A-296
PERFORMANCE DA
TA
CEILING
CASSETTE PM
CEILING CASSETTE PM SERIES PMH-P1/P1.6/P2BA
HEATING CAPACITY (240V)
Outdoor intake air WB (
:
)
-10
-5
0
CA
P.C.
CA
P.C.
CA
P.C.
15
2,159
0.63
2,346
0.69
2,618
0.80
PMH-P1BA
20
2,074
0.68
2,244
0.74
2,482
0.86
25
2,006
0.72
2,176
0.81
2,380
0.93
15
3,175
1.00
3,450
1.11
3,850
1.28
PMH-P1.6BA
20
3,050
1.09
3,300
1.19
3,650
1.38
25
2,950
1.16
3,200
1.29
3,500
1.50
15
3,969
1.43
4,313
1.57
4,813
1.82
PMH-P2BA
20
3,813
1.55
4,125
1.69
4,563
1.96
25
3,688
1.65
4,000
1.84
4,375
2.13
Indoor
intake air
DB (
:
)
Model
NOTE:
CA: Capacity (W)
P.C.: Power consumption (kW)
Outdoor intake air WB (
:
)
5
10
15
CA
P.C.
CA
P.C.
CA
P.C.
15
3,434
0.95
3,876
1.06
4,318
1.14
PMH-P1BA
20
3,315
1.03
3,740
1.14
4,165
1.23
25
3,128
1.09
3,604
1.22
4,012
1.32
15
5,050
1.53
5,700
1.70
6,350
1.84
PMH-P1.6BA
20
4,875
1.65
5,500
1.84
6,125
1.97
25
4,600
1.75
5,300
1.96
5,900
2.12
15
6,313
2.18
7,125
2.42
7,938
2.61
PMH-P2BA
20
6,094
2.35
6,875
2.61
7,656
2.81
25
5,750
2.49
6,625
2.80
7,375
3.01
Indoor
intake air
DB (
:
)
Model