53
Replace LEV.
(coil defect)
Replace LEV.
Check of linear expansion valve (LEV)
P
• Press RESET button, while pressing OPERATION SELECT button on remote controller.
(All displays on operational display section are ON.)
• With remote controller set toward the indoor unit, press OPERATE/STOP(ON/OFF)
button and confirm one beep tone.
• With remote controller set toward the indoor unit, OPERATE/STOP(ON/OFF) button and
confirm two beep tones.
Confirm again
that LEV is
operating.
Replace outdoor
electronic control P.C.
board.
LEV operates in full-opening
direction.
· Is LEV connector connected?
· Is LEV coil properly fixed to the body?
Heating/Cooling do not operate.
Ok
Do you hear LEV "click,
click·······"?
Do you touch LEV and
feel it vibrate?
Does the resistance of
LEV coil
have the characteristics?
Do you hear LEV
"click, click·········"?
No
Yes
Yes
Yes
Ok
Yes
Yes
No
No
LEV (CN 724)
WHT(6)–RED(1)
RED(1)–ORE(4)
YLW(5)–BRN(2)
BRN(2)–BLU(3)
resistance
39
"
~56
"
Characteristics of LEV coil
❈
After you have followed the entire flow chart of "Check of linear expansion valve (LEV)", be sure to follow the procedure below.
Replace current limiting resistor.
Check of rush current limiting circuit
O
Outdoor unit does not operate or stops immediately due to overcurrent.
NOTE : When the current limiting resistor is open, the rush current limiting relay
may not be working properly. There fore confirm the limiting resistor
works properly after replacing it.
Ok
Does current limiting resistor detect 10
"
?
No
∞
Yes
Start
· Re-connect the connector.
· Properly fix LEV coil to the body.
No
1
Press EMERGENCY OPERATION switch.
2
Unplug the power cord and then plug it again.
3
Press RESET button on remote controller.
OB230-2.qxp 02.5.28 7:37 PM Page 53