29
2. Flow chart of the detailed outdoor unit failure mode recall function
*2 Blinking pattern when outdoor unit is abnormal:
ON
OFF
No beep
Beeps
Repeated cycle
2.5-second OFF
3-second ON
Blinking at 0.5-
second interval
No beep
Beeps
Repeated cycle
2.5-second OFF
3-second ON
Blinking at 0.5-
second interval
Repeated cycle
Does POWER lamp on the indoor unit blink at the interval
of 0.5 seconds?
Blinks: The outdoor unit is abnormal. Beep is emitted at the
same timing as the blinking of POWER lamp. *2
Yes
(Blinks
)
No
(OFF)
The outdoor unit might be abnormal.
Check if outdoor unit is abnormal according to the following procedures.
Operational procedure
Make sure that the remote controller is set to the failure mode recall function.
With the remote controller headed towards the indoor unit, press TEMP
button to adjust the set temperature to 25°C. *1
*
1. Regardless of normal or abnormal condition, 2 short beeps
are emitted as the signal is received.
The outdoor unit is abnormal.
Check the blinking pattern, and identify the abnormal point by referring to
the table of outdoor unit failure mode recall function (12-2.3.).
Make sure to check at least 2 consecutive blinking cycles. *2
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures.
Turn OFF the power supply and turn it ON again.
Press RESET button of the remote controller.
Repair the failure parts.
The outdoor unit is normal.
Release the failure mode recall function according
to the left mentioned procedure.
Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" (12-2.1.).
Press OFF/ON (stop/operate) button of the remote controller (the set temperature is displayed) with the
remote controller headed towards the indoor unit.
Press the emergency operation switch so that the memorized abnormal condition is deleted.
*3
Release the failure mode recall function according to "Releasing the failure mode recall function"
mentioned above.
NOTE
: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
*3 The information regarding whether the
connected outdoor unit is a low-standby-
power model or a non-low-standby-
power model will also be initialized.
(Default= compatible with a low-standby-
power model)
NOTE:
It takes up to 1 minute to indicate the outdoor unit
abnormality.
Even if POWER lamp is not lit, keep checking at least
1 minute or longer.