background image

11

Caution:

Make sure to perform the “7. Test run” and confirm the unit works without 
any problems, before starting the following settings.

► How to select the “Refrigerant Leakage Detection” mode

Detection is possible regardless the unit’s operation (ON or OFF).

 Press             button for more than three seconds to switch to the maintenance

mode.
[Display    ] 

MAINTENANCE

► How to start the initial learning

 Press                          button and select the [GAS LEAK TEST START] (Fig. 8-2)

* The initial learning for the leakage detection is always done once after the new

installation or the data reset.

TEST

A

 CLOCK 

7. Test run

7.1. Before test run

►  After completing installation and the wiring and piping of the indoor and 

outdoor units, check for refrigerant leakage, looseness in the power sup-
ply or control wiring, wrong polarity, and no disconnection of one phase in 
the supply.

►  Use a 500-volt megohmmeter to check that the resistance between the 

power supply terminals and ground is at least 1 MΩ.

►  Do not carry out this test on the control wiring (low voltage circuit) termi-

nals.

 Warning:

Do not use the air conditioner if the insulation resistance is less than 1 MΩ.

Insulation resistance

After installation or after the power source to the unit has been cut for an extended 
period, the insulation resistance will drop below 1 M

 due to refrigerant accumulat-

ing in the compressor. This is not a malfunction. Perform the following procedures.
1.  Remove the wires from the compressor and measure the insulation resistance of 

the compressor.

2.  If the insulation resistance is below 1 M

, the compressor is faulty or the resis-

tance dropped due the accumulation of refrigerant in the compressor.

3.  After connecting the wires to the compressor, the compressor will start to warm 

up after power is supplied. After supplying power for the times indicated below, 
measure the insulation resistance again.

 •  

The insulation resistance drops due to accumulation of refrigerant in the com-
pressor. The resistance will rise above 1 M

 after the compressor is warmed 

up for four hours.

 

 

 (The time necessary to warm up the compressor varies according to atmo-
spheric conditions and refrigerant accumulation.)

 •  

To operate the compressor with refrigerant accumulated in the compressor, 
the compressor must be warmed up at least 12 hours to prevent breakdown.

4.  If the insulation resistance rises above 1 M

, the compressor is not faulty.

 Caution:

•  

The compressor will not operate unless the power supply phase connec-
tion is correct.

•  

Turn on the power at least 12 hours before starting operation.

-  

Starting operation immediately after turning on the main power switch can result 
in severe damage to internal parts. Keep the power switch turned on during the 
operational season.

►  The followings must be checked as well.

•  

The outdoor unit is not faulty. LED1 and LED2 on the control board of the out-
door unit flash when the outdoor unit is faulty.

•  

Both the gas and liquid stop valves are completely open.

•  

A protective sheet covers the surface of the DIP switch panel on the control 
board of the outdoor unit. Remove the protective sheet to operate the DIP 
switches easily.

7.2. Test run

7.2.1. Using SW4 in outdoor unit

SW4-1

ON

Cooling operation

SW4-2

OFF

SW4-1

ON

Heating operation

SW4-2

ON

*  After performing the test run, set SW4-1 to OFF.
•  

After power is supplied, a small clicking noise may be heard from the inside of 
the outdoor unit. The electronic expansion valve is opening and closing. The unit 
is not faulty.

•  

A few seconds after the compressor starts, a clanging noise may be heard from 
the inside of the outdoor unit. The noise is coming from the check valve due to 
the small difference in pressure in the pipes. The unit is not faulty.

The test run operation mode cannot be changed by DIP switch SW4-2 during 
the test run. (To change the test run operation mode during the test run, stop 
the test run by DIP switch SW4-1. After changing the test run operation mode, 
resume the test run by switch SW4-1.)

7.2.2. Using remote controller

Refer to the indoor unit installation manual.

Note : Occasionally, vapor that is made by the defrost operation may seem
           as if smoke come up from the outdoor unit.

8. Initial settings for refrigerant leakage detection function

[Display

]

Remote control button positions

D

A

C

B

Operation mode

Compressor information Outdoor unit information Indoor unit information

Confirm

Activate/cancel maintenance mode

GAS LEAK
JUDGE

GAS LEAK
TEST START 

Refrigerant leakage
detection judgment

Refrigerant
leakage detection
(initial teaching)

A

Fig. 8-1

Fig. 8-2

[Display 

] Waiting for stabilization

Stabilized

After 45 minutes

D

Fig. 8-3

Press

FILTER

 ( ) button to confirm. (Fig. 8-3)

How to finish the initial learning

Once the unit’s operation is stabilized, the initial learning is completed.

Press

TEST

 button for more than three seconds to cancel the initial learning.

The initial learning can also be cancelled by pressing 

ON/OFF

 button.

* Refer to the Technical Manual for the refrigerant leakage detection judgment method.

This air conditioner (outdoor unit) can detect refrigerant leakage which may happen
during a long period of use. In order to enable the leakage detection, the following
settings are required to let the unit memorize the initial conditions (initial learning).

Содержание Mr. Slim PUHZ-ZRP-HA

Страница 1: ...ding van het binnenapparaat zorgvuldig door voordat u met het installeren van de airconditioner begint MANUAL DE INSTALACIÓN Para un uso correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado MANUALE DI INSTALLAZIONE Per un uso sicuro e corretto leggere attentamente il presente manuale ed il manuale d inst...

Страница 2: ...m malfunction or unit breakdown In the worst case this could lead to a serious impediment to securing product safety Use only accessories authorized by Mitsubishi Electric and ask a dealer or an authorized technician to install them If accessories are incorrectly installed water leakage electric shock or fire may result Do not alter the unit Consult a dealer for repairs If alterations or repairs ar...

Страница 3: ...The refrigerant pipes are hot or cold depending on the condition of the flowing refrigerant If you touch the pipes burns or frostbite may result After stopping operation be sure to wait at least five minutes before turn ing off the main power switch Otherwise water leakage or breakdown may result 1 5 Using R410A refrigerant air conditioners Caution Use C1220 copper phosphorus for copper and copper a...

Страница 4: ...bove only Fig 2 13 No more than 3 units must be installed side by side In addition leave space as shown Do not install the optional air outlet guides for upward airflow Obstacles at front only Fig 2 14 When using an optional air outlet guide the clearance for ZRP100 140 models is 1000 mm or more Obstacles at front and rear only Fig 2 15 When using an optional air outlet guide the clearance for ZRP1...

Страница 5: ...Precautions for devices that use R410A refrigerant Refer to 1 5 for precautions not included below on using air conditioners with R410A refrigerant Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil applied to the flared sections Use C1220 copper phosphorus for copper and copper alloy seamless pipes to connect the refrigerant pipes Use refrigerant pipes with the thicknes...

Страница 6: ...he gas side Stop valve Use 2 wrenches to tighten the flare nut If order is reversed refrigerant leak occurs because of the part damaging by brazinig fire 4 Installing the refrigerant piping Fig 4 4 Front piping cover Piping cover Stop valve Service panel Bend radius 100mm 150mm 4 3 Refrigerant piping Fig 4 4 For ZRP35 50 Remove the service panel 1 screw For ZRP60 140 Remove the service panel 3 screw...

Страница 7: ...p the pipes Pipe inlet gap for ZRP60 140 Use putty or sealant to seal the pipe inlet around the pipes so that no gaps re main If the gaps are not closed noise may be emitted or water and dust will enter the unit and breakdown may result 4 6 Addition of refrigerant Additional charging is not necessary if the pipe length does not exceed 30 m If the pipe length exceeds 30 m charge the unit with addit...

Страница 8: ...he existing pipe thickness does not meet specifications or the pipes are damaged 4 Installing the refrigerant piping ZRP35 50 ZRP60 71 ZRP100 140 Drain socket PAC SJ08DS E PAC SH71DS E Drain pan PAC SG63DP E PAC SG64DP E PAC SH97DP E 5 Drainage piping work Outdoor unit drainage pipe connection When drain piping is necessary use the drain socket or the drain pan option Limits of refrigerant piping i...

Страница 9: ...r L N S1 S2 S3 ZRP60 140V L1 L2 L3 N S1 S2 S3 ZRP100 140Y Terminal block Indoor Outdoor connection terminal block S1 S2 S3 Service panel Clamp Clamp the cables so that they do not contact the center of the service panel or the gas valve Earth terminal ZRP35 50 ZRP35 50 Note If the protective sheet for the electrical box is removed during servicing be sure to reinstall it ZRP60 140 Caution Be sure ...

Страница 10: ...an inverter The use of an inadequate breaker can cause the incorrect operation of inverter 2 ZRP35 140 Max 45 m If 2 5 mm2 used Max 50 m If 2 5 mm2 used and S3 separated Max 80 m Use one cable for S1 and S2 and another for S3 as shown in the picture Max 50 m Total Max for PEA Wiring size 3 1 5 Polar 3 The 10 m wire is attached in the remote controller accessory 4 The figures are NOT always against ...

Страница 11: ...tarting operation Starting operation immediately after turning on the main power switch can result in severe damage to internal parts Keep the power switch turned on during the operational season The followings must be checked as well The outdoor unit is not faulty LED1 and LED2 on the control board of the out door unit flash when the outdoor unit is faulty Both the gas and liquid stop valves are c...

Страница 12: ...le there is no need of wiring Outdoor unit Indoor unit Master remote controller Subordinate remote controller Standard 1 1 Refrigerant address 00 Simultaneous twin Refrigerant address 01 Simultaneous triple Refrigerant address 02 SW 1 3 6 SW 1 3 6 SW 1 3 6 Fig 9 1 Because the unit automatically stops in about 2 to 3 minutes when the refriger ant collecting operation is completed LED1 off LED2 lit ...

Отзывы: