background image

Burr

Copper pipe

Spare reamer

Pipe cutter

3-2. FLARING WORK

1) Cut the copper pipe correctly with pipe cutter. (Fig. 1, 2)
2) Completely remove all burrs from the cut cross section 

of pipe. (Fig. 3)

•  Put the end of the copper pipe to downward direction 

as you remove burrs in order to avoid to let burrs drop 
in the piping.

5HPRYHÀDUHQXWVDWWDFKHGWRLQGRRUDQGRXWGRRUXQLWV

then put them on pipe having completed burr removal. 

1RWSRVVLEOHWRSXWWKHPRQDIWHUÀDULQJZRUN

4) Flaring work (Fig. 4, 5). Firmly hold copper pipe in the 

dimension shown in the table. Select A mm from the table 
according to the tool you use.

5) Check 

‡ &RPSDUHWKHÀDUHGZRUNZLWK)LJ
‡ ,IÀDUHLVQRWHGWREHGHIHFWLYHFXWRIIWKHÀDUHGVHF

-

WLRQDQGGRÀDULQJZRUNDJDLQ

3-3. PIPE CONNECTION

‡ )DVWHQÀDUHQXWZLWKDWRUTXHZUHQFKDVVSHFL¿HGLQWKHWDEOH
‡ :KHQIDVWHQHGWRRWLJKWÀDUHQXWPD\EUHDNDIWHUDORQJSHULRGDQGFDXVHUHIULJHUDQW

leakage.

•  Be sure to wrap insulation around the piping. Direct contact with the bare piping may 

result in burns or frostbite.

Indoor unit connection

Connect both liquid and gas pipings to indoor unit.

‡ $SSO\DWKLQFRDWRIUHIULJHUDWLRQRLO-RQWKHÀDUHGHQGVRIWKHSLSHV'RQRWDSSO\

refrigeration oil on screw threads. Excessive tightening torque will result in damage on 
the screw.

‡ )RUFRQQHFWLRQ¿UVWDOLJQWKHFHQWHUWKHQWLJKWHQWKH¿UVWWRWXUQVRIÀDUHQXWE\

hand.

•  Use tightening torque table above as a guideline for indoor unit side union joint section, 

DQGWLJKWHQXVLQJWZRZUHQFKHV([FHVVLYHWLJKWHQLQJGDPDJHVWKHÀDUHVHFWLRQ

Pipe diameter 

(mm)

Nut 

(mm)

A (mm)

Tightening torque

Clutch 

type tool 

for R32, 

R410A

Clutch type 

tool for 

R22

Wing nut 

type tool for 

R22

N•m

kgf•cm

ø6.35 (1/4”)

17

0 to 0.5

1.0 to 1.5

1.5 to 2.0

13.7 to 

17.7

140 to 

180

ø9.52 (3/8”)

22

34.3 to 

41.2

350 to 

420

ø12.7 (1/2”)

26

2.0 to 2.5

49.0 to 

56.4

500 to 

575

ø15.88 (5/8”)

29

73.5 to 

78.4

750 to 

800

Copper 
pipe

Good

Tilted Uneven Burred

No good

Fig. 1

Fig. 2

Clutch type

Flaring tool

Fig. 4

Fig. 3

Smooth all 
around

Even length 
all around

Inside is shin-

ing without any 
scratches.

Flare nut

Die

Fig. 5

Fig. 6

3.  OUTDOOR UNIT INSTALLATION

Copper pipe

Wing nut type

 WARNING

When installing the unit, securely connect the refrigerant 
pipes before starting the compressor.

3-1. CONNECTING WIRES FOR OUTDOOR UNIT

1) Open the service panel.
2) Loosen terminal screw, and connect indoor/outdoor unit connecting wire (A) from the 

indoor unit correctly on the terminal block. Be careful not to make mis-wiring. Fix the wire 

to the terminal block securely so that no part of its core is appeared, and no external force 
is conveyed to the connecting section of the terminal block. 

3) Firmly tighten the terminal screws to prevent them from loosening. After tightening, pull 

WKHZLUHVOLJKWO\WRFRQ¿UPWKDWWKH\GRQRWPRYH

4) Connect power supply cord (K).
5) Fix indoor/outdoor unit connecting wire (A) and power supply cord (K) with the cord clamp.
6) Close the service panel securely.

•  Make earth wire a little longer than others. (More than 100 mm)
•  For future servicing, give extra length to the connecting wires.
•  Be sure to attach each screw to its correspondent terminal when securing the cord 

and/or the wire to the terminal block.

35 mm

15 mm

Lead wire

Power supply cord (K)

Outdoor unit connection

Connect pipes to stop valve pipe joint of the outdoor unit in the 
same manner applied for indoor unit.

