background image

7

4. Installing the refrigerant piping

  Stop valve <Liquid side>

  Stop valve <Gas side>

 Service port

 Open/Close section

 Local pipe

  Sealed, same way for gas side

 Pipe cover

Do not use a wrench here.

     Refrigerant leakage may result.

Use two wrenches here.

Fig. 4-5

Fig. 4-6

Fig. 4-7

4.4. Refrigerant pipe airtight testing method (Fig.4-5)

(1) Connect the testing tools.
 •  

Make sure the stop valves 

 

 are closed and do not open them.

 •  

Add pressure to the refrigerant lines through the service port 

 of the liquid 

stop valve 

.

(2)  Do not add pressure to the specified pressure all at once; add pressure little by 

little.

 

  Pressurize to 0.5 MPa (5 kgf/cm

2

G), wait five minutes, and make sure the 

pressure does not decrease.

 

  Pressurize to 1.5 MPa (15 kgf/cm

2

G), wait five minutes, and make sure the 

pressure does not decrease.

 

  Pressurize to 4.15 MPa (41.5 kgf/cm

2

G) and measure the surrounding tem-

perature and refrigerant pressure.

(3)  If the specified pressure holds for about one day and does not decrease, the 

pipes have passed the test and there are no leaks.

 •  

If the surrounding temperature changes by 1 °C, the pressure will change by 
about 0.01 MPa (0.1 kgf/cm

2

G). Make the necessary corrections.

(4)  If the pressure decreases in steps (2) or (3), there is a gas leak. Look for the 

source of the gas leak.

4.5. Stop valve opening method

The stop valve opening method varies according to the outdoor unit model. Use the 
appropriate method to open the stop valves.
(1) Gas side of ZRP100-140 (Fig. 4-6)

  Remove the cap, pull the handle toward you and rotate 1/4 turn in a counter-

clockwise direction to open.

  Make sure that the stop valve is open comletely, push in the handle and rotate 

the cap back to its original position.

(2) Liquid side of ZRP100-140 and Gas/Liquid side of ZRP35-71 (Fig. 4-7)

  Remove the cap and turn the valve rod counterclockwise as far as it will go with 

the use of a 4 mm hexagonal wrench. Stop turning when it hits the stopper.

 

 (ø9.52: Approximately 10 revolutions)

  Make sure that the stop valve is open completely, push in the handle and rotate 

the cap back to its original position.

Refrigerant pipes are protectively wrapped for ZRP60-140
•  

The pipes can be protectively wrapped up to a diameter of ø90 before or after 
connecting the pipes. Cut out the knockout in the pipe cover following the groove 
and wrap the pipes. 

Pipe inlet gap for ZRP60-140
•  

Use putty or sealant to seal the pipe inlet around the pipes so that no gaps re-
main. (If the gaps are not closed, noise may be emitted or water and dust will 
enter the unit and breakdown may result.)

4.6. Addition of refrigerant

•  

Additional charging is not necessary if the pipe length does not exceed 30 m.

•  

If the pipe length exceeds 30 m, charge the unit with additional R410A refriger-
ant according to the permitted pipe lengths in the chart below.

 *  

When the unit is stopped, charge the unit with the additional refrigerant 
through the liquid stop valve after the pipe extensions and indoor unit have 
been vacuumized.

 

 

 When the unit is operating, add refrigerant to the gas check valve using a 
safety charger. Do not add liquid refrigerant directly to the check valve.

 *  

After charging the unit with refrigerant, note the added refrigerant amount on 
the service label (attached to the unit).

 

 

 Refer to the “1.5. Using R410A refrigerant air conditioners” for more informa-
tion.

•  

Be careful when installing multiple units. Connecting to an incorrect indoor unit 
can lead to abnormally high pressure and have a serious effect on operation 
performance.

Model

Permitted 

pipe  

length

Permitted 

vertical  

difference

Additional refrigerant charging amount

31 - 40 m 41 - 50 m 51 - 60 m 61 - 75 m

ZRP35, 50

-50 m

-30 m

0.2 kg

0.4 kg

ZRP60, 71

-50 m

0.6 kg

1.2 kg

ZRP100-140

-75 m

0.6 kg

1.2 kg

1.8 kg

2.4 kg

  Double spanner section

 

 (Do not apply a spanner other than to this section. 
Doing so would cause coolant leaks.)

 Seal section

 

 (Seal the end of the heat insulation material at 
the pipe connection section with whatever seal 
material you have on hand so that water does not 
infiltrate the heat insulation material.)

 Valve

 Unit side

 Handle

Cap

  Local pipe side

 Pipe cover

 Service port

 Wrench hole

Precautions when using the charge valve (Fig.4-8)

Do not tighten the service port too much when installing it, otherwise, the valve core 
could be deformed and become loose, causing a gas leak.
After positioning section 

 in the desired direction, turn section 

 only and tighten it.

Do not further tighten sections 

 and 

 together after tightening section 

.

* The figure to the left is an example only.
  The stop valve shape, service port position,
  etc., may vary according to the model.
* Turn section 

 only.

  (Do not further tighten sections 

 and 

   together.)

 Charge hose

 Service port

Fig. 4-8

(1)

(2)

 Warning:

When installing the unit, securely connect the refrigerant pipes before start-
ing the compressor.

Содержание Mr. Slim PUHZ-ZRP-HA

Страница 1: ...ding van het binnenapparaat zorgvuldig door voordat u met het installeren van de airconditioner begint MANUAL DE INSTALACIÓN Para un uso correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado MANUALE DI INSTALLAZIONE Per un uso sicuro e corretto leggere attentamente il presente manuale ed il manuale d inst...

Страница 2: ...m malfunction or unit breakdown In the worst case this could lead to a serious impediment to securing product safety Use only accessories authorized by Mitsubishi Electric and ask a dealer or an authorized technician to install them If accessories are incorrectly installed water leakage electric shock or fire may result Do not alter the unit Consult a dealer for repairs If alterations or repairs ar...

Страница 3: ...The refrigerant pipes are hot or cold depending on the condition of the flowing refrigerant If you touch the pipes burns or frostbite may result After stopping operation be sure to wait at least five minutes before turn ing off the main power switch Otherwise water leakage or breakdown may result 1 5 Using R410A refrigerant air conditioners Caution Use C1220 copper phosphorus for copper and copper a...

Страница 4: ...bove only Fig 2 13 No more than 3 units must be installed side by side In addition leave space as shown Do not install the optional air outlet guides for upward airflow Obstacles at front only Fig 2 14 When using an optional air outlet guide the clearance for ZRP100 140 models is 1000 mm or more Obstacles at front and rear only Fig 2 15 When using an optional air outlet guide the clearance for ZRP1...

Страница 5: ...Precautions for devices that use R410A refrigerant Refer to 1 5 for precautions not included below on using air conditioners with R410A refrigerant Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil applied to the flared sections Use C1220 copper phosphorus for copper and copper alloy seamless pipes to connect the refrigerant pipes Use refrigerant pipes with the thicknes...

Страница 6: ...he gas side Stop valve Use 2 wrenches to tighten the flare nut If order is reversed refrigerant leak occurs because of the part damaging by brazinig fire 4 Installing the refrigerant piping Fig 4 4 Front piping cover Piping cover Stop valve Service panel Bend radius 100mm 150mm 4 3 Refrigerant piping Fig 4 4 For ZRP35 50 Remove the service panel 1 screw For ZRP60 140 Remove the service panel 3 screw...

Страница 7: ...p the pipes Pipe inlet gap for ZRP60 140 Use putty or sealant to seal the pipe inlet around the pipes so that no gaps re main If the gaps are not closed noise may be emitted or water and dust will enter the unit and breakdown may result 4 6 Addition of refrigerant Additional charging is not necessary if the pipe length does not exceed 30 m If the pipe length exceeds 30 m charge the unit with addit...

Страница 8: ...he existing pipe thickness does not meet specifications or the pipes are damaged 4 Installing the refrigerant piping ZRP35 50 ZRP60 71 ZRP100 140 Drain socket PAC SJ08DS E PAC SH71DS E Drain pan PAC SG63DP E PAC SG64DP E PAC SH97DP E 5 Drainage piping work Outdoor unit drainage pipe connection When drain piping is necessary use the drain socket or the drain pan option Limits of refrigerant piping i...

Страница 9: ...r L N S1 S2 S3 ZRP60 140V L1 L2 L3 N S1 S2 S3 ZRP100 140Y Terminal block Indoor Outdoor connection terminal block S1 S2 S3 Service panel Clamp Clamp the cables so that they do not contact the center of the service panel or the gas valve Earth terminal ZRP35 50 ZRP35 50 Note If the protective sheet for the electrical box is removed during servicing be sure to reinstall it ZRP60 140 Caution Be sure ...

Страница 10: ...an inverter The use of an inadequate breaker can cause the incorrect operation of inverter 2 ZRP35 140 Max 45 m If 2 5 mm2 used Max 50 m If 2 5 mm2 used and S3 separated Max 80 m Use one cable for S1 and S2 and another for S3 as shown in the picture Max 50 m Total Max for PEA Wiring size 3 1 5 Polar 3 The 10 m wire is attached in the remote controller accessory 4 The figures are NOT always against ...

Страница 11: ...tarting operation Starting operation immediately after turning on the main power switch can result in severe damage to internal parts Keep the power switch turned on during the operational season The followings must be checked as well The outdoor unit is not faulty LED1 and LED2 on the control board of the out door unit flash when the outdoor unit is faulty Both the gas and liquid stop valves are c...

Страница 12: ...le there is no need of wiring Outdoor unit Indoor unit Master remote controller Subordinate remote controller Standard 1 1 Refrigerant address 00 Simultaneous twin Refrigerant address 01 Simultaneous triple Refrigerant address 02 SW 1 3 6 SW 1 3 6 SW 1 3 6 Fig 9 1 Because the unit automatically stops in about 2 to 3 minutes when the refriger ant collecting operation is completed LED1 off LED2 lit ...

Отзывы: