Check of outdoor thermistors
I
Check of indoor electronic P.C. board
H
Measure
resistance
between CN
641
1
and
2
.
Measure
resistance
between CN
642
1
and
2
.
No
Yes
The unit does not operate with the remote controller. The POWER MONITOR lamp does not light up either,
with the Emergency operation switch on.
Thermistors in the outdoor unit are abnormal.
Re-connect the
connector.
Indoor electronic
control P.C. board
Varistor (NR11)
Indoor electronic
control P.C. board
Fuse (F11)
1
3
N
2
3
Thermal fuse connector
●
Disconnect the connectors CN 641 and CN 642 from the outdoor electronic control P.C. board.
(Check the characteristics of each thermistor.)
1
Connect CN 641 and
CN 642.
2
Disconnect the
connector between
compressor and IPM.
(Defrost thermistor)
Measure
resistance
between CN
641
3
and
4
.
Turn on power
supply to indoor
unit and press
emergency
operation switch.
Discharge
temperature
thermistor
(
)
Fin
temperature
thermistor
(
)
Does the unit operate
10 minutes or more?
No
Yes
Terminal
block
Is LED in the outdoor
electronic control P.C.
board flashing 5
minutes?
Replace the outdoor
electronic control P.C.
board.
No
Yes
Does the resistance
of thermistor have
the characteristics
on page 55?
Replace the
thermistor.
Check both “parts side”
and “pattern side” of indoor
electronic control P.C.
board visually.
Replace the fuse.
Is fuse(F11) blown?
Be sure to check both fuse
and varistor in any case.
Replace the fan motor.
Replace the
indoor electronic
control P.C. board.
Is winding resistance
of fan motor 0
"
?
Is winding resistance
of vane motor 0
"
?
No
Yes
Replace the vane motor.
No
Yes
Yes
Is varistor(NR11) burnt?
Replace the varistor.
Yes
Turn off the power supply.
Remove indoor fan motor connector CN211 and vane motor connector CN151
from the indoor electronic control P.C. board and turn on the power supply.
No
No
Does the unit operate with the remote controller?
Does the POWER MONITOR lamp light up by
pressing the emergency operation switch?
Yes
No
Be sure to check both resistance.