3. Installation diagram

2.1. Outdoor unit

•  Where it is not overly exposed to strong winds.

•  Where airflow is good and dustless.

•  Where neighbors are not annoyed by operation sound or hot air.

•  Where rigid wall or support is available to prevent the increase of operation sound 

or vibration.

•  Where there is no risk of combustible gas leakage.

•  If installing the unit in a location high above the ground, be sure to secure the unit 

legs.

•  Where it is at least 10 ft. (3 m) away from the antenna of TV set or radio. Opera-

tion of the air conditioner may interfere with radio or TV reception in areas where 

reception is weak. An amplifier may be required for the affected device.

•  Install the unit horizontally.

•  Please install it in an area not affected by snowfall or blowing snow. In areas with 

heavy snow, please install a canopy, a pedestal and/or baffle boards.

Note: 

•  It is advisable to make a piping loop near outdoor unit so as to reduce vibration.

•  For increased efficiency, install the outdoor unit in a location where continuous 

direct sunlight or excessive water can be avoided as much as possible.

 Caution:

When operating the air conditioner in low outside temperature, be sure to follow the 

instructions described below.

•  Never install the outdoor unit in a place where its air inlet/outlet side may be ex-

posed directly to wind.

•  To prevent exposure to wind, install the outdoor unit with its air inlet side facing 

the wall and a baffle board on the air outlet side.

Avoid the following places for installation where air conditioner trouble is liable to 

occur.

•  Where flammable gas could leak

•  Where there is an excessive amount of machine oil in the air.

•  Salty places such as the seaside.

•  Where sulfide gas is generated such as a hot spring.

•  Where there is high-frequency or wireless equipment.

The outdoor unit produces condensate during the heating operation. Select the in-

stallation place to ensure to prevent the outdoor unit and/or the grounds from being 

wet by drain water or damaged by frozen drain water.

2. Selecting the installation location

Open 2 sides of left,

right, or rear side.

4 in.

(100

mm)

or more

14 in.

(350

mm)

or more

8 in.

(200

mm)

or more

Basically open 4 in.

(100 mm) or more

without any obstruction

in front and on both

sides of the unit.

4 in.

(100 mm)

or more

m

m

:t

i

n

U

h

c

n

i

:t

i

n

U

31-1/2

19-11/16

Air inlet

Air outlet

13-9/16

11-1/4

2-3/8

×

13/16 slot

12-12-3/4

1-9/16

800
500

Air inlet

Air outlet

2-10

×

21 slot

344.5

285

150

40

304-325

5-

15/16

m

m

:t

i

n

U

h

c

n

i

:t

i

n

U

33-1/16

14-3/16

19-11/16

Air inlet

6-5/8

15-7/16

13

Air outlet

4-3/8 x 13/16 slot

1-9/16

40

840

169

500

Air inlet

392

330

360

Air outlet

4-10 x 21 slot

20 in. (500 mm)

or more

4 in.

(100

mm)

or more

4 in.

(100

mm)

or more

14 in.

(350

mm)

or more

20 in.

(500

mm)

or more

SUZ-KA09, KA12, KA15NA

SUZ-KA18NA

When the piping is to be attached to a wall containing metals (tin plated) or metal netting, use a chemically treated wooden piece 5/3 in. (0 mm) or thicker between the 

wall and the piping or wrap 7 to 8 turns of insulation vinyl tape around the piping.

Units should be installed by licensed contractor accordingly to local code requirement.

Note:

When operating the air conditioner in low outside temperature, be sure to follow the instructions described below.

•  Never install the outdoor unit in a place where its air inlet/outlet side may be exposed directly to wind.

•  To prevent exposure to wind, install the outdoor unit with its air inlet side facing the wall.

•  To prevent exposure to wind, it is recommended to install a baffle board on the air outlet side of the outdoor unit.

Drain piping for outdoor unit

Install the unit horizontally.

Do not use drain socket in cold regions. Drain may freeze and make the fan stop.

The outdoor unit produces condensate during the heating operation. Select the installation place to ensure to prevent the outdoor unit and/or the grounds from being 

wet by drain water or damaged by frozen drain water.

Содержание Mr.SLIM SUZ-KA09NA

Страница 1: ...talling the air conditioner unit MANUEL D INSTALLATION Avant d installer le climatiseur lire attentivement ce manuel ainsi que le manuel d installation de l appareil intérieur pour une utilisation sûre et correcte MANUAL DE INSTALACIÓN Para un uso correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado Fran...

Страница 2: ...t in the unit and could cause a fire or an electric shock When installing or relocating the unit make sure that no substance other than the specified refrigerant R410A enters the refrigerant circuit Any foreign substances in the refrigerant circuit can cause abnormal pressure rise or an explosion Do not discharge the refrigerant into the atmosphere Check that the refrig erant gas does not leak aft...

Страница 3: ...ct the in stallation place to ensure to prevent the outdoor unit and or the grounds from being wet by drain water or damaged by frozen drain water 2 Selecting the installation location Open 2 sides of left right or rear side 4 in 100 mm or more 14 in 350 mm or more 8 in 200 mm or more Basically open 4 in 100 mm or more without any obstruction in front and on both sides of the unit 4 in 100 mm or m...

Страница 4: ...0 mm or more Caution Be sure to use the insulation of specified thickness table on the above Excessive insulation may cause incorrect installation of the indoor unit and too little insulation may cause condensate to form The unit has flared connections on both indoor and outdoor sides Remove the valve cover from the outdoor unit then connect the pipe Refrigerant pipes are used to connect the indoo...

Страница 5: ...16 6 5 8 15 88 49 64 25 32 19 3 19 7 Fig 4 4 4 4 Purging procedures and leak test 1 Remove service port cap of stop valve on the side of the outdoor unit gas pipe 2 Connect gauge manifold valve and vacuum pump to service port of stop valve on the gas pipe side of the outdoor unit 3 Run the vacuum pump 15 minutes or more 4 Check the vacuum with the gauge manifold valve then close it and shut off th...

Страница 6: ...oor outdoor unit connecting wire A Service panel Lock nut Conduit cover Connector TB support Grounding terminal INDOOR UNIT Terminal block 208 230 V AC 1phase 60 Hz Grounding terminal Disconnect switch OUTDOOR UNIT Grounding terminal Ground Power supply 208 230 V AC 1phase 2wires 60 Hz Terminal block 1 Remark A disconnect switch is required Check the local code Use a ring tongue termi nal in order...

Страница 7: ...ith the applicable local and national code 2 Use copper supply wires 3 Use wires rated 600V or more for the power supply cables and the indoor outdoor unit connecting cables 4 Install an earth longer than other cables 6 1 Gas charge Fig 6 1 1 Connect gas cylinder to the service port of stop valve 3 way 2 Execute air purge of the pipe or hose coming from refrigerant gas cylinder 3 Replenish specifi...

Страница 8: ...ité veillez à ce qu aucune autre substance que le réfrigérant spécifié R410A ne pénètre dans le cir cuit de réfrigération La présence d une substance étrangère dans le circuit de réfrigération peut pro voquer une augmentation anormale de la pression voire une explosion Ne libérez pas le réfrigérant dans l atmosphère Vérifiez l absence de fuites de gaz réfrigérant une fois l installation terminée E...

Страница 9: ...viter à l unité extérieure et ou aux sols d être mouillés par les condensats ou endommagés par le gel des condensats 2 Choisir l emplacement de l installation 4 pouce 100 mm minimum 14 pouce 350 mm minimum 8 pouce 200 mm minimum 4 pouce 100 mm minimum m m Unité Unité pouce 31 1 2 19 11 16 Entrée d air 13 9 16 11 1 4 2 3 8 13 16 12 12 3 4 1 9 16 800 500 2 10 21 344 5 285 150 40 304 325 5 15 16 m m ...

Страница 10: ...doit être de 4 pouce 100 mm minimum Attention Utilisez toujours un matériau d isolation de l épaisseur spécifiée tableau à droite Une isolation trop épaisse peut être à l origine d une installation incorrecte de l unité interne une isolation trop fine peut provoquer la formation de condensation L unité comporte des raccordements évasés sur les faces intérieure et extérieure Retirez le couvercle de...

Страница 11: ...trique 2 Evaser les conduits de liquide et de gaz puis appliquer un fi lm mince d huile réfrigérante application sur site Avertissement Attention aux écrous évasés volants pressurisation interne Retirer l écrou évasé en procédant comme suit 1 Desserrer l écrou jusqu à ce qu un sifflement se fasse entendre 2 Ne jamais retirer l écrou tant que tout le gaz ne s est pas échappé c est àdire lorsque le ...

Страница 12: ... attention de brancher les fils correctement Serrer fermement les vis des bornes pour les empêcher de se desserrer Puis tirer légèrement sur les fils pour vous assurer qu ils ne bougent pas Avertissement Veiller à visser correctement le panneau de service à l appareil extérieur Si le panneau de service n est pas bien installé de l eau des poussières etc pourraient pénétrer à l intérieur de l appar...

Страница 13: ...n en cuivre 3 Utiliser des fils d une intensité nominale de 600V ou plus pour les câbles d alimentation et les câbles de raccordement de l appareil intérieur l appareil extérieur 4 Installer un câble de terre plus long que les autres câbles 6 1 Charge de Gaz Fig 6 1 1 Raccorder le tuyau de gaz au port de service de la vanne d arrêt à 3 voies 2 Purger l air du tuyau raccordé au tuyau de gaz réfrigé...

Страница 14: ... y producirse un incendio o una descarga eléctrica Al instalar o reubicar la unidad asegúrese de que no entra ninguna otra sustancia excepto el refrigerante especificado R410A en el circuito de refrigeración Cualquier sustancia extraña en el circuito de refrigeración puede provocar una elevación anómala de la presión o una explosión No descargue el refrigerante en el ambiente Una vez acabada la in...

Страница 15: ... instalación en el que la unidad exterior y las tomas de tierra no se humedezcan con agua de drenaje ni se dañen debido a la congelación de este agua de drenaje 2 Selección del lugar de instalación 4 pulg 100 mm o más 14 pulg 350 mm o más 8 pulg 200 mm o más 4 pulg 100 mm o más pulganda Unidad 31 1 2 19 11 16 Entrada de aire 13 9 16 11 1 4 Ranura de 2 3 8 13 16 12 12 3 4 1 9 16 800 500 Salida de a...

Страница 16: ...instalación incorrecta de la unidad interior y el uso de una cantidad insuficiente de aislante puede provocar la condensación Las unidad tiene conexiones abocinadas en los lados interior y exterior Retire la tapa de la válvula de la unidad exterior y a continuación conecte la tubería Las tuberías de refrigerante se emplean para conectar las unidades interior y exterior Tenga cuidado de no romper n...

Страница 17: ...ura de servicio de la válvula de retención situada en el lado de la tubería de gas de la unidad exterior 2 Conecte la válvula colectora de manómetro y la bomba de vacío al puerto de servicio de la válvula de retención en el lado de la tubería del gas de la unidad exterior 3 Ponga en funcionamiento la bomba de vacío durante 15 minutos o más 4 Compruebe el vacío con la válvula colectora de manómetro...

Страница 18: ...n en la figura Tenga cuidado de que el cable de conexión no haga contacto con los tubos Cuidado Asegúrese de no realizar un mal cableado Apriete firmemente los tornillos de la terminal para evitar que se aflojen Tras apretarlos tire ligeramente de los cables para confirmar que no se muevan Atención Asegúrese de fijar firmemente el panel de servicio de la unidad exterior Si no se monta correctament...

Страница 19: ...o superior para los cables de la fuente de alimentación y los cables de conexión de las unidades in terior exterior 4 Instale un cable de toma de tierra más largo que el resto de los cables 6 1 Carga de gas Fig 6 1 1 Conecte el cilindro de gas a la abertura de servicio de la válvula de parada de 3 vías 2 Purgue el aire del tubo o conducto procedente del cilindro de gas refrigerante 3 Vuelva a llen...

Страница 20: ...OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Please be sure to put the contact address telephone number on this manual before handing it to the customer BH79D173H02 Printed in Thailand ...

Отзывы: