ACTUATOR CONTROL
MUZ-GC25VA
MUZ-GC35VA
MUZ-GC25VAH
MUZ-GC35VAH
9-3. Relation between main sensor and actuator
9-2. R.V. coil control
Heating . . . . . . . . . . . . . . . . ON
Cooling . . . . . . . . . . . . . . . . OFF
Dry. . . . . . . . . . . . . . . . . . . . OFF
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
ON
OFF
ON
OFF
Outdoor fan
motor
Compressor
5 seconds
15 seconds
ON
OFF
Compressor
Outdoor fan
motor
R.V.coil
ON
OFF
ON
OFF
<COOL>
5 seconds
<HEAT>
5 seconds
9-1. Outdoor fan motor control
The fan motor turns ON/OFF, interlocking with the compressor.
[ON] The fan motor turns ON 5 seconds before the compressor starts up.
[OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
Discharge temperature thermistor
Indoor coil temperature thermistor
Defrost thermistor
Fin temperature thermistor
Ambient temperature thermistor
Compressor
LEV
Outdoor
fan motor
Indoor
fan motor
Defrost
heater
R.V. coil
Sensor
Purpose
Actuator
w
1
w
1
MUZ-GC35VA
MUZ-GC35VAH
Protection
Cooling : Coil frost prevention
Heating : High pressure protection
Cooling : High pressure protection
Heating : Defrosting
Protection
Cooling : Low outside temperature operation
Heating : Defrosting (Heater)