13
Max. Length
A
Max. Height
difference
B
Indoor
unit
Outdoor unit
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Model
Refrigerant piping: m
Piping size O.D: mm
Max. Length A
Max. Height difference B
Gas
Liquid
MUZ-RW25VGHZ
MUZ-RW35VGHZ
20
12
9.52
6.35
MUZ-RW50VGHZ
30
15
9.52
6.35
ADDITIONAL REFRIGERANT CHARGE (R32: g)
Model
Outdoor unit
precharged
Refrigerant piping length (one way)
7 m 8 m 9 m 10 m 11 m 12 m 13 m 14 m 15 m 16 m 17 m 18 m 19 m 20 m
MUZ-RW25VGHZ
1,200
0
0
0
0
20
40
60
80
100 120 140 160 180 200
MUZ-RW35VGHZ
1,100
Calculation: X g = 20 g/m × (Refrigerant piping length(m) - 10)
Model
Outdoor unit
precharged
Refrigerant piping length (one way)
15 m
16 m
17 m
20 m
25 m
30 m
MUZ-RW50VGHZ
1,210
0
20
40
100
200
300
Calculation: X g = 20 g/m × (Refrigerant piping length (m) - 15)