7 mm or more

500 mm or more

100 mm or more

100 mm or more

500 mm or more

350 mm or more

Note:

Do not
obstruct the
air outlet.

72 mm or more

100 mm or more for left and left

back piping (using spacer)

120 mm

or more

200 mm

or more

5

Air outlet

4-10 mm 

×

 21 mm slot

Be careful the
drain hose is not
raised.

Separate the 2 connecting pipes and
apply insulation individually.

8 mm thickness thermal insulation
plastic

Decide the installation position using mark on the installation
plate indicating the indoor unit size as reference.

When the piping is to be attached to a
wall containing metals (tin plated) or
metal netting, use a chemically treated
wooden piece 20 mm or thicker
between the wall and the piping or
wrap 7 to 8 turns of insulation vinyl
tape around the piping.

Lock the catch.

Front

Piping can be directed towards rear,
right, downward, left or left-rear
directions.

Rear side
Right

Rear

Downward

Left-rear

Left

Units should be installed by licensed contractor according
to local code requirement.

PIPING PREPARATION

1

Specifications
Use the refrigerant pipes that meet the following specifications.

840 mm

330 mm

360 mm

500 mm

100 mm

15 mm

17 mm

10.5 mm

Heat resisting
foam plastic
0.045 specific
gravity

Use a copper pipe or a copper-alloy seamless pipe with a thickness of 0.8 mm
(for ø6.35, 9.52) or 1.0 mm (for ø12.7, ø15.88). Never use any pipe with a thickness
less than 0.8 mm (for ø6.35, 9.52) or 1.0 mm (for ø12.7, ø15.88), as the pressure
resistance is insufficient.

2

Ensure that the 2 refrigerant pipes are insulated to prevent condensation.

3

Refrigerant pipe bending radius must be 100 mm or more.

 CAUTION

Be sure to use the insulation of specified thickness. Excessive thickness may cause
incorrect installation of the indoor unit and lack of thickness may cause dew drippage.

8

8

8

8

Pipe

Outside diameter

Insulation thickness

Insulation material

mm

mm

For liquid

For gas

GA50/GA60

GA71/GA80

GA50

GA60/GA71/GA80

6.35

9.52

12.7

15.88

3. INSTALLATION DIAGRAM & ACCESSORIES

FLARED CONNECTIONS

This unit has flared connections on both indoor and outdoor sides.

Remove the outdoor units valve cover, then connect the pipe.

Refrigerant pipes are used to connect the indoor and outdoor units.

Be careful not to crush or bend the pipe in pipe bending.

Limits

MSZ-GA50/60/71/80

Pipe length

30 m max.

Height difference

15 m max.

No. of bends

10 max.

Refrigerant adjustment ... If pipe length exceeds 7 m, additional refrigerant
(R-410A) charge is required.
(The outdoor unit is charged with refrigerant for pipe length up to 7 m.)

Pipe length

Up to 7 m

No additional charge is required.

Exceeding 7 m

Additional charge is required.

(Refer to the table below.)

MSZ-GA50

20 g/m 

×

 (refrigerant piping length (m) -7)

MSZ-GA60

20 g/m 

×

 (refrigerant piping length (m) -7)

MSZ-GA71

55 g/m 

×

 (refrigerant piping length (m) -7)

MSZ-GA80

55 g/m 

×

 (refrigerant piping length (m) -7)

Indoor/outdoor unit connecting wire

1

(4-core 1.0 mm

2

-2.0 mm

2

)

Extension pipe

1

Wall hole sleeve

1

Wall hole cover

1

Pipe fixing band (The quantity depends
on the pipe length.)

2 to 5

Fixing screw for 

 4 

×

 20 mm (The

2 to 5

quantity depends on the pipe length.)

Piping tape

1

Putty

1

Drain hose (or soft PVC. hose, 15 mm

1

inner dia. or hard PVC pipe VP16)

Refrigeration oil

1

Power supply cord (See the table in 5
INDOOR/OUTDOOR WIRE CONNECTION

1

AND OUTDOOR POWER SUPPLY CORD
CONNECTION for the cord size.)

