background image

4

/

2

1

0

3

4

90°

2

1

0

/

0

/

/

0

3

0

1

2

1

A

4. Refrigerant piping work

Fig. 4-3

4.2. Flaring work

•  Main cause of gas leakage is defect in 

fl

 aring work.

  Carry out correct 

fl

 aring work in the following procedure.

4.2.1. Pipe cutting (Fig. 4-3)

•  Using a pipe cutter cut the copper tube correctly.

4.2.2. Burrs removal (Fig. 4-4)

•  Completely remove all burrs from the cut cross section of pipe/tube.
•  Put the end of the copper tube/pipe to downward direction as you remove burrs in 

order to avoid burrs drop in the tubing.

4.2.3. Putting nut on (Fig. 4-5)

• Remove 

fl

 are nuts attached to indoor and outdoor unit, then put them on pipe/tube 

having completed burr removal.
(not possible to put them on after 

fl

 aring work)

4.2.4. Flaring work (Fig. 4-6)

• Carry 

out 

fl

 aring work using 

fl

 aring tool as shown at the right.

Pipe diameter

(mm)

Dimension

A (mm)

B

+0

    (mm)

-0.4

When the tool for R410A is used

Clutch type

9.52

0 - 0.5

13.2

15.88

0 - 0.5

19.7

Firmly hold copper tube in a die in the dimension shown in the table at above.

4.2.5. Check (Fig. 4-7)

• Compare 

the 

fl

 ared work with a 

fi

 gure in right side hand.

•  If 

fl

 are is noted to be defective, cut off the 

fl

 ared section and do 

fl

 aring work again.

a

 Smooth all around

f

 Scratch on 

fl

 ared plane

b

 Inside is shining without any scratches

g

 Cracked

c

 Even length all around

h

 Uneven

d

 Too much

i

 Bad examples

e

 Tilted

•  Apply a thin coat of refrigeration oil on the seat surface of pipe. (Fig. 4-8)
•  For connection 

fi

 rst align the center, then tighten the 

fi

 rst 3 to 4 turns of 

fl

 are nut.

•  Use tightening torque table below as a guideline for indoor unit side union joint 

section, and tighten using two wrenches. Excessive tightening damages the 

fl

 are 

section.

Copper pipe O.D.

(mm)

Flare nut O.D.

(mm)

Tightening torque

(N·m)

ø9.52

22

34 - 42

ø15.88

29

68 - 82

 Warning:

When installing the unit, securely connect the refrigerant pipes before starting 
the compressor.

 Warning:

Be careful of 

fl

 ying 

fl

 are nut! (Internally pressurized)

Remove the 

fl

 are nut as follows:

1. Loosen the nut until you hear a hissing noise.
2.  Do not remove the nut until the gas has been completely released (i.e., hiss-

ing noise stops).

3. Check that the gas has been completely released, and then remove the nut.

Fig. 4-4

Fig. 4-5

Fig. 4-6

a

 Copper tubes

b

 Good

c

 No good

d

 Tilted

e

 Uneven

f

 Burred

a

 Burr

b

 Copper tube/pipe

c

 Spare reamer

d

 Pipe cutter

a

 Flare nut

b

 Copper tube

a

 Flaring tool

b

 Die

c

 Copper tube

d

 Flare nut

e

 Yoke

1

0

/

2

3

4

5

6

7

B

Fig. 4-7

Fig. 4-8

Содержание Mr. SLIM SUZ-SA100VA

Страница 1: ...AL DE INSTALACIÓN Para un uso correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado MANUALE DI INSTALLAZIONE Per un uso sicuro e corretto leggere attentamente il presente manuale ed il manuale d installazione dell unità interna prima di installare il condizionatore d aria EΓΧEIPIΔIO OΔHΓIΩN EΓKATAΣTAΣHΣ Γ...

Страница 2: ... relocating or servicing the air conditioner use only the specified refrigerant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines If air is mixed with the refrigerant then it can be the cause of abnormal high pressure in the refrigerant line and may result in an explosion and other hazards The use of any refrigerant other tha...

Страница 3: ... 1 Check that the difference between the heights of the indoor and outdoor units the length of refrigerant pipe and the number of bends in the pipe are within the limits shown below Model A Pipe length one way B Height difference C Number of bends one way SUZ SA71 SA100 Max 30 m Max 30 m Max of 10 Height difference limitations are binding regardless of which unit indoor or out door is positioned h...

Страница 4: ...e flared section and do flaring work again a Smooth all around f Scratch on flared plane b Inside is shining without any scratches g Cracked c Even length all around h Uneven d Too much i Bad examples e Tilted Apply a thin coat of refrigeration oil on the seat surface of pipe Fig 4 8 For connection first align the center then tighten the first 3 to 4 turns of flare nut Use tightening torque table ...

Страница 5: ...e then close the gage manifold valve and stop the vacuum pump Leave it as is for one or two minutes Make sure the pointer of the gage mani fold valve remains in the same position Confirm that the pressure gage show 0 101 MPa 760 mmHg Remove the gage manifold valve quickly from the service port of the stop valve After refrigerant pipes are connected and evacuated fully open all stop valves on gas a...

Страница 6: ...ply cable to the size given in the figure Be careful not to contact connecting cable with piping Caution Use care not to make miswiring Fig 5 3 Firmly tighten the terminal screws to prevent them from loosening After tightening pull the wires lightly to confirm that they do not move Warning Be sure to attach the service panel of the outdoor unit securely If it is not attached correctly it could res...

Страница 7: ... 230 V Indoor unit Outdoor unit S2 S3 2 DC 12 V DC 24 V 1 A breaker with at least 3 mm contact separation in each poles shall be provided Use earth leakage breaker NV Make sure that the current leakage breaker is one compatible with higher harmonics Always use a current leakage breaker that is compatible with higher harmonics as this unit is equipped with an inverter The use of an inadequate break...

Страница 8: ...oller to stop the air conditioner Note that when the extension piping is very long with a large refrigerant amount it may not be possible to perform a pump down operation In this case use refrigerant recovery equipment to collect all of the refrigerant in the system If the extension piping length for the SUZ SA100VA is 20 m or longer it will not be possible to perform a pump down operation because...

Страница 9: ...uese Branch Portuguese Branch Avda do Forte 10 2799 514 Carnaxide Lisbon Portugal Avda do Forte 10 2799 514 Carnaxide Lisbon Portugal Spanish Branch Spanish Branch Carretera de Rubi 76 80 Apdo 420 08173 Sant Cugat del Valles Barcelona Spain Carretera de Rubi 76 80 Apdo 420 08173 Sant Cugat del Valles Barcelona Spain Scandinavian Branch Scandinavian Branch Hammarbacken 14 P O Box 750 SE 19127 Solle...

Отзывы: