55
11-time flash
15-time flash
• Replace the power
board.
• Replace the power
board.
• Refer to 13-6.
D
"Check
of LEV".
• Check the drain pump of
the indoor unit.
When a short or open circuit is
detected in the current sensor
during compressor operating.
When the bus-bar voltage exceeds
430V or falls to 50V or below during
compressor operating.
Current sensor
Bus-bar voltage
LEV for drain
8 times
Goes
out
6 times Goes
out
When the indoor unit detectes any
abnormal in the LEV for drain.
Lighting Lighting
14-time flash
• Refer to 13-6.
E
"How to
check inverter/
compressor".
Power module
There is a high possibility that the
power module is out of order.
7 times Goes
out
Abnormal point
(Failure mode / protection)
Condition
Correspondence
Indoor/outdoor
unit failure mode
recall function
LED indication
(Outdoor P.C. board)
LED 1
LED 2
The left lamp of
OPERATION INDICATOR
lamp(Indoor unit)
NOTE : Blinking patterns of this mode differ from the ones of Troubleshooting check table (13-4.).
OB377--2.qxp 05.12.14 3:13 PM Page 55