36
How to check mis-wiring and serial signal error (when outdoor unit does not work)
N
• When unit cannot operate neither by the remote controller nor by EMERGENCY OPERATION switch.
Indoor unit does not operate.
• When OPERATION INDICATOR lamp flashes ON and OFF in every 0.5-seconds.
Outdoor unit doesn’t operate.
Is there rated voltage in
the power supply?
Is there any mis-wiring,
poor contact, or wire
disconnection of the
indoor/outdoor
connecting wire?
W
1. Mis-wiring may damage indoor P.C. board during the
operation.
Be sure to confirm the wiring is correct before the
operation starts.
W
3. Be sure to check this within 3 minutes after turning ON.
After 3 minutes, LED blinks 6 times. Even when
the inverter P.C.board or the outdoor electronic control
P.C.board is normal, LED blinks 6 times after 3 minutes.
(Lighted or
not lighted)
No
Yes
No
Yes
Yes
No
Yes
No
Yes
W
2 Be careful to the residual
voltage of smoothing capacitor.
No
No
Yes
No
Yes
Yes
Turn OFF the power supply.
Turn ON the power supply.
Is there rated voltage between
outdoor terminal block S1 and
S2?
Does the upper lamp of OPERATION
INDICATOR lamp light up?
<Confirmation of the power to the indoor unit>
Press EMERGENCY OPERATION switch once.
Check the power
supply.
A
Turn OFF the power supply.
Check once more if the indoor/outdoor
connecting wire is not mis-wiring.
Short-circuit outdoor terminal block S2 and
S3.
W
1
B
Turn ON the power supply.
Check the wiring.
Correct them.
Turn OFF the power supply.
Remove the short-circuit between
outdoor terminal block S2 and S3.
Turn ON the power supply.
Is there amplitude of 10 to 20V DC
between indoor terminal block S2
and S3? <Confirmation of serial
signal>
Is there rated voltage between
indoor terminal block S1 and S2?
<Confirmation of power voltage>
No
No
No
Yes
Yes
Yes
Replace the inverter P.C. board or
the outdoor electronic control P.C.board.
W
2
Is there any error of the
indoor/outdoor connecting wire,
such as the damage of the wire,
intermediate connection, poor
contact to the terminal block?
No
Replace the
indoor/outdoor
connecting wire.
Is serial signal
error indicated
6 minutes later?
Yes
No
· Turn OFF inverter-controlled lighting
equipment.
· Turn OFF the power supply and then
turn ON again.
· Press EMERGENCY OPERATION
switch.
B
· Reinstall
either the
unit or the
light each
other away.
· Attach a filter
on remote
control
receiving
section of
the indoor
unit.
A
Is serial signal error indicated 6 minutes later?
Is there 2V DC or less between CN10A
3
(+)
and JPG(GND)(–) on the indoor electronic
control P.C. board?
Is there 2V DC or less between
CN10A
4
(+) and JPG(GND)(–)
on the indoor electronic control
P.C. board?
Be sure to release the failure-mode recall function after checking.
Is there 2V DC or less between
CN10A
4
(+) and JPG(GND)(–)
on the indoor electronic control
P.C. board?
Does the LED on the inverter P.C. board
or the outdoor electronic control P.C. board
repeat "3.6-second-OFF and 0.8-second-ON
quick blinking"?
W
3
Replace the indoor power /
terminal P.C. board.
Replace the indoor
electronic control P.C. board.
OBH469--2.qxp 07.1.22 1:30 PM Page 36