Note:

When operating the air conditioner in low outside temperature,
be sure to follow the instructions described below.

Never install the outdoor unit in a place where its air inlet/outlet
side may be exposed directly to wind.

To prevent exposure to wind, install the outdoor unit with its
air inlet side facing the wall.

To prevent exposure to wind, it is recommended to install a
baffle board on the air outlet side of the outdoor unit.

PART TO BE PROVIDED AT YOUR SITE

Optional extension pipe

ACCESSORIES

Check the following parts before installation.
<Indoor unit>

Installation plate

1

Installation plate fixing screw 4 

×

 25 mm

7

Remote controller holder

1

Fixing screw for 

 3.5 

×

 16 mm (Black)

2

Battery (AAA) for remote controller

2

Wireless remote controller

1

Felt tape (Used for left or left-rear piping)

1

Anti-allergy enzyme filter

2

Refrigerant to

be added

1800 mm or
more from
the floor

Содержание MSZ-GA50VA

Страница 1: ...r or wall and set the wireless remote controller In rooms where inverter type fluorescent lamps are used the signal from the wireless remote controller may not be received 1 THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY Be sure to read THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY before installing the air conditioner Be sure to observe the cautions specified here as they include importa...

Страница 2: ...D CONNECTIONS This unit has flared connections on both indoor and outdoor sides Remove the outdoor units valve cover then connect the pipe Refrigerant pipes are used to connect the indoor and outdoor units Be careful not to crush or bend the pipe in pipe bending Limits MSZ GA50 60 71 80 Pipe length 30 m max Height difference 15 m max No of bends 10 max Refrigerant adjustment If pipe length exceeds...

Страница 3: ... 3 CONNECTING WIRE SPECIFICATIONS Use special room air conditioning circuit 4 4 INDOOR AND OUTDOOR CONNECTING WIRE CON NECTION You can connect indoor outdoor lead wire without removing the front panel 1 Open the front panel 2 Remove one screw holding the electrical cover then remove the cover 3 Remove the VA clamp and the cord clamp 4 Pass the indoor outdoor unit connecting wire from the back of t...

Страница 4: ... is off To prevent breaker off due to the rush of starting current systematize other home appliances not to turn on at the same time 4 6 PIPE FORMING Place the drain hose below the refrigerant piping Make sure that the drain hose is not heaved or snaked Do not pull the hose to apply the tape When the drain hose passes the room be sure to wrap insulation material obtain able at a store around it Wr...

Страница 5: ...ow Connect the refrigerant piping with the extension pipe Thrust the lower part of the indoor unit into the installation plate 4 7 DRAIN PIPING If the extension drain hose has to pass through a room be sure to wrap it with commercially sold insulation The drain hose should point downward for easy drain flow Fig 1 Do not make drain piping as shown in Fig 2 to 5 Spacer assembly Securely attach the s...

Страница 6: ... substituted for R410A tools The diameter of the service port on the stop valve in outdoor unit has been changed to prevent any other refrigerant being charged into the unit Cap size has been changed from 7 16 UNF with 20 threads to 1 2 UNF with 20 threads R410A tools Can R22 tools be used Description R410A has high pressures beyond the meas urement range of existing gauges Gauge manifold No Port ...

Страница 7: ...perates so the compressor will not operate for three minutes to protect the air conditioner 6 6 EXPLANATION TO THE CUSTOMER Using the OPERATING INSTRUCTIONS explain the following to the customer how to control temperature how to remove the air filters how to remove or put the remote controller in the remote controller holder how to clean precautions for operation etc Recommend the customer to read...

Страница 8: ...e top of the front panel 4 Fit in the bottom of the front panel and tighten it using screws 5 Push the section of the front panel marked by the arrow and fit the panel into the air conditioner 7 2 PUMPING DOWN When relocating or disposing of the air conditioner pump down the system following the procedure below so that no refrigerant is released into the atmosphere 1 Connect the gauge manifold val...

Отзывы: