3

3. Installation diagram

Fig. 3-1

3.1. Outdoor unit (Fig. 3-1)

Ventilation and service space

  

SUZ-SA71VA2, SUZ-SA100VA

A

 100 mm or more

B

 350 mm or more

C

 500 mm or more

When the piping is to be attached to a wall containing metals (tin plated) or metal 
netting, use a chemically treated wooden piece 20 mm or thicker between the wall 
and the piping or wrap 7 to 8 turns of insulation vinyl tape around the piping.

Units should be installed by licensed contractor accordingly to local code re-
quirement.

Note:
When operating the air conditioner in low outside temperature, be sure to fol-
low the instructions described below.

•  

Never install the outdoor unit in a place where its air inlet/outlet side may be ex-
posed directly to wind.

•  

To prevent exposure to wind, install the outdoor unit with its air inlet side facing 
the wall.

•  

To prevent exposure to wind, it is recommended to install a baf

fl

 e board on the air 

outlet side of the outdoor unit.

 

SUZ-SA71VA2

 

SUZ-SA100VA

A

C

A

C

B

Drainage hole 
(

W

42)

Air inlet

Air outlet

417.5 

50

360

500

175

Air inlet

330

40

2-10 mm × 21 mm slot

81

840

4. Refrigerant piping work

Fig. 4-2

Fig. 4-1

(C)

(B)

(A)

A

 Indoor unit

B

 Outdoor unit

A

 Indoor unit

B

 Outdoor unit

ø9.52

ø15.88

4.1. Refrigerant pipe (Fig. 4-1)

 Check that the difference between the heights of the indoor and outdoor 

units, the length of refrigerant pipe, and the number of bends in the pipe are 
within the limits shown below.

Model

(A) Pipe length

(one way)

(B) Height 

difference

(C) Number of 

bends (one way)

SUZ-SA71/SA100

Max. 30 m

Max. 30 m 

Max. of 10

•  Height difference limitations are binding regardless of which unit, indoor or out-

door, is positioned higher.

•  Refrigerant adjustment ... If pipe length exceeds 7 m, additional refrigerant 

(R410A) charge is required.
(The outdoor unit is charged with refrigerant for pipe length up to 7 m.)

Pipe length

Up to 7 m

No additional charge is required.

Exceeding 7 m

Additional charge is required.
(Refer to the table below.)

Refrigerant 
to be added

SUZ-SA71

50 g × (refrigerant piping length (m) -7)

SUZ-SA100

50 g × (refrigerant piping length (m) -7)

(1) Table below shows the speci

fi

 cations of pipes commercially available.

Model

Pipe

Outside diameter Min. wall

thickness

Insulation

thickness

Insulation

material

mm

inch

SUZ-SA71

SUZ-SA100

For liquid

9.52

3/8

0.8 mm

8 mm

Heat resisting 

foam plastic 

0.045 speci

fi

 c 

gravity

For gas

15.88

5/8

1.0 mm

8 mm

(2) Ensure that the 2 refrigerant pipes are well insulated to prevent condensation.
(3) Refrigerant pipe bending radius must be 100 mm or more.

 Caution:

Using careful insulation of speci

fi

 ed thickness. Excessive thickness prevents 

storage behind the indoor unit and smaller thickness causes dew drippage.

(mm)

Содержание Mr. SLIM SUZ-SA100VA

Страница 1: ...AL DE INSTALACIÓN Para un uso correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado MANUALE DI INSTALLAZIONE Per un uso sicuro e corretto leggere attentamente il presente manuale ed il manuale d installazione dell unità interna prima di installare il condizionatore d aria EΓΧEIPIΔIO OΔHΓIΩN EΓKATAΣTAΣHΣ Γ...

Страница 2: ... relocating or servicing the air conditioner use only the specified refrigerant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines If air is mixed with the refrigerant then it can be the cause of abnormal high pressure in the refrigerant line and may result in an explosion and other hazards The use of any refrigerant other tha...

Страница 3: ... 1 Check that the difference between the heights of the indoor and outdoor units the length of refrigerant pipe and the number of bends in the pipe are within the limits shown below Model A Pipe length one way B Height difference C Number of bends one way SUZ SA71 SA100 Max 30 m Max 30 m Max of 10 Height difference limitations are binding regardless of which unit indoor or out door is positioned h...

Страница 4: ...e flared section and do flaring work again a Smooth all around f Scratch on flared plane b Inside is shining without any scratches g Cracked c Even length all around h Uneven d Too much i Bad examples e Tilted Apply a thin coat of refrigeration oil on the seat surface of pipe Fig 4 8 For connection first align the center then tighten the first 3 to 4 turns of flare nut Use tightening torque table ...

Страница 5: ...e then close the gage manifold valve and stop the vacuum pump Leave it as is for one or two minutes Make sure the pointer of the gage mani fold valve remains in the same position Confirm that the pressure gage show 0 101 MPa 760 mmHg Remove the gage manifold valve quickly from the service port of the stop valve After refrigerant pipes are connected and evacuated fully open all stop valves on gas a...

Страница 6: ...ply cable to the size given in the figure Be careful not to contact connecting cable with piping Caution Use care not to make miswiring Fig 5 3 Firmly tighten the terminal screws to prevent them from loosening After tightening pull the wires lightly to confirm that they do not move Warning Be sure to attach the service panel of the outdoor unit securely If it is not attached correctly it could res...

Страница 7: ... 230 V Indoor unit Outdoor unit S2 S3 2 DC 12 V DC 24 V 1 A breaker with at least 3 mm contact separation in each poles shall be provided Use earth leakage breaker NV Make sure that the current leakage breaker is one compatible with higher harmonics Always use a current leakage breaker that is compatible with higher harmonics as this unit is equipped with an inverter The use of an inadequate break...

Страница 8: ...oller to stop the air conditioner Note that when the extension piping is very long with a large refrigerant amount it may not be possible to perform a pump down operation In this case use refrigerant recovery equipment to collect all of the refrigerant in the system If the extension piping length for the SUZ SA100VA is 20 m or longer it will not be possible to perform a pump down operation because...

Страница 9: ...uese Branch Portuguese Branch Avda do Forte 10 2799 514 Carnaxide Lisbon Portugal Avda do Forte 10 2799 514 Carnaxide Lisbon Portugal Spanish Branch Spanish Branch Carretera de Rubi 76 80 Apdo 420 08173 Sant Cugat del Valles Barcelona Spain Carretera de Rubi 76 80 Apdo 420 08173 Sant Cugat del Valles Barcelona Spain Scandinavian Branch Scandinavian Branch Hammarbacken 14 P O Box 750 SE 19127 Solle...

Отзывы: