background image

12

1 2 3 4 5 6

9.1. Low noise mode (on-site modification) (Fig. 9-1)

By performing the following modification, operation noise of the outdoor unit can be
reduced by about 3-4 dB.
The low noise mode will be activated when a commercially available timer or the
contact input of an ON/OFF switch is added to the CNDM connector (option) on the
control board of the outdoor unit.
•  

The ability varies according to the outdoor temperature and conditions, etc.

  Complete the circuit as shown when using the external input adapter  

 

(PAC-SC36NA-E). (Option)

 SW7-1 (Outdoor unit control board): OFF

  SW1 ON: Low noise mode

 

SW1 OFF: Normal operation

  Circuit diagram example (low noise mode)

 On-site arrangement

  External input adapter (PAC-SC36NA-E)

X: Relay

  Outdoor unit control board

  Max. 10 m

  Power supply for relay

9.3. Refrigerant collecting (pump down)

Perform the following procedures to collect the refrigerant when moving the indoor 
unit or the outdoor unit.

  Supply power (circuit breaker).

 *  

When power is supplied, make sure that “CENTRALLY CONTROLLED” is not 
displayed on the remote controller. If “CENTRALLY CONTROLLED” is dis-
played, the refrigerant collecting (pump down) cannot be completed normally.

 *  

Start-up of the indoor-outdoor communication takes about 3 minutes after the 
power (circuit breaker) is turned on. Start the pump-down operation 3 to 4 
minutes after the power (circuit breaker) is turned ON.

  After the liquid stop valve is closed, set the SWP switch on the control board of 

the outdoor unit to ON. The compressor (outdoor unit) and ventilators (indoor 
and outdoor units) start operating and refrigerant collecting operation begins. 
LED1 and LED2 on the control board of the outdoor unit are lit.

 *  

Only set the SWP switch (push-button type) to ON if the unit is stopped. How-
ever, even if the unit is stopped and the SWP switch is set to ON less than 3 
minutes after the compressor stops, the refrigerant collecting operation can-
not be performed. Wait until compressor has been stopped for 3 minutes and 
then set the SWP switch to ON again.

*  Set the refrigerant address using the DIP switch of the outdoor unit.

  Wiring from the Remote Control

This wire is connected to TB5 (terminal board for remote controller) of the indoor 
unit (non-polar).

 When a Different Refrigerant System Grouping is Used.

Up to 16 refrigerant systems can be controlled as one group using the slim MA re-
mote controller.

Note:
In single refrigerant system (twin/triple), there is no need of wiring 

.

 Outdoor unit

 Indoor unit

  Master remote controller

  Subordinate remote controller

  Standard 1:1 (Refrigerant address = 00)

  Simultaneous twin (Refrigerant address = 01)

  Simultaneous triple (Refrigerant address = 02)

  SW 1 - 3 ~ 6

  SW 1 - 3 ~ 6

  SW 1 - 3 ~ 6

Fig. 9-1

  Because the unit automatically stops in about 2 to 3 minutes when the refriger-

ant collecting operation is completed (LED1 off, LED2 lit), be sure to quickly 
close the gas stop valve. If LED1 is lit and LED2 is off and the outdoor unit is 
stopped, refrigerant collection is not properly performed. Open the liquid stop 
valve completely, and then repeat step 

 after 3 minutes have passed.

 *  

If the refrigerant collecting operation has been completed normally (LED1 off, 
LED2 lit), the unit will remain stopped until the power supply is turned off.

 Turn off the power supply (circuit breaker).

 *  

Note that when the extension piping is very long with large refrigerant amount, 
it may not be possible to perform a pump-down operation. When performing 
the pump-down operation, make sure that the low pressure is lowered to near 
0 MPa (gauge).

 Warning:

When pumping down the refrigerant, stop the compressor before disconnect-
ing the refrigerant pipes. The compressor may burst if air etc. get into it.

10. System control (Fig. 10-1)

Fig. 10-1

SW1
Function table

 <SW1>

Function

Operation according to switch setting

ON

OFF

SW1
function 
settings

1 Compulsory 

defrosting

Start

Normal

2 Error history 

clear

Clear

Normal

3
4
5
6

Refrigerant 
system ad-
dress setting

Settings for outdoor unit addresses 
0 to 15

TB1

 

TB1

TB1

TB4

TB5

TB4

TB5

TB4

TB4

TB5

TB4

TB4

 ON
 OFF

 ON
 OFF

 ON
 OFF

3    4    5    6

3    4    5    6

3    4    5    6

 ON
 OFF

   Circuit diagram example (Demand function)

   On-site arrangement

X, Y: Relay

  External input adapter (PAC-SC36NA-E)

  Outdoor unit control board

  Max. 10 m

  Power supply for relay

9.2. Demand function (on-site modification) (Fig. 9-2)

By performing the following modification, energy consumption can be reduced to 0
–100% of the normal consumption.
The demand function will be activated when a commercially available timer or the
contact input of an ON/OFF switch is added to the CNDM connector (option) on the
control board of the outdoor unit.

  Complete the circuit as shown when using the external input adapter  

 

(PAC-SC36NA-E). (Option)

  By setting SW7-1 on the control board of the outdoor unit, the energy consump-

tion (compared to the normal consumption) can be limited as shown below.

SW7-1

SW2

SW3

Energy consumption 

Demand 

function

ON

OFF

OFF

100%

ON

OFF

75%

ON

ON

50%

OFF

ON

0% (Stop)

Fig. 9-2

9. Special functions

SW1

Orange

1

3

Brown

Red

CNDM

X

X

SW2

SW3

Orange

1

3

Brown

Red

CNDM

Y

X

X

Y

Содержание Mr. Slim PUHZ-ZRP-HA

Страница 1: ...ding van het binnenapparaat zorgvuldig door voordat u met het installeren van de airconditioner begint MANUAL DE INSTALACIÓN Para un uso correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado MANUALE DI INSTALLAZIONE Per un uso sicuro e corretto leggere attentamente il presente manuale ed il manuale d inst...

Страница 2: ...m malfunction or unit breakdown In the worst case this could lead to a serious impediment to securing product safety Use only accessories authorized by Mitsubishi Electric and ask a dealer or an authorized technician to install them If accessories are incorrectly installed water leakage electric shock or fire may result Do not alter the unit Consult a dealer for repairs If alterations or repairs ar...

Страница 3: ...The refrigerant pipes are hot or cold depending on the condition of the flowing refrigerant If you touch the pipes burns or frostbite may result After stopping operation be sure to wait at least five minutes before turn ing off the main power switch Otherwise water leakage or breakdown may result 1 5 Using R410A refrigerant air conditioners Caution Use C1220 copper phosphorus for copper and copper a...

Страница 4: ...bove only Fig 2 13 No more than 3 units must be installed side by side In addition leave space as shown Do not install the optional air outlet guides for upward airflow Obstacles at front only Fig 2 14 When using an optional air outlet guide the clearance for ZRP100 140 models is 1000 mm or more Obstacles at front and rear only Fig 2 15 When using an optional air outlet guide the clearance for ZRP1...

Страница 5: ...Precautions for devices that use R410A refrigerant Refer to 1 5 for precautions not included below on using air conditioners with R410A refrigerant Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil applied to the flared sections Use C1220 copper phosphorus for copper and copper alloy seamless pipes to connect the refrigerant pipes Use refrigerant pipes with the thicknes...

Страница 6: ...he gas side Stop valve Use 2 wrenches to tighten the flare nut If order is reversed refrigerant leak occurs because of the part damaging by brazinig fire 4 Installing the refrigerant piping Fig 4 4 Front piping cover Piping cover Stop valve Service panel Bend radius 100mm 150mm 4 3 Refrigerant piping Fig 4 4 For ZRP35 50 Remove the service panel 1 screw For ZRP60 140 Remove the service panel 3 screw...

Страница 7: ...p the pipes Pipe inlet gap for ZRP60 140 Use putty or sealant to seal the pipe inlet around the pipes so that no gaps re main If the gaps are not closed noise may be emitted or water and dust will enter the unit and breakdown may result 4 6 Addition of refrigerant Additional charging is not necessary if the pipe length does not exceed 30 m If the pipe length exceeds 30 m charge the unit with addit...

Страница 8: ...he existing pipe thickness does not meet specifications or the pipes are damaged 4 Installing the refrigerant piping ZRP35 50 ZRP60 71 ZRP100 140 Drain socket PAC SJ08DS E PAC SH71DS E Drain pan PAC SG63DP E PAC SG64DP E PAC SH97DP E 5 Drainage piping work Outdoor unit drainage pipe connection When drain piping is necessary use the drain socket or the drain pan option Limits of refrigerant piping i...

Страница 9: ...r L N S1 S2 S3 ZRP60 140V L1 L2 L3 N S1 S2 S3 ZRP100 140Y Terminal block Indoor Outdoor connection terminal block S1 S2 S3 Service panel Clamp Clamp the cables so that they do not contact the center of the service panel or the gas valve Earth terminal ZRP35 50 ZRP35 50 Note If the protective sheet for the electrical box is removed during servicing be sure to reinstall it ZRP60 140 Caution Be sure ...

Страница 10: ...an inverter The use of an inadequate breaker can cause the incorrect operation of inverter 2 ZRP35 140 Max 45 m If 2 5 mm2 used Max 50 m If 2 5 mm2 used and S3 separated Max 80 m Use one cable for S1 and S2 and another for S3 as shown in the picture Max 50 m Total Max for PEA Wiring size 3 1 5 Polar 3 The 10 m wire is attached in the remote controller accessory 4 The figures are NOT always against ...

Страница 11: ...tarting operation Starting operation immediately after turning on the main power switch can result in severe damage to internal parts Keep the power switch turned on during the operational season The followings must be checked as well The outdoor unit is not faulty LED1 and LED2 on the control board of the out door unit flash when the outdoor unit is faulty Both the gas and liquid stop valves are c...

Страница 12: ...le there is no need of wiring Outdoor unit Indoor unit Master remote controller Subordinate remote controller Standard 1 1 Refrigerant address 00 Simultaneous twin Refrigerant address 01 Simultaneous triple Refrigerant address 02 SW 1 3 6 SW 1 3 6 SW 1 3 6 Fig 9 1 Because the unit automatically stops in about 2 to 3 minutes when the refriger ant collecting operation is completed LED1 off LED2 lit ...

Отзывы: