltage between each terminal become 5 VDC and 0 VDC
repeatedly?
Replace the outdoor fan motor.
Replace the inverter P.C. board/electronic control
P.C. board.
MXZ-2C30/2C40/2C52/3C54/3C68/4C71/4C80/5C100VA
MXZ-4C80/5C100VA2
CN931
CN932
Electronic control P.C.
board
MXZ-2C
MXZ-3C/4C/5C
Inverter P.C. board
OBH584G