30
Check of compressor winding
Check of compressor operation time
●
Disconnect the connector (CN61) between the compressor and
intelligent power module, and measure the resistance between the
compressor terminals.
<<Measurement point>>
at 3 points
BLK-WHT
BLK-RED
WHT-RED
<<Judgement>>
Refer to 11-4.
0[
"
] ···············Abnormal [short]
Infinite[
"
] ·······Abnormal [open]
NOTE: 1. Be sure to zero the ohmmeter before measurement.
2. Winding resistance for each phase at 20
:
.
Refer to 3.SPECIFICATION.
w
Measure the resistance between the
lead wires at 3 points.
●
Connect the compressor and activate the inverter. Then measure the
time until the inverter stops due to over current.
<<Operation method>>
Start heating or cooling operation by pressing EMERGENCY
OPERATION switch on the indoor unit.
(Test run operation : Refer to 8-3.)
<<Measurement>>
Measure the time from the start of compressor to the stop of compressor
due to over current.
0 second
10 seconds
10 minutes
1 second
2 seconds
Normal
Abnormal
(Refrigerant circuit defect)
(closed valve)
Abnormal
(Poor contact,)
(Outdoor P.C.board defect)
(disconnected connector)
Abnormal
(Compressor lock out)
(Starting defect)
Abnormal
(IPM failure)
(Compressor winding short)
Compressor starts
<<Judgement>>
For refrence
D
E
Check of compressor start failure
F
Yes
No
Yes
Confirm that 1~5 is normal.
•Electrical circuit check
1
Contact of the compressor connector (including CN61)
2
Output voltage of inverter P.C.board and balance of them (See 11-5.
B
)
3
Direct current voltage between DB61(+) and (-) on inverter P.C.board
4
Voltage between outdoor terminal block S1-S2
Check the refrigerant circuit.
Check the stop valve.
w
1
Heat with a drier for about
20 minutes.
Do not recover refrigerant
gas while heating
compressor with a drier.
Compressor start failure. Activate pre-heat control.
(Refer to 10-2. "PRE-HEAT CONTROL SETTING")
After the compressor is heated with a drier,
does the compressor start?
w
1
Does the compressor run for 10 seconds
or more after it starts?
No
Replace the compressor
Heating part
OBH469--1.qxp 07.1.22 1:29 PM Page 30