When relocating or disposing of the air conditioner, pump down the system following 
the procedure below so that no refrigerant is released into the atmosphere.

1

  Turn off the power supply (circuit breaker).

2

  Connect the gauge manifold valve to the service port of the stop valve on the gas 

pipe side of the outdoor unit.

3

  Fully close the stop valve on the liquid pipe side of the outdoor unit.

4

  Supply power (circuit breaker).

 

5

 Perform the refrigerant collecting operation (cooling test run).

 

• 

  For the PAR-31MAA, select “Service” 

 “TestRun” from the main menu to start 

the test run, and then select the cooling mode.

 

• 

  For details or for other information about starting the test run when using re-
mote controllers, refer to the installation manual for the indoor unit or the re-
mote controller.

6

  Fully close the stop valve on the gas pipe side of the outdoor unit when the pres-

sure gauge shows 0.05 to 0 MPa [Gauge] (approx. 0.5 to 0 kgf/cm

2

) and quickly 

stop the air conditioner.

 

• 

 Push the “ON/OFF” button on the remote controller to stop the air conditioner.

 *  

Note that when the extension piping is very long with a large refrigerant 
amount, it may not be possible to perform a pump-down operation. In this case, 
use refrigerant recovery equipment to collect all of the refrigerant in the system.

 *  

If the extension piping length for the SUZ-SA100VA is 20 m or longer, it will 
not be possible to perform a pump-down operation because there is a large 
amount of refrigerant. In this case, collect the refrigerant in the system.

7

  Turn off the power supply (circuit breaker), remove the gauge manifold valve, and 

then disconnect the refrigerant pipes.

 Warning:

When pumping down the refrigerant, stop the compressor before disconnect-
ing the refrigerant pipes.
•  If the refrigerant pipes are disconnected while the compressor is operating 

and the stop valve (ball valve) is open, the pressure in the refrigeration cycle 
could become extremely high if air is drawn in, causing the pipes to burst, 
personal injury, etc.

7. Pumping down

Outdoor model

SUZ-SA71VA2

SUZ-SA100VA

Power supply

Single phase 230 V, 50 Hz

Dimensions H × W × D

mm

880 × 840 × 330

Weight

kg

52

56

Sound level *1

Cooling 

dB (A)

55

Heating

55

*1  Measured under rated operating frequency.

8. Speci

fi

 cations

Содержание Mr. SLIM SUZ-SA100VA

Страница 1: ...AL DE INSTALACIÓN Para un uso correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado MANUALE DI INSTALLAZIONE Per un uso sicuro e corretto leggere attentamente il presente manuale ed il manuale d installazione dell unità interna prima di installare il condizionatore d aria EΓΧEIPIΔIO OΔHΓIΩN EΓKATAΣTAΣHΣ Γ...

Страница 2: ... relocating or servicing the air conditioner use only the specified refrigerant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines If air is mixed with the refrigerant then it can be the cause of abnormal high pressure in the refrigerant line and may result in an explosion and other hazards The use of any refrigerant other tha...

Страница 3: ... 1 Check that the difference between the heights of the indoor and outdoor units the length of refrigerant pipe and the number of bends in the pipe are within the limits shown below Model A Pipe length one way B Height difference C Number of bends one way SUZ SA71 SA100 Max 30 m Max 30 m Max of 10 Height difference limitations are binding regardless of which unit indoor or out door is positioned h...

Страница 4: ...e flared section and do flaring work again a Smooth all around f Scratch on flared plane b Inside is shining without any scratches g Cracked c Even length all around h Uneven d Too much i Bad examples e Tilted Apply a thin coat of refrigeration oil on the seat surface of pipe Fig 4 8 For connection first align the center then tighten the first 3 to 4 turns of flare nut Use tightening torque table ...

Страница 5: ...e then close the gage manifold valve and stop the vacuum pump Leave it as is for one or two minutes Make sure the pointer of the gage mani fold valve remains in the same position Confirm that the pressure gage show 0 101 MPa 760 mmHg Remove the gage manifold valve quickly from the service port of the stop valve After refrigerant pipes are connected and evacuated fully open all stop valves on gas a...

Страница 6: ...ply cable to the size given in the figure Be careful not to contact connecting cable with piping Caution Use care not to make miswiring Fig 5 3 Firmly tighten the terminal screws to prevent them from loosening After tightening pull the wires lightly to confirm that they do not move Warning Be sure to attach the service panel of the outdoor unit securely If it is not attached correctly it could res...

Страница 7: ... 230 V Indoor unit Outdoor unit S2 S3 2 DC 12 V DC 24 V 1 A breaker with at least 3 mm contact separation in each poles shall be provided Use earth leakage breaker NV Make sure that the current leakage breaker is one compatible with higher harmonics Always use a current leakage breaker that is compatible with higher harmonics as this unit is equipped with an inverter The use of an inadequate break...

Страница 8: ...oller to stop the air conditioner Note that when the extension piping is very long with a large refrigerant amount it may not be possible to perform a pump down operation In this case use refrigerant recovery equipment to collect all of the refrigerant in the system If the extension piping length for the SUZ SA100VA is 20 m or longer it will not be possible to perform a pump down operation because...

Страница 9: ...uese Branch Portuguese Branch Avda do Forte 10 2799 514 Carnaxide Lisbon Portugal Avda do Forte 10 2799 514 Carnaxide Lisbon Portugal Spanish Branch Spanish Branch Carretera de Rubi 76 80 Apdo 420 08173 Sant Cugat del Valles Barcelona Spain Carretera de Rubi 76 80 Apdo 420 08173 Sant Cugat del Valles Barcelona Spain Scandinavian Branch Scandinavian Branch Hammarbacken 14 P O Box 750 SE 19127 Solle...

Отзывы: