Check of outdoor fan motor
K
Check of R.V. coil
J
Disconnect connector between
compressor and IPM.
Turn on power supply to indoor
unit, and press emergency
operation switch to heating
operation.
Heating operation works when cooling is expected.
Outdoor fan motor does not work.
· Press emergency operation
switch again to check if 52C
relay works.
· Re-connect connecting wire
of indoor and outdoor unit.
· Replace the indoor electronic
control P.C. board.
· Replace the lead
wires of outdoor fan
motor.
· Re-connect
connector CN 771
· Replace the outdoor
fan motor.
Replace the R.V.
coil.
Replace the
relay P.C.
board.
• If the connector CN 913 is connected or the R.V. coil is open, the voltage occurs
between the terminals even when the control is OFF.
3 min. after power turns on, is there voltage of 220-240V
AC between CN 913
1
and
2
on relay P.C. board ?
3 minutes after power
turns on, is there voltage
of 220-240V AC between
outdoor terminal block
2
and
N
?
Is there voltage of
approx. 220-240V AC
either between
2
and
3
or between
2
and
4
or
between
2
and
5
at
CN 771?
Indoor -outdoor
connecting
wire
Outdoor terminal block TB1
N
2
3
Disconnect connector
CN 771 on relay P.C.
board.
Disconnect connector
between compressor
and IPM.
Turn on power supply
to indoor unit, and
press emergency
operation switch.
3 minites after
power turns on,
measure voltage
between terminals
of CN 771.
1
CN913
Relay P.C. board
2
4-way valve
AC 220-240V
Yes
Yes
Yes
No
No
No
CN771
Relay P.C. board
1 2 3
4 5 6
Fan
motor
Indoor-outdoor
connecting
wire
Outdoor terminal block TB1
N
2
3
Cooling operation works when heating is expected.
•First, measure resistance of the R.V. coil to check if it is defective or not.
• If the connector CN 913 is connected or the R.V. coil is open, the voltage occurs
between the terminals even when the control is OFF.
Replace the relay P.C. board.
Is there voltage of 0V between CN 912
1
(+)and
2
(-)
on relay P.C. board?
Approx. 1V
DC voltage
occurs.
Yes
Replace the
outdoor electrinic
control P.C. board.
Disconnect connector between
compressor and IPM.
Turn on power to indoor unit, and
press emergency operation switch
to cooling opeation.
3 min. after power turns on, is there voltage of 220-
240V AC between CN 913
1
and
2
on relay P.C.
Yes
No
Replace the relay P.C. board.
Is there voltage of 1V DC between CN 912
1
(+)and
2
(-) on relay P.C. board?
No
The voltage
is 0V
Yes
· Replace the lead
wires of R.V. coil.
· Re-connect
connector.
· Replace the 4-way
valve.
Replace the
outdoor electrinic
control P.C. board.