•  For tightening, use a torque wrench or spanner and use the 

same tightening torque applied for indoor unit.

3-4. INSULATION AND TAPING

1) Cover piping joints with pipe cover.
2) For outdoor unit side, surely insulate every piping including valves.
3) Using piping tape (G), apply taping starting from the entry of outdoor unit.

•  Stop the end of piping tape (G) with tape (with adhesive agent attached).
•  When piping have to be arranged through above ceiling, closet or where the tempera-

ture and humidity are high, wind additional commercially sold insulation to prevent 
condensation.

Terminal block

Terminal block

Cord clamp

Cord clamp

Cord clamp

Power supply 
cord (K)

Power supply cord (K)

Terminal block

Indoor/outdoor 

unit connect-

ing wire (A)

Indoor/outdoor unit 
connecting wire (A)

$OZD\V¿[WKHSRZHU

supply cord on this side.

$OZD\V¿[WKHSRZHUVXSSO\

cord on this side.

Insert the end of the cable 
tie in the rectangle hole.

<LN25, 35>

<LN50>

<LN50HZ, 60>

Содержание MSZ-LN18VG2

Страница 1: ...F VKRFN WKH unit falling etc When plugging the power supply plug into the outlet make sure that there is no dust clogging or loose parts in both the outlet and the plug Make sure that the power supply plug is pushed com pletely into the outlet If there is dust clogging or loose parts on the power supply plug or the outlet it could cause electric shock or UH I ORRVH SDUWV DUH IRXQG RQ WKH SRZHU VXS...

Страница 2: ... QVWDOO WKH XQLW KRUL RQWDOO Please install it in an area not affected by snowfall or blowing snow In areas with KHDY VQRZ SOHDVH LQVWDOO D FDQRS D SHGHVWDO DQG RU VRPH EDIÀH ERDUGV Note It is advisable to make a piping loop near outdoor unit so as to reduce vibration transmitted from there WARNING 7KH XQLW VKRXOG EH LQVWDOOHG LQ URRPV ZKLFK KDYH WKH ÀRRU VSDFH VSHFL HG below LN50VG2 2 5 m LN50VGH...

Страница 3: ...QVWDOODWLRQ SODWH LQJ VFUHZ 4 25 mm 5 3 Wireless remote controller 1 4 Felt tape For left or left rear piping 1 5 Corner box R 4 6 Corner box L 4 7 Battery AAA for 3 2 8 LU FOHDQLQJ OWHU 1 9 Air purifying device 1 Outdoor unit 10 Drain socket VG type only 1 Air inlet LN25 35 50 50HZ 60 LN25 35 50 50HZ 60 3 When any 2 sides of left right and rear of unit are clear 4 The manufacturing year and month...

Страница 4: ...drain piping as shown below Do not raise Accumulated drain water Air Waving Water leakage Water leakage Water leakage Tip of drain hose dipped in water Ditch At least 50 mm gap Downward slope Drain hose Soft hose I D 15 mm Drain hose Hard vinyl chloride pipe I D 30 mm Insert securely Different diameter joint 70 cm or more Fig 1 Fig 2 Fig 3 For future servicing give extra length to the connecting w...

Страница 5: ...1 part about 90 degrees around the hinge point you have just created to put the parts together 3 Press the base of portion with the mark to snap into place When changing the part disassemble by moving the part in a reverse direction The parts that were not used may be necessary in the future if the air conditioner is relocated so ask customers to keep those parts 4 Attach the assembled corner box ...

Страница 6: ...t any scratches Flare nut Die Fig 5 Fig 6 3 OUTDOOR UNIT INSTALLATION Copper pipe Wing nut type WARNING When installing the unit securely connect the refrigerant pipes before starting the compressor 3 1 CONNECTING WIRES FOR OUTDOOR UNIT 1 Open the service panel 2 Loosen terminal screw and connect indoor outdoor unit connecting wire A from the indoor unit correctly on the terminal block Be careful ...

Страница 7: ...art operation automatically when power supply is resumed To the user After installing the unit make sure to explain the user about auto restart function If auto restart function is unnecessary it can be deactivated Consult the service representative to deactivate the function Refer to the service manual for details 4 PURGING PROCEDURES LEAK TEST AND TEST RUN Pressure gauge for R32 R410A Emergency ...

Страница 8: ...river deeply into the holes 2 Pry off the right and left arm holders by moving the screwdriver down and towards the back wall 3 Remove the safety string from the upper center of the panel assembly Installation procedure 1 Install the panel assembly following the removal procedure in reverse 2 Be sure to press the positions as indicated by the arrows in order to attach the assembly completely to th...

Отзывы: