4. INDOOR UNIT INSTALLATION

4-1 FIXING OF INSTALLATION PLATE

Find a structural material (such as a stud) in the wall and fix installation plate
horizontally.

When bolts recessed in the concrete wall are to be utilized, secure the installation
plate 

 using 11 

×

 20 · 11 

×

 26 oval hole (450 mm pitch).

If the recessed bolt is too long, change it for a shorter one available in the market.

4-2 WALL HOLE DRILLING

1

Determine the wall hole position.

2

Drill a 75 mm hole so that outside can be lower than inside.

3

Insert the wall hole sleeve 

.

Positioning of the holes on the wall

Be sure to use wall hole sleeve 

 to prevent the outdoor connecting wires from

contacting with metal part in the wall and to prevent damage by rat in case the wall
is hollow.

Wall hole sealing and fixing pipe to wall

72 mm or more
100 mm or more for left
and left back piping (using
spacer)

200 mm or more

(off the wall)

Plumb

Installation
plate fixing
screw
4

×

 25 mm

120 mm or more

(off the wall)

Insert the scale.

Align the scale with the line.

Installation plate 

Hole of dia.
75 mm

Repeat the same procedure for the left hole.

Wall hole

75 mm dia.

(Indoor side)

(Wall hole cross section)

Wall thickness

One scale

Wall hole sleeve 

Cut with 1 extra
scale length.

Installation
plate

To prevent the installation plate from vibrating, be sure to fix the holes
as indicated by the arrows 

{

.

Wall hole
sleeve

Indoor unit

Wall hole cover 

Seal the wall hole
gap with putty 

.

Fix the pipe to wall with
pipe fixing band 

.

Cut off the
extra length.

Pipe fixing
band

Fixing screw 

Align the plumb line
with the mark 

.

Bind the line to the center hole.

100 mm

4-3 CONNECTING WIRE SPECIFICATIONS

Use special room air conditioning circuit.

4-4 INDOOR AND OUTDOOR CONNECTING WIRE CON-

NECTION

You can connect indoor/outdoor lead wire without removing the front panel.

1

Open the front panel.

2

Remove one screw holding the electrical cover, then remove the cover.

3

Remove the VA clamp and the cord clamp.

4

Pass the indoor/outdoor unit connecting wire from the back of the indoor unit and
process the end of the wire, then connect it to the terminal block.

5

Replace the fixture and electrical cover securely.

Indoor
terminal block

ELECTRICAL COVER

Fixing screws

Securely push the wire into
the terminal block until no
part of its core is appeared.

Indoor/outdoor unit connecting wire 

VA clamp

Never fail to hook the left claw on
the wire fixture to secure indoor/
outdoor unit connecting wire 

.

15 mm

35 mm

Indoor terminal block

Indoor/outdoor unit
connecting wire 
4-core 1.0 mm

2

Outdoor terminal block

<Connection details>

Loosen terminal
screw.

Lead wire

Terminal
block

 WARNING

Never cut the indoor and outdoor unit connecting wire and connect it to other wires.
It may cause a fire.

Do not bundle the spare wire, but put it as shown below.

Indoor/outdoor unit connecting wire

Specification

Cable 4-core 1.0 mm

2

, in conformity

 with Design 245 IEC 57.

 WARNING

Use the indoor/outdoor unit connecting wire that meets the Standards to connect
the indoor and outdoor units and fix the wire to the terminal block securely so that
no external force is conveyed to the connecting section of the terminal block.
Incomplete connection or fixing of the wire could result in a fire.

Attach the electrical cover securely. If it is attached incorrectly, it could result in a
fire or an electric shock due to dust, water, etc.

Earth wire
(green/yellow)

1800 mm or more

from the floor

Содержание MSZ-GA50VA

Страница 1: ...r or wall and set the wireless remote controller In rooms where inverter type fluorescent lamps are used the signal from the wireless remote controller may not be received 1 THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY Be sure to read THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY before installing the air conditioner Be sure to observe the cautions specified here as they include importa...

Страница 2: ...D CONNECTIONS This unit has flared connections on both indoor and outdoor sides Remove the outdoor units valve cover then connect the pipe Refrigerant pipes are used to connect the indoor and outdoor units Be careful not to crush or bend the pipe in pipe bending Limits MSZ GA50 60 71 80 Pipe length 30 m max Height difference 15 m max No of bends 10 max Refrigerant adjustment If pipe length exceeds...

Страница 3: ... 3 CONNECTING WIRE SPECIFICATIONS Use special room air conditioning circuit 4 4 INDOOR AND OUTDOOR CONNECTING WIRE CON NECTION You can connect indoor outdoor lead wire without removing the front panel 1 Open the front panel 2 Remove one screw holding the electrical cover then remove the cover 3 Remove the VA clamp and the cord clamp 4 Pass the indoor outdoor unit connecting wire from the back of t...

Страница 4: ... is off To prevent breaker off due to the rush of starting current systematize other home appliances not to turn on at the same time 4 6 PIPE FORMING Place the drain hose below the refrigerant piping Make sure that the drain hose is not heaved or snaked Do not pull the hose to apply the tape When the drain hose passes the room be sure to wrap insulation material obtain able at a store around it Wr...

Страница 5: ...ow Connect the refrigerant piping with the extension pipe Thrust the lower part of the indoor unit into the installation plate 4 7 DRAIN PIPING If the extension drain hose has to pass through a room be sure to wrap it with commercially sold insulation The drain hose should point downward for easy drain flow Fig 1 Do not make drain piping as shown in Fig 2 to 5 Spacer assembly Securely attach the s...

Страница 6: ... substituted for R410A tools The diameter of the service port on the stop valve in outdoor unit has been changed to prevent any other refrigerant being charged into the unit Cap size has been changed from 7 16 UNF with 20 threads to 1 2 UNF with 20 threads R410A tools Can R22 tools be used Description R410A has high pressures beyond the meas urement range of existing gauges Gauge manifold No Port ...

Страница 7: ...perates so the compressor will not operate for three minutes to protect the air conditioner 6 6 EXPLANATION TO THE CUSTOMER Using the OPERATING INSTRUCTIONS explain the following to the customer how to control temperature how to remove the air filters how to remove or put the remote controller in the remote controller holder how to clean precautions for operation etc Recommend the customer to read...

Страница 8: ...e top of the front panel 4 Fit in the bottom of the front panel and tighten it using screws 5 Push the section of the front panel marked by the arrow and fit the panel into the air conditioner 7 2 PUMPING DOWN When relocating or disposing of the air conditioner pump down the system following the procedure below so that no refrigerant is released into the atmosphere 1 Connect the gauge manifold val...

Отзывы: