62
Normal
MXZ-2A40/52
0.56
Ω
~ 0.69
Ω
Discharge temperature
thermistor (RT62)
Fin temperature
thermistor (RT64)
WHT - RED
RED - ORN
Measure the resistance using a tester. (Part temperature : -10°C ~ 40°C)
37.4
Ω
~ 53.9
Ω
Part name
Check method and criterion
Measure the resistance between terminals using a tester.
(Winding temperature : -10°C ~ 40°C)
Compressor
W
U
V
WHT
RED
BLK
Measure the resistance between lead wires using a tester.
(Part temperature : -10°C ~ 40°C)
Outdoor fan motor
R.V. coil
Measure the resistance using a tester.(Part temperature : -10°C ~ 40°C)
Linear expansion valve
LEV
WHT
RED
YLW BRN
ORN
BLU
Color of lead wire
Normal
YLW - BRN
BRN - BLU
U
RED
WHT
BLK
V
W
(W)
(V)
(U)
Normal (1 Each phase)
13.4
Ω
~ 16.4
Ω
Pressure
Normal
HPS
3.7 ± 0.15MPa
4.8 MPa
Open
Close
0.05
0.1
+
-
High pressure switch
(HPS)
MXZ-4A80
Normal (1Each phase)
MXZ-4A80
MXZ-3A54/4A71
1.29
Ω
~ 1.49
Ω
0.39
Ω
~ 0.49
Ω
13-5. Trouble criterion of main parts
MXZ-2A40VA MXZ-2A52VA MXZ-3A54VA MXZ-4A71VA MXZ-4A80VA
1.2k
Ω
~ 1.56k
Ω
MXZ-3A/4A
12
Ω
~ 16
Ω
MXZ-2A
Defrost thermistor
(RT61)
Ambient temperature
thermistor (RT65)
Outdoor heat exchanger
temperature thermistor
(RT68)
Gas pipe temperature
thermistor (RT6A~D)
Measure the resistance with a tester.
Refer to 13-7. “Test point diagram and voltage”,1. “Inverter P.C. board” or 2.
“Outdoor electronic control P.C. board”, the chart of thermistor.
Measure the resistance with a tester.
Before measurement, hold the thermistor with your hands to warm it up.
Refer to 13-7. “Test point diagram and voltage”,1. “Inverter P.C.board” or 2. “Outdoor
electronic control P.C. board”, the chart of thermistor.
2
3
W
U
V
1
WHT
RED BLK
MXZ-3A/4A
MXZ-2A
OB377--3.qxp 05.12.14 3:34 PM Page 62